10
7014-285A
October 9, 2017
CB1200 Pellet Insert
NOTE: Clearances may only be reduced by
means approved by the regulatory authority
having jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
WARNING
0 to 5 inches from bottom of unit,
thermal protection required. R value of
3.0.
5 inches or more from bottom of unit,
ember protection only required
NOTE: Hearth Rug may be used in
Suggested Area
Figure 10.1
Thermal Resistance: R value
The R value is a measure of a material’s resistance to heat
transfer.
R value is convenient when more than one material is used
since you can add the R values together, whereas you can
not do this for k value.
The HIGHER the R factor means less heat is being conduct
-
ed through the non-combustible material to the combustible
material beneath it.
The R value of a material must be equal or larger then the
required R value to be acceptable.
NOTE
: A Quadra-Fire floor protector (Part 811-0730) is
available through your dealer to be used as a floor protector
for the section under the insert body only. Floor protection
to front and sides of insert appliance must be supplied in
addition to this part.
D. Floor Protection
1.
Zero Clearance Installations*
It is necessary to install a floor protection of non-combustible
material with a R value of 3.0 (1 inch [25mm] minimum thick-
ness with a “k” value of 0.58) or a 1 inch (25mm) air space
between insert base and hearth.
2.
Non-Zero Clearance Installations*
A non-combustible floor protector is required with a minimum
R value of 3.0 (1 inch [25mm] minimum thickness with a “k”
value of 0.58) extending 6 inches (153mm) in front of the
insert and 8 inches (203mm) to each side of the door open
-
ing.
* See Thermal Resistance: R value.