MT. VERNON AE INSERT

With proper installation, operation, and maintenance your appliance will provide years of trouble-free service. If you do 

experience a problem, this troubleshooting guide will assist a qualified service person in the diagnosis of a problem and 

the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician.

Error Message

Possible Cause

Corrective Action

Bad wall control or control board

3 wires have loose connections or installed wrong

Replace wall control or control board

Check connections

BAD TC DROP TUBE 

(TC = Thermocouple)

Drop tube thermocouple is broken or leads are 

reversed

Check connections
Replace thermocouple

BAD TC Fire pot

(TC = Thermocouple)

Fire pot thermocouple is broken or leads are reversed

Check connections
Replace thermocouple

SNAP DISC TRIPPED

Overheat sensor (snap disc #3) has tripped

Convection blower may need cleaning

Turn power off to appliance and manually reset snap disc then 

turn power back on
Clean convection blower if needed

VACUUM SW ERROR

(SW = Switch)

Appliance and venting is dirty plugged
Vacuum switch is bad
Vacuum hose is plugged/disconnected

Clean appliance and venting to appliance

Check connections.  Bypass vacuum with jumper wire, if runs, 

switch is bad. Replace switch
Check vacuum hose 

COMB BLOWER JAMMED

Combustion blower is blocked/jammed

Remove blockage
Replace blower if necessary
Must unplug appliance to clear error

AUGER JAMMED

Auger jammed, feed motor bad

Pull the feed system and inspect
Clear jam and Press Retry

MISSED IGNITION

Igniter bad or poor harness connection 

Out of fuel or fuel is bridging in hopper
Faulty fire pot thermocouple connection has shorted.
Ash plugging the igniter slot in the fire pot bottom and 

clear the slot

Check connections, if OK replace igniter
Break up bridging pellets.  Refill hopper

Replace the thermocouple

Press Retry
Use cleaning tool or a spoon to scrape ash

MIN Fire pot TEMP

Out of fuel

Refill hopper
Add handful of pellets to fire pot to prime it

Press Retry

MAX DROP TUBE TEMP

Appliance in over-heat condition  
Flame height set too high
Components may need cleaning

Confirm setting matches burning fuel
Adjust flame height
Clean the firebox, heat exchanger, convection blower, fire pot 

and ash pan

CONV BLOWER JAMMED

Convection blower blocked/jammed

Remove blockage
Replace blower if necessary
Must unplug appliance to clear error

CHECK ASH PAN

Auto-clean jammed

Auto-clean switch is bad
Linkage has become disconnected

If ash pan is empty, check for a jam. Use a screw driver and 

firmly push in the fire pot floor holes and flex spring and push 

toward home to release jam
Replace switch
Reconnect linkage

SCREEN GOES BLANK

Static discharge or nearby lightning or
Electric fast transients at the input mains

Wait 25 seconds and press any key to refresh the screen.

Hopper lid not closed all the way

Switch is out of adjustment (auger will not function)

Close the lid.  If that didn’t work replace the switch 
Adjust or replace switch

Firebox door is not latched properly

Adjust or replace door switch

Out of fuel

Check the fuel level, if OK the switch may be out, replace 

switch

Troubleshooting Guide

Summary of Contents for MT VERNON

Page 1: ...ldren away CAREFULLY SUPERVISE children in same room as fireplace Alert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clot...

Page 2: ...IONS OMNI Test Laboratories Inc has determined that this appliance complies with Canadian Standards Association CSA B415 1 and Title 40 of the U S Code of Federal Regulations Part 60 SubPart AAA OMNI...

Page 3: ...tdown Procedure 26 C General Maintenance and Cleaning 26 D Soot or Creosote Fire 30 E High Ash Fuel Content Maintenance 30 5 Troubleshooting Guide 31 6 Service Parts Replacement 32 A Glass Replacement...

Page 4: ...ectronic components and glass X X X Factory installed blowers X Molded refractory panels X Ignition Modules X Firepots burnpots mechanical feeders auger assemblies X Vent Free burners Vent Free cerami...

Page 5: ...ranging a warranty call Travel and shipping charges for parts are not covered by this warranty Limited Catalyst Warranty o For wood burning products containing a catalyst the catalyst will be warrante...

Page 6: ...to water or weather damage which is the result of but not limited LIMITATIONS OF LIABILITY have other rights which vary from state to state EXCEPT TO THE EXTENT PROVIDED BY LAW HHT MAKES NO EXPRESS W...

Page 7: ...er Settings MENU 1 At the starting screen press MENU 2 Highlight AUTO MANUAL OFF Press SELECT 3 Highlight MANUAL Press SELECT 4 Press DONE twice or wait 15 seconds for starting screen to re appear 1 A...

Page 8: ...ing screen to re appear 1 If the appliance has stopped operating check the wall control screen If it is showing Min Fire pot Temp the hopper has run out of fuel 2 Fill the hopper with fuel and press t...

Page 9: ...od Pellets Weighted average LHV efficiency using data collected during EPA emissions test Weighted average HHV efficiency using data collected during EPA emissions test A range of BTU outputs based on...

Page 10: ...earth Home Technologies Operating appliance without fully assembling all components Operating appliance without legs attached if supplied with appliance Do NOT Over fire If appliance or chimney connec...

Page 11: ...be Furnace of 750 C Material made of or surfaced with any of the following materials Wood Compressed Paper Plant Fibers Plastic Plywood OSB Sheet Rock drywall Any material that can ignite and burn fla...

Page 12: ...re your satisfaction Changing to Different Fuel Type Empty the hopper of the previous fuel Thoroughly vacuum hopper before filling with the new fuel Select the appropriate setting on the FUEL SELECTIO...

Page 13: ...ll the hopper The hopper lid must be completely closed to maintain proper vacuum and for the feed motor to operate An error ICON will appear on the wall control if the hopper lid is not properly close...

Page 14: ...tible objects in front of the appliance High temperatures may ignite clothing furniture or draperies Maintain a minimum clearance of 3 feet 914mm in front of appliance WARNING Fire Risk Do NOT operate...

Page 15: ...the battery back up mode Figure 15 2 L Ignition Cycles The appliance engine is controlled by the digital thermostat wall control The digital display on the wall control will tell you what your applia...

Page 16: ...Appliance will stop feeding fuel and allow fire to diminish Convection blower will continue to run until the appliance cools to appropriate temperature Appliance will begin the auto clean cycle 5 Auto...

Page 17: ...is is normal Clean the glass 3 Glass has turned dirty 3 Excessive build up of ash The lower burn settings will produce more ash the higher burn settings produce less The more it burns on low the more...

Page 18: ...Codes The status area is used to indicate the current status of the system It indicates if the system is running in automatic or manual cycle if it is turned on or off and where it is in the operatin...

Page 19: ...If the wall control is subjected to a static shock the screen may go blank If this happens wait 25 seconds and press any button This will reset the screen restore functionality and turn on the back l...

Page 20: ...en is used to set the level of heat produced whenever the wall control calls for heat Figure 16 3 The HEAT OUTPUT screen is not accessible in AUTOMATIC cycle AUTO MANUAL SETTINGS Manual Off Automatic...

Page 21: ...s now on the temperature value Set the desired temperature for the Wake period and press Set Next The highlight is now on the hour display for the Day period and the triangle has moved to the second l...

Page 22: ...Appliances F C TEMP Appliances is used to change from Fahrenheit to Celsius and back for the temperatures displayed b Flame Height Adjust FLAME HEIGHT ADJUST is used to adjust flame height fuel feed r...

Page 23: ...ed The message in the center will change between NORMAL and QUIET NORMAL allows the convection blower to reach maximum RPM at 135 degrees and QUIET at 165 degrees CONV BLOWER SPEED Normal Normal Quiet...

Page 24: ...n Battery Back Up A battery icon appears on your wall control to let you know you are now operating on battery power Figure 24 2 Fire must be manually lit as the appliance will no longer automatically...

Page 25: ...Ash Pan Burning Wood Pellets Every 5 bags of fuel OR X Ash Pan Burning Alternate Fuels Every 1 bag of fuel OR X Ash Removal from Firebox More frequently depending on the fuel type or ash build up OR...

Page 26: ...Burning biomass fuels may require a more through cleaning during the burn season e Excessive clinkers will eventually jam the auto clean system and generate an error message on the wall control Inspe...

Page 27: ...ble vapors and liquids clear of appliance WARNING Do NOT store flammable materials in the appliance s vicinity DO NOT USE GASOLINE LANTERN FUEL KEROSENE CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO ST...

Page 28: ...emble the crevice tool from the micro cleaning kit to attach to a Shop Vac Figure 28 3 d Use the crevice tool to finish cleaning the heat exchanger fins It is critical that the 2 exhaust exits at the...

Page 29: ...control screen says OFF and the appliance is allowed to cool b After burning approximately 1 ton of fuel you will need to clean the hopper to prevent sawdust and or fines build up c A combination of s...

Page 30: ...riodically during heating season By Qualified Service Technician Homeowner This chimney should be inspected periodically during the heating season to determine if a creosote build up has occurred If a...

Page 31: ...otor bad Pull the feed system and inspect Clear jam and Press Retry MISSED IGNITION Igniter bad or poor harness connection Out of fuel or fuel is bridging in hopper Faulty fire pot thermocouple connec...

Page 32: ...e up and then out toward you Figure 32 2 5 To replace the baffle place the 2 locating ears behind the bottom edge and tilt the baffle up and into place 6 The baffle must be centered in the firebox bef...

Page 33: ...replace the side set the bottom in first Squeeze the latch in an open position Place the cast side into position and then release the latch The latch hooks onto a bracket to hold the side in place Co...

Page 34: ...motor and impeller in the place of the old inside the housing on the appliance 10 Secure motor and impeller with 6 screws 11 Reconnect wires to control board and plug in appliance Loosen 6 screws 5 b...

Page 35: ...ill display on the wall control when the appliance has lost main power and is running on battery back up 4 Combustion Exhaust Blower The combustion exhaust blower is mounted in the bottom right rear o...

Page 36: ...s the convection blower on and off varies the speed of the convection blower and will shut down appliance if internal heat exceeds set temperature 21 Vacuum Switch The vacuum switch is located on the...

Page 37: ...9 10 n a 11 12 13 COMBUSTION BLOWER FEEDBACK COMBUSTION BLOWER WHITE BLUE GREEN THERMOCOUPLE THERMOCOUPLE THERMOSTAT WALL CONTROL LOW FUEL SENSOR WHITE RED YELLOW BLACK BLACK YELLOW BLACK BLACK BLACK...

Page 38: ...Baffle Ash Pan Fire pot Thermocouple Thermocouple Cover Baffle Firepot Ash Pan Thermocouple and Thermocouple Cover Heat Exchanger Front Back Power Supply Control Board Convection Blower Drop Tube Low...

Page 39: ...August 13 2018 7036 187M 39 MT VERNON AE INSERT F Service and Maintenance Log Date of Service Performed By Description of Service...

Page 40: ...acturing Date Sept 2006 Ending Manufacturing Date Active Advanced Energy Pellet Insert MTVERNINSAE CSB MTVERNINSAE MBK MTVERNINSAE PMH MTVERNINSAE CWL Sept 2006 thru June 2011 Part number list on foll...

Page 41: ...atch Clip 7036 146 5 Elbow Catch 7000 393 6 Bracket Catch 7036 145 7 Glass Assembly Side 1 Piece 5 7 8 in W x 9 in H Interchangeable SRV414 5380 Y Gasket Channel 3 Mm X 32 Field Cut to Size 10 Ft 7000...

Page 42: ...1 W x 14 H 7034 007 Y Gasket Channel 3 Mm X 32 Field Cut to Size 10 Ft 7000 377 10 Y Tape Door Corner Field Cut to Size 1 Ft SRV7027 227 Y 19 7 Glass Retainer 7034 136 20 Ash Pan Door SRV7034 133 21 A...

Page 43: ...7000 714 10 Y 31 Control Board Assembly SRV7000 456 Y Fuse 15A Slow Iec Glass Pkg of 10 7000 491 10 Y 32 Convection Blower SRV7000 260 Y 33 Gasket Blower Convection SRV7000 329 34 Detent Pin Pre 00700...

Page 44: ...6 Auto Clean Link Arm 7034 176 Y 39 7 Plow Weldment Auto Clean SRV7034 024 Y 39 8 Rail Auto Clean SRV7034 152 Y 39 9 Spring Pkg of 4 7000 513 4 Y 39 10 Hitch Pin Clip 3 32 Pkg of 10 7000 374 10 Y 39 1...

Page 45: ...ut Tool 414 1140 Y Paint Touch Up Pre HF1910001 812 0910 Post HF1910001 3 42 19905 Sienna Bronze TOUCHUP CSB No longer available TOUCHUP CWL Mahogany 855 1450 Power Cord 812 1180 Y Thermostat Wire 3 C...

Page 46: ...s Ignitor SRV7034 273 Y Wire Harness Power Out Ac AC Current SRV7034 220 Y Wire Harness Power Out Dc DC Current SRV7034 221 Y Wire Harness Power Supply Receptacle SRV7034 233 Y Wire Harness Snap Disc...

Page 47: ...K 3 Surround Std Panel For Cast Trim SP MTVS CST Component Pack 7036 041 Surround Std Panel w Gold Trim No Longer Available SP MTVS GD Component Pack 7036 042 Trim Panel Set Gold SRV250 4660 Surround...

Page 48: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Reviews: