background image

Page  40

Quadra-Fire  •  GARNET-T  •  7016-127 Rev. i  •  12/11

10

Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do 
experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the 
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician.

Symptom

Possible Cause

Corrective Action

1.  After repeated trig-
gering of the piezo 
button, the spark ignitor 
will not light the pilot.

a.  Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode 
wire is properly connected, replace the ignitor.

b.  Defective pilot or 
misaligned electrode 
(spark at electrode).

Using a match, light the pilot. If the pilot lights, turn off the pilot and 
trigger the piezo button again. If the pilot lights, an improper gas/air 
mixture caused the bad lighting and a longer purge period is recom-
mended. If the pilot will not light, ensure the gap at the electrode and 
pilot is one-eighth (1/8) inch to have a strong spark. If the gas is OK, 
replace the pilot.

c.  No gas or low gas 
pressure.

Check the remote shut-off valve from the appliance. Usually, there is 
a valve near the gas main. There can be more that one (1) valve from 
the appliance and the main.

d.  No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.  The pilot will not stay 
lit after carefully follow-
ing the lighting instruc-
tions.

a.  Defective thermo-
couple.

Check that the pilot fl ame impinges on the thermocouple. Clean and /
or adjust the pilot for maximum fl ame impingement.

Ensure that the thermocouple connection at the gas valve is fully 
inserted and tight (hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt lead 
wire on the tip of the thermocouple and the other meter wire on the 
thermocouple copper lead. Start the pilot and hold the valve knob in. If 
the millivolt reading is less than 15mV, replace the thermocouple.

b.  Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty 
valve.

3.  The pilot is burning, 
there is no gas to the 
burner, the valve knob is 
in the ON position, and 
the ON/OFF switch is in 
the ON position.

a.  ON/OFF switch or 
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the 
jumper wires across the terminals at the switch. If the burner comes on, 
replace the defective switch. If the switch is OK, place the jumper wires 
across the switch wires at the gas valve. IF the burner comes on, the 
wires are faulty or connections are bad.

b.  Thermopile may 
not be generating 
suffi cient millivoltage.

If the pilot fl ame is not close enough physically to the thermopile, adjust 
the pilot fl ame.

Be sure the wire connections from the thermopile at the gas valve ter-
minals are tight and that the thermopile is fully inserted into the pilot 
bracket. 

Check the thermopile with a millivolt meter. Take the reading at TH-
TP&TP terminals of the gas valve. The meter should read 325 millivolts 
minimum, while holding the valve knob depressed in the pilot position, 
with the pilot lit, and the ON/OFF switch in the OFF position. Replace 
the faulty thermopile if the reading is below the specifi ed minimum.

With the pilot in the ON position, disconnect the thermopile leads from 
the valve. Take a reading at the thermopile leads. The reading should 
be 325 millivolts minimum. Replace the thermopile if the reading is 
below the minimum.

Summary of Contents for GARNET-MBK

Page 1: ...This appliance may be installed as an OEM installation in manu factured home USA only or mobile home and must be installed in accordance with the manufacturer s instructions and the manufac tured hom...

Page 2: ...00 0 610m aux tats Unis et au Canada pour les altitudes de 0 4500 0 1370m Pour les altitudes au dessus de 2000 aux tats Unis la configuration du ventilateur son orifice ou les deux peuvent possiblemen...

Page 3: ...Conversions 25 B Gas Pressures 27 C Gas Connection 27 Section 7 Electrical Information A Recommendation for Wire 29 B Connecting to the Appliance 29 C Standing Pilot Ignition System Wiring 29 Section...

Page 4: ...use this appliance if any part has been under water Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been...

Page 5: ...t vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL...

Page 6: ...e 33 Remove log set and component pack from firebox Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starting the instal...

Page 7: ...learances Figure 3 1 Model A B C D E F G H Garnet T Inches 6 2 2 43 36 30 19 1 2 19 3 8 Millimeters 152 51 51 1092 914 762 495 492 NOTE Flooring beneath appliance may reach 90 degrees plus room ambien...

Page 8: ...G Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 0 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 0 Over 12 12 to 14 12 5...

Page 9: ...IN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMA X 2 termination caps xQACTUAL N 6 inches non vinyl...

Page 10: ...Diagonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45 elbows may b...

Page 11: ...line of the flue pipe to the center of the 90 elbow On the graph below draw a horizontal line from that measurement on the vertical axis across until it intersects with the slanted line 2 From the po...

Page 12: ...ers are not in the way when the venting system is attached If this is the case you may want to adjust the location of the appliance Step 2 Direct vent pipe is designed with a locking connection To con...

Page 13: ...quare draw a 14 in x 14 in 356mm x 356mm square around the pilot hole in the siding See Figure 5 7 on the next page Step 3 For installations using a round support box wall thimble check pipe manufactu...

Page 14: ...area where the standoff will be located Burn Risk Local codes may require installation of a cap shield to prevent anything or anyone from touching the hot cap WARNING WARNING Do NOT connect a pipe se...

Page 15: ...ent Pipe Figure 5 10 VERTICAL TERMINATION CAP STORM COLLAR FLASHING FIRESTOP PIPE LENGTH SUPPORT BOX Step 2 Set the gas appliance in its desired location Drop a plumb bob down from the ceiling to the...

Page 16: ...that for steep roof pitches the vent height must be increased See Roof Pitch Table Figure 4 3 on page 8 In high wind conditions nearby trees adjoining rooflines steep pitched roofs and other similar...

Page 17: ...occupied areas above the first floor including closets and storage spaces which the vertical vent passed through must be enclosed The enclosure may be framed and sheetrocked with standard construction...

Page 18: ...edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 7 Complete the cathedral ceiling installation by following the same...

Page 19: ...e retro connector and attach it to the support box with sheet metal screws Step 7 The connection between the appliance and the retro connector may be completed with sections of direct vent pipe 3 Clas...

Page 20: ...ion Cap 25 ft 8m of 3 in 76mm Flex Liner Exhaust Section 4 ft 1m of 3 in 102mm Flex Liner Air Intake Section Chimney must be sealed from 4 ft 1m section to termination using a smoke shelf or a damper...

Page 21: ...of flex above the existing chimney to allow for connection to the termination kit NOTE FOR HEARTHAPPLICATIONS REFER TO PAGE 19 FOR THE USE OF A CO AXIAL TO CO LINEAR APPLIANCE CONNECTOR Step 3 Secure...

Page 22: ...Secure the top adapter to the flashing Use three sheet metal screws through the side of the top adapter into the flange on the flashing Figure 5 28 Twist lock the high wind termination cap on to the t...

Page 23: ...t shield and into the brackets on the trim ring Figure 5 34 When installing the trim ring heat shield assem bly make sure the trim ring is centered in the hole and that the shield is above the pipe Th...

Page 24: ...WALL INTERIOR WALL 2 IN 51MM CLEARANCE FROM REAR OF STOVE 90 ELBOW PIPE LENGTH PIPE LENGTH center line TRIM RING SOLID OR VENTILATED TERMINATION CAP Place mark where protrudes through exterior wall t...

Page 25: ...NOTE Do not remove the wire clip Figure 6 3 Use a 5 32 in Allen wrench to remove the pilot injector Replace pilot injector with the appropriate size injector supplied with the appliance 35 for Propan...

Page 26: ...exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of...

Page 27: ...mponents please consult local codes for compliance NOTE The gap between the supply piping and gas access hole may be plugged with non combustible insulation to prevent cold air infiltration C Gas Conn...

Page 28: ...nd connections Do not use open flame After the gas line installation is complete all connections must be tightened and checked for leaks with a commercially available non corrosive leak check solution...

Page 29: ...of appliance 4 Use low resistance thermostat wire for wiring from igni tion system to the wall switch and thermostat 5 Use the following chart for wire sizing 6 Keep wire lengths as short as possible...

Page 30: ...ors can cause improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation CAUTION...

Page 31: ...just legs up and down to desired level C Flue Restrictor Installation Figure 8 4 Installation of the flue restrictor requires the removal of the baffle located inside the firebox Remove the baffle by...

Page 32: ...f unit and set aside Remove cast face by sliding straight up and set aside Remove the glass by releasing the latch located on the top of the appli ance Lean glass frame forward and lift out Place the...

Page 33: ...back shield by removing the two screws along the top of the shield Place the blower on the floor behind the appliance and route the ends of the wiring harness through the rubber grommet on the undersi...

Page 34: ...e appliance has heated up enough to activate the snap disc This can take up to 15 minutes depending on the temperature of the room Likewise the blower will not turn off until the appliance has cooled...

Page 35: ...ra Fire GARNET T 7016 127 Rev i 12 11 Figure 8 15 Blower Wiring Diagram Fan Speed Control Thermal Disc 110 VAC Power Cord BLAC K Bushing Strain Relief GREEN BLACK Ground Fan Assembly BLACK BLACK WHITE...

Page 36: ...ward toward the front of the appliance To OPEN the damper push the wingnut back Adust the damper in 1 4 in increments until the desired flame is achieved After adjustment tighten the nut Figure 8 17 L...

Page 37: ...the baffle adjustment Ensure that there are no gas leaks Ensure that the glass is sealed and in the proper posi tion Ensure that the flow of combustion and ventilation air is not obstructed front gri...

Page 38: ...the power from the appliance 4 Open the door of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five 5...

Page 39: ...etectors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if appl...

Page 40: ...thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple...

Page 41: ...g exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to p...

Page 42: ...hing or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL R...

Page 43: ...necessary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect for plu...

Page 44: ...sion Diagram Dimensions are actual appliance dimensions Use for reference only For clearances refer to Section 3 Figure 12 1 Appliance Dimensions A B F C D E Location Inches Millimeter Location Inches...

Page 45: ...1 4 in 235mm 6 1 2 in 165mm 6 5 8 in 168mm 17 24 in 432 610mm 11 3 4 in 298mm 5 3 4 in 146mm 6 5 8 in 168mm 6 3 8 in 162mm 6 1 2 in 165mm 9 5 8 in 244mm 6 5 8 in 168mm 6 1 2 in 165mm 6 3 8 in 162mm 9...

Page 46: ...lack SLP36 BK 46 DVA 36B 48 Pipe Length Galvanized SLP48M 46 DVA 48 48 Pipe Length Black SLP48 BK 46 DVA 48B Adjustable Length 3 6 Black SLP6A BK Adjustable Length 3 6 Galvanized SLP6AM Adjustable Len...

Page 47: ...i d a R e v i t a r o c e D Firestop Spacer Ceiling Firestop SLP FSM 46DVA FS Flex Trap Cap with Firestop SLP FLEX TRAP Flex Trap Cap with Firestop and 30 Flex Pipe SLP FLEX TRAP30 Masonry Chimney Con...

Page 48: ...rcelain Mahogany 839 1140 4 02 5 04 Porcelain Midnite Blue 839 1150 4 02 4 04 839 1151 4 03 5 04 Powder Coat Linden Green GARNET D CLG 6 04 4 06 Color SKU No Mfg Dates Powder Coat Merlot GARNET D CME...

Page 49: ...ize Qty 10 Ft 844 3010 Y Tape Door Corner Field Cut to Size Qty 1 Ft SRV7027 227 Y 9 Front Plate Solitaire Front Only Black 464 0160 10 Front Quartet Front Black 7016 106MBK Specify Color 7016 106POR...

Page 50: ...ize Qty 10 Ft 844 3010 Y Tape Door Corner Field Cut to Size Qty 1 Ft SRV7027 227 Y 9 Front Plate Solitaire Front Only Black 464 0160 10 Front Quartet Front Black 7016 106MBK Specify Color 7016 106POR...

Page 51: ...Valve Mineral Wool Pilot Injector Ez Lp 35 Conversion Regulator Label Orifice Plug Insert 56 Leveling Assembly Snap Disc Bracket Warranty Card Manual Restrictor Touch Up Paint Fasteners Black 7016 00...

Page 52: ...l purchase In the case of new home construction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dea...

Page 53: ...I QRUPDO XVH V D KHDWLQJ DSSOLDQFH VRPH FKDQJHV LQ FRORU RI LQWHULRU DQG H WHULRU VXUIDFH ILQLVKHV PD RFFXU 7KLV LV QRW D IODZ DQG LV QRW FRYHUHG XQGHU ZDUUDQW DPDJH WR SULQWHG SODWHG RU HQDPHOHG VXUI...

Page 54: ...understand and follow these instruc tions for safe installation and operation Leave this manual with party responsible for use and operation R Quadra Fire GARNET T 7016 127 Rev i 12 11 This product m...

Reviews: