background image

Page  36

10/08

Quadra-Fire  •  Columbia Bay  •  250-5195 Rev. K

10

Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do 
experience a problem, this troubleshooting guide will assist a qualifi ed service person in the diagnosis of a problem and the 
corrective action to be taken. This troubleshooting guide can only be used by a qualifi ed service technician.

Symptom

Possible Cause

Corrective Action

1.  After repeated trig-
gering of the piezo 
button, the spark ignitor 
will not light the pilot.

a.  Defective ignitor.

Check the spark at the electrode and pilot. If no spark and electrode 
wire is properly connected, replace the ignitor.

b.  Defective pilot or 
misaligned electrode 
(spark at electrode).

Using a match, light the pilot. If the pilot lights, turn off the pilot and 
trigger the piezo button again. If the pilot lights, an improper gas/air 
mixture caused the bad lighting and a longer purge period is recom-
mended. If the pilot will not light, ensure the gap at the electrode and 
pilot is one-eighth (1/8) inch to have a strong spark. If the gas is OK, 
replace the pilot.

c.  No gas or low gas 
pressure.

Check the remote shut-off valve from the appliance. Usually, there is 
a valve near the gas main. There can be more that one (1) valve from 
the appliance and the main.

d.  No LP in tank.

Check the LP (propane) tank. You may be out of fuel.

2.  The pilot will not stay 
lit after carefully follow-
ing the lighting instruc-
tions.

a.  Defective thermo-
couple.

Check that the pilot fl ame impinges on the thermocouple. Clean and /or 
adjust the pilot for maximum fl ame impingement.

Ensure that the thermocouple connection at the gas valve is fully 
inserted and tight (hand tighten plus 1/4 turn).

Disconnect the thermocouple from the valve, place one millivolt lead 
wire on the tip of the thermocouple and the other meter wire on the 
thermocouple copper lead. Start the pilot and hold the valve knob in. If 
the millivolt reading is less than 15mV, replace the thermocouple.

b.  Defective valve.

If the thermocouple is producing more than 15 millivolts, replace faulty 
valve.

3.  The pilot is burning, 
there is no gas to the 
burner, the valve knob is 
in the ON position, and 
the ON/OFF switch is in 
the ON position.

a.  ON/OFF switch or 
wires defective.

Check the ON/OFF switch and wires for proper connections. Place the 
jumper wires across the terminals at the switch. If the burner comes on, 
replace the defective switch. If the switch is OK, place the jumper wires 
across the switch wires at the gas valve. IF the burner comes on, the 
wires are faulty or connections are bad.

b.  Thermopile may 
not be generating 
suffi cient millivoltage.

If the pilot fl ame is not close enough physically to the thermopile, adjust 
the pilot fl ame.

Be sure the wire connections from the thermopile at the gas valve ter-
minals are tight and that the thermopile is fully inserted into the pilot 
bracket. 

Check the thermopile with a millivolt meter. Take the reading at TH-TP 
& TP terminals of the gas valve. The meter should read 325 millivolts 
minimum, while holding the valve knob depressed in the pilot position, 
with the pilot lit, and the ON/OFF switch in the OFF position. Replace 
the faulty thermopile if the reading is below the specifi ed minimum.

With the pilot in the ON position, disconnect the thermopile leads from 
the valve. Take a reading at the thermopile leads. The reading should 
be 325 millivolts minimum. Replace the thermopile if the reading is 
below the minimum.

Summary of Contents for Direct Vent Gas Appliance COLBAY-FS-B

Page 1: ...stalledasanOEM installation in manufactured home USAonly or mobile home and must be installed in accordance with the manufacturer s instructions and the manufactured home con struction and safety stan...

Page 2: ...1 02 Le canada tuyau minimum 65 42 NG 65 96 LP APPROUV POUR LE CANADA ET LES TATS UNIS ANSI Z21 88a 2001 CSA 2 33a M01 Fournaises au Gaz avec Ventilation et les sections applicable de UL 307b Appareil...

Page 3: ...rtical Termination 15 Section 6 Gas Information A Fuel Conversions 22 B Gas Pressures 24 C Gas Connection 24 Section 7 Electrical Information A Recommendation for Wire 26 B Connecting to the Appliance...

Page 4: ...nput BTU Minimum Input BTU Orifice Size DMS Efficiency Up To P 4 Columbia Bay FS NG 30 000 21 000 36 84 65 42 Columbia Bay FS LP 30 000 24 500 52 86 65 96 Manufactured Home or Mobile Home installation...

Page 5: ...ust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF A...

Page 6: ...ro tective surface Remove log set and component pack from firebox Report to your dealer any parts damaged in shipment particularly the condition of the glass Read all of the instructions before starti...

Page 7: ...RNING B Clearances Figure 3 1 Model A A B C D E F G H I Columbia Bay FS Inches 6 6 3 4 2 6 14 2 84 19 36 36 Millimeters 152 171 515 152 356 51 2134 483 914 914 NOTE Flooring beneath appliance may reac...

Page 8: ...DISCHARGE OPENING 2 FT MIN 20 INCHES MIN H MIN MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING Roof Pitch H Min Ft Flat to 6 12 1 0 Over 6 12 to 7 12 1 25 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12...

Page 9: ...___________________________________________ _ _ QMIN RMAX 1 cap 3 feet 2 x Q ACTUAL 2 caps 6 feet 1 x Q ACTUAL 3 caps 9 feet 2 3 x Q ACTUAL 4 caps 12 feet 1 2 x Q ACTUAL QMIN termination caps x 3 RMA...

Page 10: ...flue WARNING Diagonal runs have both vertical and horizontal vent aspects when calculating the effects Use the rise for the vertical aspect and the run for the horizontal aspect See Figure 5 1 Two 45...

Page 11: ...l dimension from the center line of the flue vent to the center of the 90 elbow is 7 ft 2m the horizontal run to the outer wall flange must not exceed 13 ft 4m EXAMPLE 2 If the vertical dimension from...

Page 12: ...s per installation instructions Connect vent sections per installation instructions Maintain all clearances to combustibles Do NOT allow vent to sag below connection point to appliance Maintain specif...

Page 13: ...c around its outside edges so as to make a seal between it and the wall attach termination cap to the exterior wall with the four wood screws provided The arrow on the vent cap should be pointing up F...

Page 14: ...on cap must be sealed with silicone Termination caps shall not be recessed into a wall or siding Fire Risk Explosion Risk Maintain vent clearance to combustibles as specified WARNING Do not pack air s...

Page 15: ...TIONAL RESTRICTION This installation may not have two horizontal sections connected by 90 elbows Figure 5 12 Step 1 Check the installation instructions for required 1 in 25mm clearances air space to c...

Page 16: ...e and elbow connections are in their fully twist locked position Assemble as instructed NOTE 1 If an offset is necessary in the attic to avoid obstructions it is important to support the vent pipe eve...

Page 17: ...ween the storm collar and the pipe OPTIONAL HIGH WIND TERMINATION CAP SECURE FLASHING WITH NON HARDENING SEALANT AND ROOFING NAILS Figure 5 16 MIN 1 in 25mm CLEARANCE CEILING FIRESTOP NAILS MIN 1 in 2...

Page 18: ...he top edges of the support box to make a seal between it and the roof Clean out any combustible material from inside the support box Step 7 Complete the cathedral ceiling installation by following th...

Page 19: ...8 in 3mm diameter holes through the top adapter and into the chimney top Ensure that you are drilling into the metal on the chimney Twist lock the high wind termination cap onto the top adapter Figure...

Page 20: ...framed a wall thimble is required This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles Figure 5 26 Step 3 Secure the flashing to the top...

Page 21: ...that the connector is centered in the opening and the mounting holes line up with the masonry wall Step 8 Secure the top adapter to the flashing Use three sheet metal screws through the side of the t...

Page 22: ...t pilot injector valve regulator conversion label TOOLS REQUIRED Power drill a 90 handle is helpful 2 Phillips bit 5 32 in Allen wrench 5 8 in open end wrench If the shutter is removed with the burner...

Page 23: ...actly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of th...

Page 24: ...sachusetts approved 1 2 inch 13mm T handle manual shut off valve and flexible gas connector are connected to the 1 2 inch 13mm control valve inlet If substituting for these components please consult l...

Page 25: ...and connections Do not use open flame After the gas line installation is complete all connections must be tightened and checked for leaks with a commercially available non corrosive leak check soluti...

Page 26: ...mostat 5 Use the following chart for wire sizing 6 Keep wire lengths as short as possible by removing any excess wire length 7 Low voltage and 110 VAC voltage cannot be shared within the same wall box...

Page 27: ...can cause improper and dangerous operation Verify proper operation after servicing Shock hazard Replace damaged wire with type 105O C rated wire Wire must have high temperature insulation CAUTION Red...

Page 28: ...sed safely WARNING C Door Crown Installation IMPORTANT PREVENT PERMANENT STAINING 2 Screws 2 Screws Use a soft cloth and a window cleaning solution to clean all fingerprint oils from the gold or nicke...

Page 29: ...e appliance E Positioning the Logs While still breakable the logs do not become fragile until after the appliance is burned and they have cured After curing any handling must be done with care as brea...

Page 30: ...ove the existing door from the appliance Remove the crown from the existing door by removing four screws on the back side of the door assembly Pull crown off door face Install replacement door with gl...

Page 31: ...lower housing to appliance Turn power supply back on Blower motor comes standard with 2 male spade wire connectors If your appliance has a different connec tion use the two female spade wire connector...

Page 32: ...lame Improper adjustment can cause sooting in the firebox and or on the outside of a house with a horizontal termination After adjustment tighten nut to lock in place I Vertical Damper Adjustment Figu...

Page 33: ...that there are no gas leaks Ensure that the glass is sealed and in the proper posi tion Ensure that the flow of combustion and ventilation air is not obstructed front grilles and vent caps B Controls...

Page 34: ...t the power from the appliance 4 Open the door of the appliance May need to remove face front first 5 Push in gas control knob slightly and turn clockwise to the OFF position Do not force 6 Wait five...

Page 35: ...detectors Smoke and odors may be irritating to sensitive individuals CAUTION Prevent accidental appliance operation when not attended Unplug or remove batteries from remote control if absent or if ap...

Page 36: ...he thermocouple connection at the gas valve is fully inserted and tight hand tighten plus 1 4 turn Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocoup...

Page 37: ...ing exhaust gases back into the system Check for proper vent connection at flue collar and all vent joints c Horizontal vent improperly pitched The horizontal vent cap should slope down only enough to...

Page 38: ...tching or slamming glass Do NOT use abrasive cleaners Use a hard water deposit glass cleaner on white film Do NOT clean glass when hot Turn off appliance after 3 4 hours of operation and ALLOW TO COOL...

Page 39: ...t as neces sary 2 Replace appliance if firebox has been perforated Burner Ignition and Operation 1 Verify burner is properly secured and aligned with pilot or igniter 2 Clean off burner top inspect fo...

Page 40: ...Page 40 10 08 Quadra Fire Columbia Bay 250 5195 Rev K B Service and Maintenance Log Date of Service Performed By Description of Service...

Page 41: ...ctual appliance dimensions Use for reference only For clearances refer to Section 3 Figure 12 1 Appliance Dimensions A B F G H I J K C D E Location Inches Millimeter Location Inches Millimeter A 22 1...

Page 42: ...in 184 mm 7 1 4 in 184 mm 5 1 4 in 133 mm 25 1 4 in 641 mm 37 1 4 in 946 mm 49 1 4 in 1251 mm 13 1 4 in 337 mm 13 1 4 in 337 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm 6 5 8 in 168 mm SLP45 SL...

Page 43: ...iling Firestop SLP WS Wall Firestop SLP HVS Pipe Support Hanger 950 Vinyl Protector Kit SL Pipe DRC RADIUS Decorative Radius Cover HTI DV WT Wall Thimble RF4 8 Roof Flashing TERMINATION KITS SLP TRAP2...

Page 44: ...250 5195 Rev K Service Parts Diagram Part number list on following page Log Set Assembly COLBAY FS B Columbia Bay Free Standing 1 2 3 4 5 6 7 8 9 R D Service Parts List Beginning Manufacturing Date Fe...

Page 45: ...alve Cover 474 0240 Adaptor Inner 4 200 2470 Adaptor 6 5 8 7000 162 Baffle Assembly 842 4051 Baffle Hanger 452 0030 Brick Refractory Ceramic 841 0810 Burner Pan 474 0080 Burner Support Kit 842 5190 El...

Page 46: ...30 0730 Y 3 Piezo Ignitor 291 513 Y 4 Knob On Off 571 534 Y 5 Knob Hi Lo 571 533 Y 6 Valve NG 842 0240 Y Valve LP 842 0230 Y Valve Bracket 474 0230 7 Latch Assembly 452 5070 Y 8 Blower 812 4900 Y Blow...

Page 47: ...able under this warranty is limited to the purchase price of the product In no event shall HHT be liable for any incidental or consequential damages caused by defects in the product Adjustments regula...

Page 48: ...zed and approved by HHT in writing This warranty does not apply to non HHT venting components hearth components or other accessories used in conjunction with the installation of this product This warr...

Page 49: ...___________ Columbia Bay Direct Vent Gas Appliance Do NOT discard this manual CAUTION Important operating and maintenance instructions included Read understand and follow these instruc tions for safe...

Reviews: