Page 13
CB 1200 Pellet Stove
Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer
to the owner’s information manual provided with this appli-
ance. For assistance or additional information consult a
qualifi ed installer, service agency or your dealer.
WARNING
The chart will help you in determining proper
venting size according to the equivalent feet of
pipe calculated above and the altitude above sea
level of this installation.
Figure 13.2.
Locate the calculated equivalent feet of pipe on
the vertical left side of the chart. Move to the
right horizontally on the chart until you reach
your altitude above sea level.
If you fall below the diagonal line, 3 or 4 inch (76
to 102mm) pipe may be used. If it is anywhere
above the diagonal line, a 4 inch (102mm) diam-
eter pipe is required.
The chart reveals that a 90° elbow is 5 times as
restrictive to the fl ow of exhaust gases under
positive pressure as 1 foot of horizontal pipe, and
a foot of horizontal pipe is twice as restrictive as
a foot of vertical pipe.
E. Pipe Selection Chart
The table below can help you calculate the equivalent feet
of pipe which is a method used to determine pellet vent size.
Figure 13.1.
D. Equivalent Feet of Pipe
Example of 3 Elbow-Rear Vent Termination Calculation
Figure 13.1
Fire Risk.
Do NOT pack insulation or other
combustibles between fi restops.
• ALWAYS maintain specifi ed clearances
around venting and fi restop systems.
• Install
fi restops as specifi ed.
Failure to keep insulation or other material
away from vent pipe may cause fi re.
WARNING
3 in. or 4 in. (76mm or 102mm) Diameter Pipe
Equivalent Pipe
Length In Feet
ALTITUDE IN THOUSANDS OF FEET
0
20
30
1 2 3 4 5 6 7 8 9 10
4 in. (102mm) Diameter Pipe Only
10
Example 1
Example 2
Figure 13.2
3 ft
(914mm)
2 ft (609mm)
2 ft (609mm)
2 ft (609mm)
Pellet Venting
Component
# of
Elbows
Feet of
Pipe
Multiplied
By
Equivalent
Feet
Components
Equivalent Feet
90
o
Elbow or Tee
3
X
5
15
45
o
Elbow
X
3
Horizontal Pipe
7
X
1
7
Vertical Pipe
2
X
0.5
1
Total Equivalent Feet
23
Note: This is a generic example and is not
intended to represent any specifi c fuel type.
Example 1
: If the equivalent length of pipe is 23 feet
(7m)with altitude of 8,000 feet (2438m) you must use
4 inch (102mm) diameter type “L” or “PL” vent.
Example 2
: If the equivalent length of pipe is 12 feet
(3.7m) with altitude of 6,000 feet (1829m) you may
use 3 or 4 inch (76 to 102mm) diameter type “L” or
“PL” vent
Summary of Contents for CB1200M-MBK
Page 47: ...R May 6 2015 7014 179K Page 47 CB 1200 Pellet Stove E Warranty Policy...
Page 48: ...Page 48 7014 179K May 6 2015 R CB 1200 Pellet Stove...
Page 49: ...R May 6 2015 7014 179K Page 49 CB 1200 Pellet Stove...
Page 50: ...Page 50 7014 179K May 6 2015 R CB 1200 Pellet Stove...
Page 51: ...R May 6 2015 7014 179K Page 51 CB 1200 Pellet Stove...