Page 8
7014-083E
September 1, 2008
R
CB1200-I Pellet Insert
Fire Risk.
Comply with all minimum clear-
ances to combustibles as speci-
fied.
WARNING
Failure to comply may cause
house fire.
NOTE:
•
Illustrations reflect typical installations
and are FOR DESIGN PURPOSES
ONLY.
•
Illustrations/diagrams are not drawn to
scale.
•
Actual installation may vary due to
individual design preference.
B. Clearance To Combustibles, UL and ULC
12 in
Rear Shroud
6 in
Shown with Hopper Extended
Optional Outside
Air
Combustible
Mantel
INSTALLED AS A BUILT-IN UNIT
Shown with Rear Vent and Optional Outside Air
Figure 8.1
Figure 8.2
AS A BUILT-IN
B
D
C
E
B
C
A
0 INCH (0mm) CLEARANCE TO EXPOSED SECTION AND FACE TRIM
Rear Shroud Kit, Part 811-0680 is Required for Built-In Installation
(see pages 17-18 for installation instructions)
A
Top of Shroud
Top Vent
3.0
76
Rear Vent
0
0
B
Sides of Inside Shroud
Top or Rear Vent
0
0
C
Back of Inside Shroud
Top Vent
2.5
64
Rear Vent
0
0
D
Vent Pipe to Combustible
Top or Rear Vent
3.0
76
E
From Outside Edge of
Panel Set to Combustibles
0 0
Inches
Millime-