background image

C. Mantel and Wall Projections

A combustible mantel may be positioned no lower than 60 

in. (1524 mm) from the base of the fireplace.
Refer to Section 3 for reduced mantel height allowances.
The combustible mantel may have a maximum depth of 

12 in. (305mm). Combustible trim pieces that project no 

more than 3/4 in. (19 mm) from the face of the fireplace 

can be placed no closer than 6 in. (152 mm) from the top 

or side of the decorative front. Combustible trim must not 

cover:

•  the metal surfaces of the fireplace

•  where  the  non-combustible  board  is  placed  over  the 

metal surfaces

•  the space between the metal face of the fireplace and 

framing members

60 in.

(1524 mm)

Mantel

Clearances are from 

bottom of appliance to 

lower edge of mantel 

or trim

Trim

48 in.

(1219 mm)

36 in. (914 mm)

Ceiling/enclosure

Figure 7.2  Mantel Specifications - Combustible Mantel

D. Finishing the Hearth Extension

Table 7.1 

= 1/k x inches of thickness

Table 7.2 

WARNING! Risk of Fire! 

High temperatures, sparks, em-

bers  or  other  burning  material  falling  from  the  fireplace 

may ignite flooring or concealed combustible surfaces.
•  Protective metal hearth strips MUST be installed.

•  Hearth  extensions  MUST  be  installed  exactly  as 

specified.

A hearth extension must be installed with all fireplaces to 

protect the combustible floor in front of the fireplace from 

both radiant heat and sparks.
•  You MUST use a hearth extension with this fireplace. 

•  Refer to Figure 7.4 for minimum dimensions.

•  This fireplace has been tested and approved for use with 

a hearth extension insulated to a minimum R value of 

2.06.

•  The hearth extension material MUST be covered with 

tile, stone or other non-combustible material.

•  Manufactured  hearth  materials  will  usually  have  a 

published 

R value

  (resistance  to  heat)  or 

k value

 

(conductivity of heat). Refer to the formula in Table 7.1 

to convert a k value to an R value,

•  Refer  to  Table  7.2  for  hearth  extension  insulation 

alternatives.

Hearth Extension Insulation Alternatives, R Value = 2.06

Material

k per inch 

thick

r per inch 

thick

Minimum 

thickness 

required

Hearth & Home HX3, HX4

0.49

2.06

1 in.

USG Micore 300™

0.49

2.06

1 in.

USG Durock™ Cement Board

1.92

0.52

4 in.

Cement Mortar

5.0

0.20

10 1/2 in.

Common Brick

5.0

0.20

10 1/2 in.

Ceramic Tile

12.50

0.08

25 3/4in.

Armstrong™ Privacy Guard Plus

0.46

2.18

1 in.

Marble

14.3-20.0

0.07-0.05

29 1/2 - 41 1/4 in.

A noncombustible mantel may be positioned no lower 

than 46 in. (1168 mm) from the base of the fireplace.
Noncombustible framing materials must  be used above 

the fireplace to a height of 84 in. (2134 mm) or to the 

ceiling from the base of the fireplace for all construc-

tion materials, framing members, sheeting, and all finish 

materials.

Figure 7.2  Mantel Specifications - Non-Combustible Mantel

46 in.

(1168 mm)

Noncombustible 

Mantel

Clearances are from 

bottom of appliance to 

lower edge of mantel 

or trim

All construction materials, framing 

members, sheeting and finish 

materials MUST be noncombustible.

37

Quadra-Fire • 7100 FP • 433-3610 Installation Manual • Rev G • 5/27/14

Summary of Contents for 7100FP-GD-B

Page 1: ...ert children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable materials away INSTALLE...

Page 2: ...Chase 13 D Frame the Fireplace 14 E Secure and Level the Fireplace 14 F Protective Metal Hearth Strips 15 G Facing Material 15 H Outside Air Kit 16 I Auxiliary Convection Air System 18 J Heat Zone Ki...

Page 3: ...talled in non combustible areas Verified all clearances meet installation manual requirements Mantels and wall projections comply with installation manual requirements Protective hearth strips and hea...

Page 4: ...Installation Codes in Canada Warning Risk of Fire Hearth Home Technologies disclaims any responsibility for and the warranty and agen cy listing will be voided by the following actions DO NOT install...

Page 5: ...pter protection in compliance with the applicable electrical codes when it is installed in damp locations WARNING Improper installation adjustment alteration service or maintenance can cause injury or...

Page 6: ...material Hearth extension Non combustible roof flashing maintains minimum clearance around chimney Additional lateral support for chimney above roof or enclosed in chase if needed Enclosed space abov...

Page 7: ...r to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisdic...

Page 8: ...l Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler climates Recommended Location Above peak Inside heated space Location NOT recommended Too close...

Page 9: ...and doors are shipped in separate packages Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these instructions carefully during the...

Page 10: ...2 in 826 mm 38 in 965 mm 40 in 1016 mm 42 5 16 in 1075 mm 45 13 16 in 1148 mm 23 7 16 in 595 mm 13 3 16 in 335 mm 10 13 16 in 259 mm 4 5 16 in 109 mm 6 in 152 mm 1 in 25 mm 13 3 4 in 349 mm 9 7 16 in...

Page 11: ...fire Figure 3 2 Clearances to Combustible Materials ceiling roof ceiling 2 in 51 mm min Attic Insulation Shield Ceiling Firestop attic Storm Collar Roof Flashing 2 in min 51 mm 2 in 51 mm min 2 in 51...

Page 12: ...E AREA Fireplace to backwall 1 in 25 mm Fireplace to sidewall 1 in 25 mm Duct boots to framing 0 in 0 mm Top standoffs to header 0 in 0 mm Door opening to sidewall 22 7 8 in 581 mm EXPOSED SURFACES Fa...

Page 13: ...d be insulated Figure 3 5 Chase Constructions 1 Fireplace and chimney enclosed in an exterior chase 2 Chimney offset through exterior wall and enclosed in chase 3 Chase constructed on roof The chase i...

Page 14: ...above the level of the top standoffs No recess above standoffs The finished cavity depth must be no less than 24 in 610 mm from the finished backwall to the outside of front wall framing Framing must...

Page 15: ...be installed Hearth extensions MUST be installed exactly as specified WARNING Risk of Fire Follow these instructions exactly Facing materials must be installed properly to prevent fire No materials ma...

Page 16: ...mm metal flex or rigid piping not supplied to directly connect outside air to fireplace intake Insulate the pipe to prevent frost condensation Use the supplied outside air inlet hood Seal between the...

Page 17: ...on away from chimney Ceiling firestop on floor of attic Outlet blocked by snow leaves etc NO Garage or combustible liquids storage NO Attic space NO Outlet placed higher than 3 ft below the terminatio...

Page 18: ...gure 3 13 Auxiliary Convection Air Duct Alternatively a 6 inch 152 mm duct can be run to an other location in the home and used as a cold air return within the home and distributed into the room where...

Page 19: ...a remove the one screw and plate to allow the handle to be moved in the full motion right to left See Figure 3 14 Discard the plate and screw Replace fascia The auxiliary convection lever is located u...

Page 20: ...it conveys warm air from the fireplace through air duct s to remote locations in the same room or other rooms of the building You may install 1 or 2 Heat Zone kits on the fireplace Installation of thi...

Page 21: ...sembly Cut a 7 5 8 in x 13 5 8 in 143 mm x 346 mm hole between framing members wall studs or floor joists The brackets can be rotated 180 and mounted to the back side of the 2 x 4 if necessary See Fig...

Page 22: ...lack and neutral white fan wires and screw the 110 VAC ground wire to the junction box See Figure 3 21 Secure the return air grille to the fan housing making sure it is flush The grille must be instal...

Page 23: ...the bottom right side of the fireplace Thread the 14 3 with ground wire through the opening with the strain relief on the cover plate Match colors to wire harness red to red white to white etc and sec...

Page 24: ...eturn 6 ft 1 83 m Maximum unsupported chimney height above the fireplace 35 ft 10 67 m Maximum unsupported chimney above roof 6 ft 1 83 m Warning Risk of Fire You must maintain 2 in 51 mm air space cl...

Page 25: ...mm Dimension B between the offset and return The chimney component that best fits your application is one SL324 15 degree 30 degree SL306 SL312 SL318 SL324 SL336 SL348 A B A B in mm in mm in mm in mm...

Page 26: ...cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decorative cap cover In a staggered installation with both gas and wood terminations the woo...

Page 27: ...al Support straps for offsets returns must be secured to adequate framing Ceiling firestops are required where chimney passes through ceiling or floor Attic Shield is required where chimney passes thr...

Page 28: ...ly engaged and will not separate You may use 6 or 8 sheet metal screws no longer than 1 2 in 13 mm to fasten chimney sections together Do NOT penetrate inner flue Warning Risk of Fire You MUST use scr...

Page 29: ...l around the cap and flex with caulk to stop air from getting into the chase see Figures 6 4 Wire Ties Seal Seal 4 Duct Use UL181 Class 0 or Class 1 ducting Figure 6 4 Installing Flex Pipe WARNING Ris...

Page 30: ...2 in 51mm clearance Warning Risk of Fire Do NOT seal area between firestop opening and chimney pipe except where they en ter the attic or leave the warm air envelope of the home use 600 F sealant Fig...

Page 31: ...gainst pipe Attic Insulation Shield Ceiling Firestop 10 1 2 in 267 mm 14 1 2 in 368 mm diameter Insulation Insulation Pipe Pipe 2 in 51 mm air space Tabs bent in 90 and taped Tabs bent 90 to rest agai...

Page 32: ...where the chimney will exit the roof by plumbing down to the center of the chimney Lay out cut and frame a 14 1 2 in 368 mm square opening measured on the horizontal through the ceiling and roof stru...

Page 33: ...welded or spun collar around pipe opening to keep water out Provide a 1 8 in 3 mm gap around the flue pipe Slope the chase top downward away from the opening Warning Risk of Fire Do not caulk the pip...

Page 34: ...ermination Cap Chase 14 1 2 in 368 mm Maximum Collar 2 in 51 mm Minimum Height Caulk gaps between storm collar pipe and storm collar chase top Do NOT block air holes 3 clip brackets Slip over chase co...

Page 35: ...der each flange of the termination cap and on top of each screw to help prevent leaks 2 in 51 mm maximum 4 3 4 in 121 mm maximum The last section of pipe must stop between 2 in 51 mm above the top of...

Page 36: ...e fascia must be removable for future serviceability of the automatic combustion control Figure 7 1 Install the Finishing Template Note DO NOT remove hang tags until installing finish materials B Fini...

Page 37: ...e Refer to Figure 7 4 for minimum dimensions This fireplace has been tested and approved for use with a hearth extension insulated to a minimum R value of 2 06 The hearth extension material MUST be co...

Page 38: ...ble finish material Figure 7 4 Fireplace and Hearth Extension Flush on the Floor Raised Hearth Extension Framing The hearth framing must be constructed of non combustible materials such as metal frami...

Page 39: ...k of Fire Maintain clearances Use only non combustible material below standoffs material such as cement board is acceptable Framing or finishing material used on the front of the fireplace closer than...

Page 40: ...stall rear bricks on the top of the bottom bricks Slide top of bricks under clip on back of firebox wall and push bottom of brick back Install side bricks Slide top of brick under clips on side of fir...

Page 41: ...Figure 8 3 Ceramic Blanket Back of Firebox Baffle Board Baffle Protection Channel in position C Install Fascia Fronts Fronts are required to complete the installation The 7100 fireplace allows a choi...

Page 42: ...ney Offset Return 15 deg SL330 Chimney Offset Return 30 deg FS338 Ceiling Firestop Straight FS339 Ceiling Firestop 15 deg FS340 Ceiling Firestop 30 deg AS8 SL300 Straight Attic Insulation Shield 24 in...

Page 43: ...mm Outside Diameter 10 1 2 in 267 mm 4 3 4 in 121 mm Effective Height SL3 Chimney Stabilizer Inside Diameter 8 in 203 mm Outside Diameter 10 1 2 in 267 mm SL315 Chimney Offset Return 15 deg SL330 Chi...

Page 44: ...21 18 24 mm 864 538 610 DTS146 in 46 21 18 26 mm 1168 538 660 23 in 584 mm 19 in 483 mm 15 5 8 in 397 mm ST375 Square Termination Cap 22 1 2 in 572 mm 9 1 2 in 241 mm 16 1 2 in 419 mm 9 1 2 in 241 mm...

Page 45: ...70 mm TV342 Top Vent Round Termiantion Cap A B C D Catalog A B C D in mm in mm in mm in mm LDS33 36 914 36 914 8 5 216 11 279 LDS46 48 1219 72 1829 8 5 216 11 279 LDS33 LDS46 Decorative Shroud Catalog...

Page 46: ...B Accessories MESH HHT Firescreen Doors Classic Black Gold Satin Nickel Fronts Valley Forge Mission Hill Rolling Meadow 46 Quadra Fire 7100 FP 433 3610 Installation Manual Rev G 5 27 14...

Page 47: ...This page intentionally left blank 47 Quadra Fire 7100 FP 433 3610 Installation Manual Rev G 5 27 14...

Page 48: ...t West Lakeville MN 55044 www quadrafire com Please contact your Quadra Fire dealer with any questions or concerns For the location of your nearest Quadra Fire dealer please visit www quadrafire com 4...

Reviews: