background image

© COPYRIGHT

 2008          www.quadlogic.com 

© COPYRIGHT

 2008          www.quadlogic.com 

    It is recommended that the RSM-5c and RSM-5 meters be mounted on 

a concrete wall with the appropriate screws long enough to hold the box 
in place.  If the only choice is to mount the meter on a drywall or plaster 
wall, make sure that the boxes are properly screwed on the studs of the 
wall.

2. Mount the RSM-5c or RSM-5 back box to the wall, with mouting screws.  

Connect the distribution panel box to the RSM-5c or RSM-5 back box 
with a metal conduit.  This conduit will be used for the voltage taps and 
current transformer (CT) secondary wiring.  There will be between 2 and 
4 #12AWG wires in this conduit, connected to the hot line(s) and neutral 
(if present).  There will also be between 2 and 6 #16 AWG stranded wires 
connected to the CT secondary wiring.  The conduit should be sized to 
accommodate this.   

3. The RSM-5c or RSM-5 metal boxes must be grounded.  Either a ground 

wire may be run and attached to one of the box mounting screws, or the 
boxes may be grounded by the conduit. 

4. Securely fasten one end of the grounding wire so that the screw cuts the 

paint on the back box.  Securely fasten the other end of the wire to true 
earth ground connection.  When grounding to the electrical conduit, use 
continuous pipes, bending when necessary instead of using couplers.

Step 2:  Connect voltage taps

        Power must be off when connecting these wires!

1. Locate the incoming feeder phase (hot) wires in the distribution panel.  

Tape the incoming feeder wires with colored electrical tape according to 

phase, for identification purposes. 

2. Tap the feeder wires with #12 AWG stranded wires.  The color of the 

insulation on these wires must match the color of the tape on the feeder 
wire to which they are connected.  If neutral is required, tap the neutral 
connection with a #12 AWG stranded wire with white insulation.  These 
voltage connections can be made in any way that meets local codes and 
requirements.  

A service disconnect switch for the hot wires is required.  It is 

Chapter 2

 

- RSM-5c and RSM-5 Installation -

3

recommended that the disconnect switch should be placed as near as 
possible to the meter. If fused, no less than a 15-A fast-acting fuse must 
be used.

3. Run the #12 AWG feeder phase tap wires through the conduit to the back 

box.  

Step 3:  Install and connect Current Transformers (CTs)

 

Power must be off when connecting these wires!

Un-terminated CT secondary wires will produce hazardous electrical 

potentials if any current is flowing through the CT.  While connecting the 
CTs, POWER MUST BE OFF  until the CTs have all been connected to the 
fuse block.

  

1. Each CT is supplied with two secondary wires.  One wire is colored black, 

red, or blue, and the other wire is white.  Connect these 2 wires to the 
screw terminals on the fuse block. 

2. If the wires that are supplied with the CTs are too short to reach the fuse 

block screw terminals, they must be extended.  Extend the CT wires with 
#16 AWG stranded wire.  This should be black, red, or blue wire to match 
the existing CT wire.  Extend the white wire of each CT with a white 
wire.  It is very important to maintain the association of a particular CT’s 
secondary wires.  One must keep track of which white wire goes with each 
individual colored wire.  It may be helpful to tape them together before 
pulling them through the conduit.

Wire color coding may vary depending on local codes and regulatory 
standards within certain jurisdictions.   

3. Locate the branch circuit that supplies current from the distribution panel 

to the metered load. Disconnect these wires one (or two) at a time and 
properly run each wire (or pair of wires) through a CT as shown in Figure 
2-1.  The colors of the CT leads must correspond to the color of the tape 
on the phase feeder wires that supply this load.   

Chapter 2

 

- RSM-5c and RSM-5 Installation -

4

Summary of Contents for RSM-5c

Page 1: ...Table of Contents Manual 3 Phase kWh 3 Phase Demand Single Phase kWh...

Page 2: ...RSM 5c RSM 5 Installation Manual Power Line Communications Metering Systems...

Page 3: ...6 Chapter 4 Menu Navigation 11 Chapter 5 Verifying Meter Functionality 15 Chapter 6 Resetting Demand Values For D Models 18 Chapter 7 Reading the Display 19 Chapter 8 Metering Specifications 21 Chapte...

Page 4: ...raining and are qualified to work with electricity and electrical metering equipment All applicable national and local electrical codes and standards must be followed Failure to follow proper procedur...

Page 5: ...abnormally proceed with caution The safety of the device may be impaired Do not install the meter in the presence of explosive or combustible gas or gas vapor Do not install the meter on an electrical...

Page 6: ...on with a 12 AWG stranded wire with white insulation These voltage connections can be made in any way that meets local codes and requirements A service disconnect switch for the hot wires is required...

Page 7: ...nd 4 above for each CT until all CTs have been installed and connected to the MCI screw terminals Chapter 2 RSM 5c and RSM 5 Installation 5 The following diagrams show the necessary fuse block connect...

Page 8: ...nnections Figure 3 3 1 Phase 3 Wire 120 240V 120 208V or 277 480V Network Fuse Block Connections Chapter 3 Fuse Block Connections 8 Figure 3 4 RSM 5 3 Phase 4 Wire Wye with High Current Adapter HCA 16...

Page 9: ...ogic com COPYRIGHT 2008 www quadlogic com Figure 3 6 RSM 5 3 Phase 4 Wire Wye with High Current Adapter HCA All CTs must be the same primary amperage and secondary amperage must be 5 Amp 9 10 Chapter...

Page 10: ...hown in figure 4 3 Each main menu heading will be displayed in two second intervals Note that the RSM 5c and RSM 5 default to the kWh register Figure 4 2 Meter LCD Main Menu headings Chapter 4 Menu Na...

Page 11: ...COPYRIGHT 2008 www quadlogic com COPYRIGHT 2008 www quadlogic com Chapter 4 Menu Navigation Figure 4 4 Display Menu Structure For an RSM 5c and RSM 5 Meter 13 Chapter 4 Menu Navigation 14...

Page 12: ...Display Scroll button Scroll down by pressing and releasing the Display Scroll button until the following screen is displayed The A mperage reading is the indication of current The A mperage reading...

Page 13: ...as above 17 Resetting Demand Values For D Models Chapter 6 BE CERTAIN TO RECORD THE CURRENT PEAK DEMAND WITH THE TIME AND DATE BEFORE RESETTING THE DEMAND Once the user resets the demand according to...

Page 14: ...ge How CT multipliers are calculated 0 1 Amp CTs The multiplier values for CTs with 0 1A secondary ratings are derived by dividing the primary side rating by 100 For example a 50 0 1A rated CT will ha...

Page 15: ...r off 500msec Max Pulse Rate Power on 10pulses sec max Power off 1 pulse sec max 21 Chapter 8 Metering Specifications When RSM 5 loses power the pulse accumulator still has the capability to record pu...

Page 16: ...for the RSM 5c and RSM 5 products and include the complete meter assembly meterhead fuse block and back box as well as the required current transformers CTs for operation Meters CTs not included page...

Page 17: ...s RSM5c 120200 3SL includes 3 SOLID CORE CTs RSM5c 277100 3SL includes 3 SOLID CORE CTs RSM5c 277200 3SL includes 3 SOLID CORE CTs 25 Chapter 9 Ordering Information RSM 5 Meter Kits kWh for Large Serv...

Page 18: ...alog 120 208V 277 480V 1600 3200 1600 3200 3 SPLIT CORE Figure 3 4 Volts Amps kWh and Demand CTs included Diagram 3 Phase Demand Meter Delta DTA RSM5 480DTA1600 2D RSM5 480DTA3200 2D Catalog 1600 3200...

Page 19: ...mand kWh Demand 4 Pulse Inputs Diagram 3 Phase Meter DELTA DTA A B C N Single Phase kWh Meter Wye RSM5c 120 2PH RSM5c 277 2PH Catalog 120 208V 277 480V 0 1A Figure 3 3 Volts Amps kWh Only Diagram C A...

Page 20: ...ts Diagram 3 Phase Meter DELTA DTA 0 1Amp A B C N C A B Dimension 13 5 X 8 5 X 4 5 RSM5 480DTA01A D RSM5 480DTA01AMD RSM5 480DTA01ARSD RSM5 480DTA01A PD Catalog 480V 0 1A Figure 3 2 Volts Amps kWh Dem...

Page 21: ...and 4 Pulse Inputs Diagram 3 Phase Meter DELTA DTA CL10 accepts one or two sets of 5Amp CTs A B C N B C A RSM5 480DTACL10 D RSM5 480DTACL10MD RSM5 480DTACL10RSD RSM5 480DTACL10 PD Catalog 480V 10A Fig...

Page 22: ...Added clarifying note Correction of memory size to 512 kilobyte Meets ANSI C12 1 Correction of voltage to 480V Delta Qualified fuse type Use shielded twisted pair for 50 CT extensions Deleted amperage...

Page 23: ......

Page 24: ...QUADLOGIC 33 00 Northern Blvd Long Island City NY 11101 Tel 212 930 9300 Fax 212 930 9394 www quadlogic com RSM5 5c MANR2 0 R...

Page 25: ...3 Phase kWh...

Page 26: ......

Page 27: ......

Page 28: ...3 Phase Demand...

Page 29: ......

Page 30: ......

Page 31: ...Single Phase kWh...

Page 32: ......

Page 33: ......

Reviews: