AN-X2-MOD-MON Page
35
Rack
Location
Slot
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
0L
0H
1L
1H
2L
2H
3L
3H
4L
4H
5L
5H
6L
6H
7L
7H
Offset
2
8L
8H
9L
9H
10L 10H 11L 11H 12L 12H 13L 13H 14L 14H 15L 15H Offset
3
16L 16H 17L 17H 18L 18H 19L 19H 20L 20H 21L 21H 22L 22H 23L 23H Offset
4
24L 24H 25L 25H 26L 26H 27L 27H 28L 28H 29L 29H 30L 30H 31L 31H Offset
To map the module status data for a given Quantum drop, include a line with the keyword
dnModSts, where n is the drop number, from 1 to 32, and the length of the module status
data, in 16-bit words, in the input section of a connection.
The length must be large enough to include all modules in the configuration. For
example, if the last module is in rack 1 slot 3, the size must be at least 2.
If the length is omitted, AN-X uses a default length of 10. If a length of 10 is not large
enough to include all modules in the drop, AN-X generates an error when you download
the configuratuion to the AN-X.
If you omit the offset, the line must start with a comma.
Examples:
,d4ModSts,17
30, d4ModSts ; offset 30
Connection Statistics
The module maintains statistics for each exclusive owner scheduled connection. In the
following table, O represents the connection originator (ControlLogix) and T represents
the connection target (AN-X).
There are 10 words of connection statistics data for each connection, of which three are
used.
Offset
Description
0
Average update time, average of last 32 updates
1
Reserved
2
Minimum update time since last reset of statistics
3
Reserved
4
Maximum update time since last reset of statistics
5
Reserved
6
Reserved
7
Reserved