WIRING DIAGRAM

ALT SIREN WIRING - A

ALT SIREN WIRING - B

Optional

 Siren Relay wiring using GND (-) 

and IQ Panel 2 “EXT Siren” output*

Optional

 Siren Relay wiring using 12v (+) 

and IQ Panel (GEN1) “Buzzer” output*

*

Not intended for UL Installations

*

Not intended for UL Installations

For Service Contact 
COMPANY NAME: 
ADDRESS: 
PHONE:

#

ZONE LIST

#

ZONE LIST

1

9

2

10

3

11

4

12

5

13

6

14

7

15

8

2W 

SMK

Document #: IQHW16FDL 
Revision Date: 5/21/19 
Qolsys Part #: QS7134-840

The 

IQ Hardwire 16-F 

offers a cost effective way of integrating hardwired security & 

smoke detector zones with the IQ Panel 2.  It includes a large enclosure with ample 
wire routing room, backup battery charging, 500mA of 12volt auxiliary power, an 
onboard siren relay, built-in status LED’s for each zone and support for up to 10 
two-wire smoke detectors.  Normally Open and Normally Closed contacts are 
supported as well as powered zones like motion sensors and glass break detectors. 

Note: Not for use with CO detectors

INSTALLATION MANUAL

TECHNICAL SPECIFICATIONS

Document #: IQHW16FEQG 
Revision Date: 10/7/19 

Qolsys Part #: QS7134-840

ENCLOSURE OVERVIEW

Confidential & 
Proprietary. 
Made in Taiwan.   
 

Page    of 4 Qolsys Confidential and Proprietary.

1

Input Voltage:

 16.0VDC Plug-In Transformer 

Backup Battery: 

12VDC 5AH Max (not included) 

Dimensions:

 16” X 14” X 3” 

Operating Temperature: 

32 to 122F (0 to 50C) 

EOL Supervision:

  4.7k Ohm fixed 

or

 1k-10k Ohm 

depending on Resistor Mode 

Input Zones: 

15 N/O or N/C 

Smoke Zone:

  1 two-wire smoke loop, 10 detectors 

max.  Support for System Sensor® 2W-B, 2WT-B, 
2WTA-B*  

*Detector models should not be mixed

 

Auxiliary Voltage Output: 

12VDC @ 500mA Max 

Tamper Zone:

 Used for case tamper, no resistor 

Relay Contact: 

60VDC/1A Max drives siren

Compatible Control Panel:

  The IQ Hardwire 16-F 

is for use with the Qolsys IQ Panel 2 only.  Refer to 
the full IQ Panel 2 installation manual for typical 
installation layout, including recommended 
locations of the control unit, detectors and 
notification appliances. 

Enclosure:  

For UL Installations, Qolsys enclosure 

QR0073-840 shall be used. 

Listed Resistor:  

For UL Installations, Qolsys 4.7K 

Fire Resistor Part # QR0072-840 shall be used on 
the 2-wire fire loop at the end of line. 

Wiring:

  For UL Installations, recognized limited 

energy cable shall be used.

UL REQUIREMENTS

INFORMATION

Tamper

Expansion  

Slot

Battery Compartment 

(5aH & 8aH compatible)

Locking 

Screw

Optional  

Cam Lock

Door 

Label

Zip Tie 

Rails

Knock 

Outs

Expansion Battery 

Compartment

ACCESSORIES

Resistors (x16)

5aH Battery 

Bracket (x2)

8aH Battery 

Bracket (x2)

Knock Out 

Bushings (x2)

Power Supply Battery Cables

RF Antenna (x1)

Summary of Contents for IQ Hardwire 16-F

Page 1: ...put Voltage 16 0VDC Plug In Transformer Backup Battery 12VDC 5AH Max not included Dimensions 16 X 14 X 3 Operating Temperature 32 to 122F 0 to 50C EOL Supervision 4 7k Ohm fixed or 1k 10k Ohm depending on Resistor Mode Input Zones 15 N O or N C Smoke Zone 1 two wire smoke loop 10 detectors max Support for System Sensor 2W B 2WT B 2WTA B Detector models should not be mixed Auxiliary Voltage Output ...

Page 2: ... resistor included or a 1k 10k resistor installed depending on the which Resistor Mode is selected see Troubleshooting on page 3 in either the N O parallel or N C series position b Wire the positive and negative leads from powered devices such as motion sensors and glass break detectors into the AUX and GND terminals to power the devices c The case tamper should be pre wired from the factory and d...

Page 3: ... default mode is UL Mode where 4 7k resistors are required on each zone In this mode the Processor LED blinks rapidly 8 times per second If UL installation is not required EOL Resistor Learning can be enabled In this mode the Processor LED blinks slowly 1 time per second and any resistor value from 1k to 10k can be used NOTE Zone 16 is dedicated for 2 wire smokes and requires a 4 7k resistor regar...

Page 4: ...te the equipment This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause interference and 2 this device must accept any interference including interference that may cause undesired operation of the device Cet appareil est conforme avec Industrie Canada exempts de licence standard RSS s Son fonctionneme...