background image

HEATER LOCATION INSTRUCTIONS

Arrange units so their discharge air streams:

a.

are subjected to a minimum of interference from

columns, machinery and partitions;

b

.

wipe exposed walls without blowing directly at them;

c.

are directed away from room occupants in comfort heating;

d.

are directed along the windward side when installed

in a building exposed to a prevailing wind.

Locate thermostats approximately 5' (1524mm) above the floor

on interior partition walls or post away from cold drafts, internal

heat sources and away from heater discharge air streams.

Small rooms can be heated by one unit heater.

Large rooms require multi-unit installations. Number and

capacity of units will be determined by volume of building and

square feet of floor area to be heated. Arrange units to provide

perimeter air circulation where each unit supports the air

stream from another.

MOUNTING THE HEATER

GENERAL

The heater may be mounted to discharge the heated air either

horizontally or vertically. When the heater is mounted for verti-

cal discharge, it is recommended that the heater be positioned

so that the access door will open away from the wall to provide

greater access to the wiring and control compartment. If the

heater is to be mounted with the access door facing a wall, the

heater must be mounted far enough from that wall to allow full

opening of the access door (a distance approximately equal to

the width of the heater ... check clearance before installing).

Refer to Table 1 for wall and ceiling clearances before mount-

ing heater. 

The heater may be mounted for either vertical or horizontal

discharge by the use of threaded rods. (Refer to Table 2 for

threaded rod sizes required.) Observe the detailed procedures

in the following installation instructions.

The heater may also be suspended from the wall or ceiling by

means of an optional mounting bracket (type MMB or MCMB)

which permits horizontal pivoting of the heater.

After the heater is installed, the louvers may be positioned 

DO NOT MOUNT MERCURY TYPE THERMOSTAT

DIRECTLY ON UNIT. VIBRATION COULD CAUSE

HEATER TO MALFUNCTION.  

MANUAL

RESET LIMIT

(FACTORY

INSTALLED

OPTION ONLY.)  THE LIMIT SWITCH IS LOCATED INTER-

NALLY ON THE REAR OF THE HEATER.  ON THE

MUH03 AND MUH05 MODELS, THE ACCESS TO THE

ALL BUILT-IN THERMOSTATS: IF THE HEATER IS USED TO

PREVENT PIPING OR LIQUIDS FROM FREEZING, AND IF

THE THERMOSTAT IS SET BELOW 45° F (7°C), THE FAN

MUST RUN CONTINUOUSLY. 

CAUTION 

TO PREVENT POSSIBLE OVERHEATING OR DAMAGE

DUE TO OVERHEATING, KEEP AT LEAST 5' (1524mm)

CLEARANCE IN FRONT OF HEATER. REFER TO TABLE 1

FOR SIDE, TOP, AND BACK CLEARANCE REQUIREMENTS.

CAUTION 

THE HEATER MUST BE MOUNTED AT LEAST 7' (2134mm)

ABOVE THE FLOOR TO PREVENT ACCIDENTAL CONTACT

WITH THE FAN BLADE WHICH COULD CAUSE INJURY.

CAUTION 

THE CEILING MOUNTING STRUCTURE AND THE

ANCHORING PROVISIONS MUST BE OF SUFFI-

CIENT STRENGTH TO SUPPORT THE COMBINED

WEIGHT OF THE HEATER AND MOUNTING BRACKET.

(SEE TABLE 4).

CAUTION 

RESET BUTTON IS ON THE RIGHT SIDE (WHEN FAC-

ING REAR OF HEATER); ON ALL OTHER MODELS IT

IS NEAR THE TOP REAR OF THE HEATER.

THE MANUAL RESET LIMIT IS IN SERIES WITH THE

AUTOMATIC RECYCLING PROTECTOR (LIMIT). THE

MANUAL RESET LIMIT WILL NOT RESET UNTIL THE

HEATER HAS COOLED AND THE BUTTON IS

PUSHED IN.

IMPORTANT

!

2

!

!

!

!

Summary of Contents for MUH Series

Page 1: ...g must be in accordance with the National and Local Electrical Codes and the heater must be grounded as a pre caution against possible electric shock 3 Verify the power supply voltage coming to heater...

Page 2: ...ing heater The heater may be mounted for either vertical or horizontal discharge by the use of threaded rods Refer to Table 2 for threaded rod sizes required Observe the detailed procedures in the fol...

Page 3: ...ons are made 6 The power terminal block is equipped with box terminals sized to accept the correct size power supply wire Branch circuit wire rated min 600V 60 C is acceptable for heaters rated up to...

Page 4: ...ctor lead wire A1 must be moved from the end terminal of the power terminal block terminal clos est to the contactor or control terminal board to the A termi nal of the lower terminal block center ter...

Page 5: ...STATS SHOULD BE TREATED AS SINGLE STAGE ONLY 5 WARNING 1 Use min 600 volts NEC Class 1 insulated wire for all control circuit wiring 2 Use a crimp on type fork terminal on the wire ends that attach to...

Page 6: ...55 24 9 MUH252 89 40 4 MUH254 89 40 4 MUH308 30 265 8 113 4 89 40 4 504 in3 MUH302 76 2 676 4 298 5 89 40 4 8260 cm3 MUH304 89 40 4 MUH256 89 40 4 MUH306 89 40 4 MUH402 119 54 0 MUH404 119 54 0 MUH508...

Page 7: ...L OF THE UNIT DISCONNECT POWER BEFORE SERVICING IF EXTERNAL CONTROL IS USED ALSO DISCONNECT EXTERNAL POWER SUPPLY NE PAS RELEVER LES LAMES AU DEL A DU NIVEAU PREVU DE L APPAREIL METTRE HORS TENSION AV...

Page 8: ...IEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH EXCEED THE AFORESAID EXPRESSED WARRANTIES ARE HEREBY DISCLAIME...

Page 9: ...calentador debe estar conectado a tierra como precauci n contra un choque el ctrico posible 3 Antes de activar verifique que el voltaje del suministro de potencia entrante al calentador corresponda a...

Page 10: ...descarga vertical u horizontal mediante el uso de varillas con rosca Refi rase a la Tabla 2 para los tama os de varilla con rosca requeridos Observe los proced imientos en forma detallada en las sigui...

Page 11: ...de terminales de la energ a se equipa de los termi nales de la caja clasificados para aceptar el alambre correcto de la fuente de alimentaci n del tama o El circuito minuto clasificado alambre 600V 60...

Page 12: ...a la par de los rel s contactores Mueva sola mente los dos cables marcados C1 y D1 en cada uno de esos blo ques de terminales tri f sicos a la terminal B No mueva o cambie ning n otro cable El modelo...

Page 13: ...el calentador Ejemplo MUH0581 24 amperos 4 En las unidades que si incluyen contactor interno 7 kW y mas refiere a la figura 5 para el diagrama electrico El alambre del circuito de control deber ser mi...

Page 14: ...0 4 MUH402 119 54 0 MUH404 119 54 0 MUH508 30 265 8 171 4 119 54 0 648 in3 MUH502 76 2 676 4 435 1 119 54 0 10620 cm3 MUH504 119 54 0 MUH406 119 54 0 MUH506 119 54 0 T T MT 1 MT 2 BLACK TO W1 RED TO R...

Page 15: ...SIANAS POR ENCIMA DEL NIVEL DE LA UNIDAD DESCONECTE ANTES DE REPARAR SI SE UTILIZA CONTROL EXTERNO TAMBIEN SE DEBE DESCONECTAR LA FUENTE DE ALIMENTACION EXTERNA NE PAS RELEVER LES LAMES AU DEL A DU NI...

Page 16: ...N DE ESTE ACUERDO TODAS LAS GARANTIAS IMPLICITAS DE COMERCIALIZACION Y APTITUD PARA UN FIN PARTICULAR QUE EXCEDAN LAS GARANTIAS PREVIAMENTE EXPRESADAS MARLEY ENGINEERED PROD UCTS NO SERA RESPONSABLE P...

Page 17: ...nsion d alimentation vers l appareil et la tension du circuit de commande arrivant au radiateur et aux accessoires correspondent aux valeurs nominales indiqu es sur la plaque signal tique du radiateur...

Page 18: ...reporter au tableau 2 pour conna tre les dimensions des tiges filet es requises Suivre les m thodes d taill es dans les instructions d installa tion suivantes Le radiateur peut aussi se suspendre au...

Page 19: ...TB de puissance est quip des bornes de bo te class es pour accepter le fil correct d alimentation d nergie de taille Le circuit la minute valu e par fil 600V 60 C de branche est acceptable pour des r...

Page 20: ...ontacteur A1 doit tre d plac de la borne d extr mit du bornier de puissance borne la plus proche du contacteur ou de la plaque bornes de commande vers la borne A du bornier inf rieur borne centrale Le...

Page 21: ...ERMOSTAT NIVEAU UNIQUE 21 AVERTISSEMENT 1 Utilisez les fils Class 1 de NEC isole pour 600V minimum pour le tout le c blage de circuit de commande 2 Utiliser une cosse sertir en forme de fourche sur le...

Page 22: ...504 in3 MUH302 76 2 676 4 298 5 89 40 4 8260 cm3 MUH304 89 40 4 MUH256 89 40 4 MUH306 89 40 4 MUH402 119 54 0 MUH404 119 54 0 MUH508 30 265 8 171 4 119 54 0 648 in3 MUH502 76 2 676 4 435 1 119 54 0 10...

Page 23: ...URN LOUVERS ABOVE LEVEL OF THE UNIT DISCONNECT POWER BEFORE SERVICING IF EXTERNAL CONTROL IS USED ALSO DISCONNECT EXTERNAL POWER SUPPLY NE PAS RELEVER LES LAMES AU DEL A DU NIVEAU PREVU DE L APPAREIL...

Page 24: ...TRES GARANTIES EXPLICITES OU IMPLICITES ET TOUTES LES GARANTIES IMPLICITES DE QUALIT MARCHANDE ET D ADAPTATION UN BUT PARTICULIER D PASSANT LES GARANTIES EXPLICITES SUS MENTIONN ES SONT REJET ES ET EX...

Reviews: