55
4
55
Figure 11
≥
ø85 mm
S1825 - S1833 - S1847
Installation & Service Manual
www.zibro.com/download
3.03
≥
20
cm
<
20
cm
≥
20
cm
<
20
cm
G
The last 20 cm of the refrigerant pipe, close to the
connector must be kept straight. Bending can cause
leakage and is not covered by the warranty.
Figure 12
G
ATTENTION
All refrigerant work and refrigerant piping should comply with the local legislation, standards
and codes and should only be done by qualified and skilled people.
To disconnect the couplings:
Step 1: Shut down the A/C unit and unplug the electrical power cord from the wall outlet.
Step 2: Wait five minutes for the line pressure between the indoor compressor unit and outdoor condensing
unit to equalize.
Step 3: Pull the male coupling handle up and toward the male coupling to the full back position.
Step 4: Retract the Release Sleeve on the female coupling to release the male coupling half from the female
half.
Step 5: To seal and protect from dust, reinstall the protective cap and plug.
8.2 Connecting the coolant pipes for the S33xx models
a.
Fit a gland nut or suchlike to the piping and make a so-called “flare” at the end of the piping.
b.
Interior unit: Tighten the gland nut by hand to the piping on the interior unit and then tighten it
with a spanner and torque wrench as shown in fig. 13.
c.
Exterior unit: Tighten the gland nut by hand to the connections on the valves on the exterior unit
and then tighten it with a spanner and torque wrench as shown in fig. 13.
Summary of Contents for S(C) 33xx
Page 12: ...S3325 SC3325 S3331 SC3331 6 12 ...
Page 21: ...6 21 ...
Page 33: ...3 33 SC3325 S3331 SC3331 S3348 ...
Page 53: ...53 4 53 S3331 SC3331 S3348 SC3348 Figure 9 ...
Page 73: ...73 73 S3331 SC3331 S3348 SC3348 Figura 9 ...
Page 113: ...1 113 SC3325 S3331 SC3331 S3348 ...
Page 133: ...133 133 SC3325 S3331 SC3331 S3348 ...