UG-1083 ePAQ-9400
-
Copyright © 2016 QEI.
Test Panel
37
14.21
SAVE <A or B> Command
The ePAQ-9400 can contain up to two stored configurations (A and B) for use as
backups. Using the test panel SAVE and RESTORE commands, each configuration
file can be stored in non-volatile memory, and recalled when needed. Using
ConfigWiz 2.0, the user can assign a unique ID string for each configuration file. This
ID string will appear at the test panel user prompt to let the user know which
configuration file is active.
ePAQ-9400_A > SAVE B
14.22
RESTORE <A or B> Command
See section above. This command will restore either of the two backup configuration
that were saved using the SAVE command above. NOTE: A restart is required after
restoring a configuration file.
14.23 12BIT/16BIT Commands
These commands determine whether analog points (RA command) are read as 12 or
16 bit values. If 12 bit values are selected, the fill scale reading will be +/-2047. If 16
bit values are selected, the full scale reading is +/-32767.
ePAQ-9400_A > 16BIT