background image

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO ML-G11.X

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.PEAK DUO ML-G11.X

8

9

Installation Site

MOUNTING

OPTION

POSITION OF CLAMPS* [MM]

TEST LOAD 

PUSH / PULL** [Pa] 

DESIGN LOAD 

PUSH / PULL** [Pa] 

SAFETY 

FACTOR

CL1a

300 - 550

5400 / 2400

3600 / 1600

1.5

20 - 550

2000 / 2000

1330 / 1330

CL3

300 - 550

3000 / 2400

2000 / 1600

CL5

short side: 100 - 250

long side: 300 - 450

2400 / 2400

1600 / 1600

FB1

373

5400 / 2400

3600 / 1600

FB2

373

3000 / 2400

2000 / 1600

IP1

-

3000 / 2400

2000 / 1600

  The below mounting options are only possible under certain conditions.

MOUNTING

OPTION

POSITION OF CLAMPS* [MM]

TEST LOAD 

PUSH / PULL** [Pa] 

DESIGN LOAD 

PUSH / PULL*** [Pa]

SAFETY 

FACTOR

CL2a

20 - 300

2400 / 1600

1600 / 1065

1.5

CL2b

(without rails)

20 - 300

1700 / 1600

1130 / 1065

** 

***

Distance between outer edge of module and middle of the clamp; consider further details below.

Loads according to IEC 61215-2:2016 and UL 61730.

Test procedure according to IEC 61215-2:2016 and UL 61730. Loads for these mounting options do not fulfill the requirements 

of the standards.

2 Planning

2.3 Mounting options

2 Planning

2.3 Mounting options

MOUNTING OPTION

REQUIREMENTS

All

  The loads in the table are related to the mechanical stability of the solar modules. The mechanical 

stability of the mounting system including clamps has to be evaluated by the system supplier. The 

listed test load values have been determined with the following clamp parameters: clamp width = 

40 mm and clamp depth = 10 mm.

  The system installer is responsible for the determination of location-specific load requirements.

  Ensure that the connection cables of the junction box do not run between laminate and mounting 

rails.

  Modules bend under load. Therefore, sharp objects (e.g. screws, ballast stones, rail ends, rails 

with burrs or sharp corners) must not be placed near the module backside so as not to touch the 

laminate under load.

  Ensure that the junction boxes do not touch the mounting structure (e.g. shorts rails, ballast, etc.) 

or the rooftop under load. Clamps or insertion profiles etc. must not touch the glass (even under 

load).

  Unbalanced loads (e.g. snow overhangs, snowdrifts) which result in locally significantly increased 

loads must be removed or avoided by technical measures.

CL1a, CL2a, CL3,

FB1, FB2

  Ensure that module frame is fixed directly on the rail of the substructure (no spacer allowed 

between the module and substructure).

CL2b, CL3, FB2

  A minimum support depth of 15mm is required on the back side of the module. 

CL5

  The minimum required support depth on the module backside is 10 mm on long frame side and 

15 mm on short frame side. 

IP1

  Ensure minimum support depth of 15mm on the backside and 10mm on the front side of the 

module. 

FB1, FB2

  Use M8 corrosion-proof screws and washers (diameter ≥ 15.8 mm) for mounting slots (Detail A, 

Fig.1). Mounting screws and washers should have the same material properties.

Summary of Contents for Q.PEAK DUO ML-G11 Series

Page 1: ...Installation and operation manual Q PEAK DUO ML G11 X solar module series...

Page 2: ...e of the solar modules This manual Other applicable stipulations such as country specific regulations for pressure equipment operational safety hazardous goods and environmental protection Regulations...

Page 3: ...n MISUSE OR INCORRECT USE OF SOLAR MODULES VOIDS THE LIMITED WARRANTY AND MAY CREATE A SAFETY HAZARD AND RISK PROPERTY DAMAGE THIS INCLUDES IMPROPER INSTALLATION OR CONFIGURATION IMPROPER MAINTENANCE...

Page 4: ...ind loads Properly fastened to the ground the roof or the fa ade Forces acting on the module are relayed to the mounting substructure Ensures sufficient rear ventilation of the module Avoid the usage...

Page 5: ...m supplier The listed test load values have been determined with the following clamp parameters clamp width 40mm and clamp depth 10mm The system installer is responsible for the determination of locat...

Page 6: ...y be damaged by the occurrence of reverse currents caused by module defects ground leaks or defective insulation Ensure that the maximum reverse current load capacity indicated in the data sheet is me...

Page 7: ...ght and horizontally as shown Note Module damage may occur Never step on modules Do not subject modules to any mechanical stress Do not allow any objects to fall onto modules 3 Installation 3 2 Prepar...

Page 8: ...ectric arcs may result from the separation of a closed circuit These can result in life threatening injuries The danger increases when several modules are connected in series Please be aware of that t...

Page 9: ...el see page 3 Ensure correct polarity 4 Electrical connection 4 3 Connection of modules Use solar cables for the connection at the junction box outlet Only interconnect connectors of the same type and...

Page 10: ...ulations Warning Fire Risk Do not use light concentrators e g mirrors or lenses Ensure that the cabling is not exposed and or hanging and is protected from dirt moisture and mechanical friction 5 Grou...

Page 11: ...may occur Remove snow and ice carefully without force e g with a very soft broom Do not scratch off dirt Module cleaning has to be done by qualified personnel according to the state of the art and tak...

Page 12: ...n manual solar modules Q PEAK_DUO_ML G11 X_modules_series_2022 06_Rev02_EN HANWHA Q CELLS GMBH OT Thalheim Sonnenallee 17 21 06766 Bitterfeld Wolfen Germany EMAIL WEB TEL FAX sales qcells com www qcel...

Reviews: