INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.POWER-G5 / L-G5 • Q.PRIME-G5 / L-G5 – EN

INSTALLATION AND OPERATION MANUAL SOLAR MODULES Q.POWER-G5 / L-G5 • Q.PRIME-G5 / L-G5 – EN

2 PLANNING

2.3  Mounting options

Specifications

 

MODULE TYPE

MOUNTING OPTION

CLAMPING AREA

1

 [MM]

TEST-LOAD ACC. IEC 61215  
PUSH/PULL [PA] 

Q.POWER L-G5.1

Q.PRIME L-G5.1

CL1 (4 point clamping on 

long side)

208-417

5400/2400

CL1 (4 point clamping on 

long side)

0-625

2400/2400

CL3 (4 point clamping on 

short side)

0-250

2400/2400

FB1 (4 screws mounting 

on long module side)

345

5400/2400

IP1 (Slide-in / long 

module side)

5400/2400

IP1 (Slide-in / short 

module side)

2400/2400

Q.POWER-G5.1

Q.PRIME-G5.1

CL1 (4 point clamping on 

long side)

246-493

5400/4000

CL1 (4 point clamping on 

long side)

0-739

2400/2400

CL3 (4 point clamping on 

short side)

0-248

2400/2400

FB1 (4 screws mounting 

on long module side)

332

5400/4000

IP1 (Slide-in / long 

module side)

5400/4000

IP1 (Slide-in / short 

module side)

2400/2400

1

 

Distance between outer edge of module and middle of the clamp.

DISTANCE BETWEEN MODULES

 

Ä

 Maintain an interval of at least 10 mm between two modules along the short side

 

Ä

 Maintain an interval of at least 5 mm between two modules along the long side

MOUNTING OPTIONS CL1

 

Ä

Ensure, that the subconstruction does not run below the junction box.

 

Ä

Ensure, that the connection cables of the junction box don‘t run between laminate and substructure.

MOUNTING OPTION FB1

 

Ä

Use M8 corrosion-proof screws and washers (min. diameter 16 mm).

 

Ä

Ensure, that the connection cables of the junction box don‘t run between laminate and substructure.

• 

The fastening points are located on the backside of the module frame.

Module Selection

For detailed key electrical data, please refer to the actual 
data sheet referring to the relevant Module (available at 
www.q-cells.com). 

 

Ä

Only connect modules of the same type and the same 
power class.

Safety Factor

During normal operation, a module may generate a greater 
current and / or higher voltage than that determined under 
standardized test conditions. Please use a safety factor of 
1.25 for the following:

• 

Calculating the voltage measurement values (V

oc

) of 

components 

• 

Calculating the current measurement values (I

SC

) of 

conductors

• 

Sizing of control systems connected to the outlets of 
the solar modules 

 

Ä

Please follow the valid national guidelines for the 
installation of electrical systems.

Series Connection

Connection of modules in series is only permitted up to 
the maximum system voltage as listed in the applicable 
data sheet of all the relevant modules to be installed.  

 

Ä

Take into account all possible operating situations and all 
relevant technical norms and regulations when designing 
the system. It has to be ensured that the maximum 
system voltage, including all necessary safety margins, 
is not exceeded. 

 

Ä

Take the voltage limit of the inverter into account when 
determining the maximum number of modules in the 
string.  

Parallel Connection

Modules may be damaged by the occurrence of reverse 
currents (caused by module defects, ground leaks, or 
defective insulation).

 

Ä

Ensure that the maximum reverse current load capacity 
indicated in the data sheet is met. 

In order to limit reverse currents that may occur, we 
recommend using the following safety options:

1)  Layout with a limited number of parallel connected 

strings :

Without undertaking further current blocking measures, 
a maximum of two module strings may be operated in 
parallel on an inverter or MPP tracker.

2)  Layout with string fuses :

place fuses for each string of modules at the plus and 
minus ends. Observe the maximum permitted number 

of strings as indicated in the specifications provided by 

the respective string fuse manufacturer and the technical 
guidelines.

NOTE! 

When installing different product versions, the lowest 
minimum permitted reverse current load capacity applies.  

Inverters

Inverters with or without transformers may be used.

2.4  Electrical layout

2 PLANNING

Summary of Contents for Q.POWER-G5.1

Page 1: ...Valid for Africa Asia Europe Latin America South America Q POWER G5 1 L G5 1 Q PRIME G5 1 L G5 1 SOLAR MODULES INSTALLATION AND OPERATION MANUAL...

Page 2: ...and disposal Symbols and Labels The following symbols and labels are used throughout the Manual for ease of use SYMBOL DESCRIPTION Procedure with one or more steps Lists of items Ensure that when car...

Page 3: ...nts prior to installation of the solar power system Your financial success depends on the fulfillment of these requirements Other applicable documents In addition to this Manual following technical in...

Page 4: ...ces acting on the module are relayed to the mounting substructure Ensures sufficient rear ventilation of the module Guarantees long term stability Avoid the usage of different metals to prevent contac...

Page 5: ...mp Subconstruction Mounting profile TYPE OF INSTALLATION MODULE TYPE LONG SIDE SHORT SIDE INSTALLATION WITH CLAMPS Q PRIME L G5 1 Q POWER L G5 1 INSTALLATION ON MOUNTING POINTS Q PRIME L G5 1 Q POWER...

Page 6: ...ass Safety Factor During normal operation a module may generate a greater current and or higher voltage than that determined under standardized test conditions Please use a safety factor of 1 25 for t...

Page 7: ...cool and dry rooms The packaging is not weatherproof DANGER Risk of fatal injury due to electric shock Do not install damaged modules Inform your distributor of any damages immediately 3 1 Safety and...

Page 8: ...electric shock Only use dry insulated tools Do not carry out the installation alone Only install undamaged modules and components Do not modify the module e g do not drill any additional holes 3 2 Pr...

Page 9: ...at the inverter prior to separation Be sure to observe the specified time intervals after switching off the inverter High voltage components need time to discharge DANGER Risk of fatal injury due to e...

Page 10: ...l injury due to electric shock Ensure that all electrical components are in a proper dry and safe condition 4 3 Connection of modules 4 ELECTRICAL CONNECTION The 60 cell modules with min 1 000mm and f...

Page 11: ...odules by yourself Please contact an installer or Q CELLS Technical Customer Service Department Dispose of modules in accordance with the local disposal regulations The symbols on the products packagi...

Page 12: ...Qidong City Jiangsu Province China TEL 86 0 5138360 6222 FAX 86 0 5138360 6376 EMAIL sales hanwha qcells com WEB www q cells com Subject to change without notice Hanwha Q CELLS Installation_Manual_Q...

Reviews: