Operating Manual: PX-1C - Smoke Alarm Device with Radio Link
EN
61
EN
Fig. 17
Flat 1
Flat 2
Corridor
Flat 3
Flat 4
Alarm dir
ection
Example shared radio group
Flat = subgroup
Corridor = shared radio group
Alarm direction = to shared radio group
6.1 Setting up the radio group
The first device placed into service is Mas-
ter, and manages the installation of a radio
group. When setting up the master device
of a radio group, observe the following:
(1)
Push the split pin down sideways off
the activation button.
(2)
Push the activation button so that
it is flush.
Short acoustic signal
5
No other device is in learning mode.
(3)
Press and hold the radio button with
a split pin until the LED signal lamp is
continuously on.
(4)
Immediately release the radio button
as soon as the LED lights up.
5
Device is a max. of 10 minutes in
learning mode.