UV-O Odour Control Units
Technical and Operations Manual - Maintenance
38
Switch to the ‘On’ position.
6.3.3 Replacing the UV-O 1000 Filter
1.
Isolate the Unit from the mains power supply by turning the Rotary Mains Isolator
Switch to the ‘Off’ position.
2.
Double check that the mains power supply has been isolated.
3.
Undo the lock, unscrew the four Star Knobs anti-clockwise on the Front Panel and
open it.
4.
Remove the old filter element by sliding it out of its housing inside the Unit’s main
body, on the left-hand side.
5.
Spray the filter housing and mounting with a high quality degreaser and wipe down
with a suitable cloth or paper towel.
6.
Insert the new filter element by sliding it into the housing inside the Unit’s main body.
Note:
Ensure that the filter element is inserted in the correct orientation, with the arrows
printed on the end of the filter’s frame pointing in the direction of the airflow
through the Unit.
CAUTION
Ensure that the filter housing and mounting are completely dry before
inserting the new filter, closing the Front Panel and reconnecting the
mains power supply.
7.
Close the Front Panel, screw the four Star Knobs clockwise to tighten them and then
fasten the lock.
8.
Switch on the mains power supply to the Unit by turning the Rotary Mains Isolator
Switch to the ‘On’ position.
Figure 3
6
- UV-O 1000 Air Filter