
4
SECTION 2: CONTROLS
REMOTE OPERATION
On first use insert the batteries into the remote control handset—see battery replacement
section. With the mains supply connected to the fire and switched on the fire can be
operated.
Care
DO NOT drop - DO NOT immerse in liquids - DO NOT leave flat batteries in the unit -
Clean only with a dry cloth
.
As this product operates using infra-red, ensure there is a clear line of sight between the
handset and the appliance for it to operate effectively.
By pressing the ON/OFF button the operational features of
the fire are enabled; if you then press the LAMP button the
Visual effect will operate; if you then press the HEAT 1 but-
ton the 1kW heat setting will operate together with the Visual
effect; if you then press the HEAT 2 button the 2kW heat
setting will operate together with the Visual effect. From here
if you press a different button it will go back to that status - if
you press the O/OFF button it will turn the fire off. Please
note that it is possible to miss out steps once the operational
features are enabled e.g. if you press the ON/OFF button
then the HEAT2 button the fire will go straight to 2kW togeth-
er with the Visual effect.
NOTE: Each function is accompanied by an audible beep.
MANUAL OVER-RIDE OPERATION
If the Remote handset is mislaid or the batteries run out the fire can be operated manually
by use of the membrane pad situated next to the thermostat. With the mains supply con-
nected to the fire and switched on the fire can be operated.
By pressing the ON/OFF FUNCTION button the features of the
fire can be used. This is a single touch button and when pressed
sequences through the available functions.
NOTE: Each function is accompanied by an audible beep.
LED DISPLAY EXPLANATION
Red LED on LHS of pad illuminated: Fire in standby mode. (not
illuminated when other functions in use or fire is off)
Green LED on RHS of pad flashes 5 times then goes out: Visual
effect on.
Amber LED on RHS of pad flashes 5 times then goes out: Visual 1kW on.
Red LED on RHS of pad flashes 5 times then goes out: Visual 2kW on.
THERMOSTAT
The thermostat enables the room temperature to be controlled around a pre-set level and
can be used when the 1Kw or 2Kw switches are on. To set the thermostat, first set the
control at position
9
then turn on the heating elements and heat the room to the desired
temperature. When this temperature has been reached reduce the setting by turning the
control anti-clockwise towards a lower figure until you hear the thermostat click off and the
heat from the fan stops. When the room temperature drops the thermostat will turn the
selected heat setting on the fire back on again.
The thermostat control is designed to operate at room temperatures of 0 – 40
o
C.
At very low temperatures (approx. 6°C) the thermostat will NOT turn the fire off until the
temperature rises above approx. 8°C.
Push
button
Standby
Indicator
Function
Indicator
OFF / FUNCTION
Summary of Contents for XPG170
Page 11: ...11 LOG BED...