7
.1
PLACE OF INSTALLATION
The dehumidifier is suitable for indoor usage. For the convenience of
maintenance and inspection, some space around the machine should be
retained (800mm gap at least). In order to prevent condensation inside the
machine, the dehumidifier should not be put into the condition in which the air
temperature is below the dew point.
In addition, if the machine is installed outdoors, some protective measures
should be
taken
to prevent rain, snow and dust etc.
In any case the dehumidifier has to be installed on a horizontal ground or
platform, which has to be able to sustain the weight of it
.
After the
installation, it would be wise to re-check the ground or the platform on
which the dehumidifier has been placed. In case the dehumidifier has to be
mounted, the retaining base should be from stainless steel.
The dimension
s
of duct for process air and reactivation air should be in line
with ISO7807 recommended values. Ducting should be connected with
the connection part on flange.
Please
pay attention to the
following
notes about the duct
connection.
•
In order to reduce loss of static pressure, it is advice
d
to install with the
shortest
length of duct possible.
•
In order to ensure the maximum perfomance of the machine, all connctions
have to be done right, without any loss of air.
•
The duct should have a good capacity of thermal insulation, to prevent
moisture condensation inside or outside the duct surface.
•
To reduce noise and vibration transmitted along the duct,
high
quality,
soft
and strong airtight adapting pieces should be used in the joint parts.
•
The air valve
can
be installed in
side
the duct of process air and reactivation air
if
it is needed.
•
If the reactivation air is introduced from outdoor air, the reactivation air duct
should be high enough off the ground to prevent inhale of dust and debris,
meanwhile, it must be far away from some sources of pollution, such as
energy emissions, steam and gases. In order to prevent wet air outlet is
inhaled back into machine, the distance between the regeneration inlet air and
wet air outlet should be at least distant by 1 meter.
If the outlet air contains a high amount of moisture, droplets may form inside
the conduit. In this case, the drain should be positioned vertically so that the
droplets flow smoothly out of it. If installed horizontally, these droplets will
remain in the interior and may cause long-term corrosion of the pipeline.
•
11
ΕΝ
Summary of Contents for PDD 200M
Page 1: ...USER S MANUAL ENGLISH Desiccant Dehumidifier PDD 200M...
Page 2: ...LANGUAGES ENGLISH 3 21...
Page 17: ...10 FREQUENTLY ASKED QUESTIONS TROUBLESHOOTING 17...
Page 22: ...GR 22 1 l 8 l l l l l l l l l 3 l l l l l l l l l l l l l l l l...
Page 23: ...GR 23 24 2 l l l l l l l l PCB T 3 15A 250V 350V 3 l 2002 96 EC 27 2003 l CO2 l A B...
Page 24: ...1 2 3 4 5 15 6 7 1 8 9 10 4 GR 24 5 desiccant...
Page 25: ...GR 25 1 2 mm 5 2 5 3...
Page 26: ...GR 26 60 PID SCR 5 4...
Page 27: ...GR 27 60 5 5 5 6...
Page 29: ...29 GR 7 7 1 80 ISO7807 O...
Page 30: ...30 GR 7 2 7 2 1 1...
Page 31: ...GR 7 2 2 31 Puredry...
Page 32: ...GR 32 7 2 3 Volt 7 2 4 1 1 5...
Page 33: ...GR 33 8 1 PV SV PV OUT SET set 3 SV 3 3...
Page 35: ...15 15 Puredry GR 35 9...
Page 36: ...10 GR 36...
Page 37: ...11 GR 37 Puredry Hellas Puredry...
Page 38: ...Puredry Puredry Puredry Hellas EE service 15 38 GR...
Page 39: ...l link https www puredryhellas com egguiseis l email...