![PURE ED6100-LED Installation & Maintenance Instructions Manual Download Page 9](http://html1.mh-extra.com/html/pure/ed6100-led/ed6100-led_installation-and-maintenance-instructions-manual_1626408009.webp)
9
PROGRAMMING INSTRUCTIONS
Press the
button for at least 10 seconds to enter the menu. You can move through the menu by pressing the
or
buttons. When you have reached the required menu option, press the
button to enter the sub-menu. In
The sub-menu you can change the default setting by pressing
or
buttons. After you have changed the default
setting, simply press the
button to save the change. Wait for at least 10 seconds (without pressing any button) to
exit the complete menu structure.
SYMBOL
MEANING
ACTION TO BE TAKEN
Default Settings.
Resets all settings to factory settings.
Press the
button to select.
Anti-Air lock setting.
Each X hours the unit will purge, regardless of the condensate level.
Use the
or
buttons to
choose 1-99 hours.
0 = disabled, 8 = default
Purge time setting.
When the condensate level has reached a pre-defined level, the unit will purge
and open the valve for X seconds.
Use the
or
buttons to
choose 0.1-0.9 seconds.
0.3 = default
Alarm Cycle setting.
When the unit purges more than X consecutively times without pause, this
could mean that an illogical amount of condensate is being discharged. The
alarm output is activated.
Use the
or
buttons to
choose 1-99 times.
0 = disabled, 0 = default