PURE ED6100-LED Installation & Maintenance Instructions Manual Download Page 9

9

 

 

 
PROGRAMMING INSTRUCTIONS

 

Press the 

 button for at least 10 seconds to enter the menu. You can move through the menu by pressing the 

  

or 

 buttons. When you have reached the required menu option, press the 

 button to enter the sub-menu. In 

The sub-menu you can change the default setting by pressing  

 or 

 buttons. After you have changed the default 

setting, simply press the 

 button to save the change. Wait for at least 10 seconds (without pressing any button) to  

exit the complete menu structure.

 

SYMBOL 

MEANING 

ACTION TO BE TAKEN 

 

Default Settings. 
Resets all settings to factory settings. 

Press the 

 button to select. 

 

Anti-Air lock setting. 
Each X hours the unit will purge, regardless of the condensate level. 

Use the 

 or 

 buttons to 

choose 1-99 hours. 

0 = disabled, 8 = default 

 

Purge time setting. 
When the condensate level has reached a pre-defined level, the unit will purge 
and open the valve for X seconds. 

Use the 

 or 

 buttons to 

choose 0.1-0.9 seconds. 

0.3 = default 

 

Alarm Cycle setting. 
When the unit purges more than X consecutively times without pause, this 
could mean that an illogical amount of condensate is being discharged. The 
alarm output is activated. 

Use the 

 or 

 buttons to 

choose 1-99 times. 

0 = disabled, 0 = default 

 

 

Summary of Contents for ED6100-LED

Page 1: ...1 INSTALLATION MAINTENANCE INSTRUCTIONS 01 2016 ED6100 LED...

Page 2: ...fety when operating this product When handling operating or carrying out maintenance on this product personnel must employ safe engineering practices and observe all local health safety requirements r...

Page 3: ...ed The use of a ball valve is advisable The use of a venting line may be required 1 4b Side inlet connection Connect the outlet to an Oil Water separator We advise to use the nipple supplied with your...

Page 4: ...4 1 1 1 2 1 3a 1 3b 1 4a 1 4b 1 5 1 6 1 7 1 8 L N...

Page 5: ...le Connector screw 2x Screw gasket 2x Connector 2x Connector gasket 2x Electronics compartment with attached Earth cable Sensor module screw 4x Sensor module Sensor module O ring small Sensor module O...

Page 6: ...move the cap from the alarm connector to connect the alarm cables to the connector as shown below Caution is required as you may be working with hazardous voltages 2 Connect the cable to your alarm de...

Page 7: ...pe is not sufficient or if any other flow problem occurs a venting line must be installed to prevent an air lock Do not narrow the feed pipe when installing additional adapters or piping these may cau...

Page 8: ...warning AC Flashing Alarm cycle and alarm output activated The unit has purged more than the AC set value times without pause Unit works as normal Check why the alarm cycle has been activated and rese...

Page 9: ...G ACTION TO BE TAKEN Default Settings Resets all settings to factory settings Press the button to select Anti Air lock setting Each X hours the unit will purge regardless of the condensate level Use t...

Page 10: ...Closed alarm relay output Use the or buttons to choose NO or NC contacts NC default DO NOT CHANGE 1 default Sensing time setting When the condensate has reached a pre defined level the unit will wait...

Page 11: ...no debris left in the other parts of the drain 2 7 Use a 10mm Allen key to remove the plug and strainer Clean the strainer thoroughly Replace the strainer and plug using a 10mm Allen key 2 8 Reassemb...

Page 12: ...12 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11 2 12...

Page 13: ...top and 7 5 1 5 cm side 1 2 BSP or NPT 4 3 top and 2 9 0 6 side Outlet connection height 1 4 BSP 1 5 cm side 1 4 BSP 0 6 side Valve seals FPM Supply voltage options 230VAC or 115VAC or 24VAC or 24VDC...

Page 14: ...14 SERVICE CHART Date Description Name...

Page 15: ...15 DIMENSIONS mm...

Reviews: