Pulsar PSDCB05125C Manual Download Page 4

www.pulsar.pl                                                             PSDCB05125C            

 
 

 

4

 

 

 

Fig.3. The view of the PSU. 

 

1.4 Specifications:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 

      

Electrical parameters (tab. 3) 

Mains supply 

176÷264V AC  

Current up to 

0.95A@230VAC  

Supply power 

100W max.  

Efficiency 

80% 

Output voltage 

11V÷

13,8V DC – buffer operation 

9,5V÷13,8V DC – battery-assisted operation 

Output current 

 5x1A + 1A    battery charge 
 5x1A + 2A   battery charge 

Output current t

AMB

<30°C 

5x1 A + 1A battery charge - refer to chart 1 
5x1 A + 2A battery charge - refer to chart 1 

Output current t

AMB

=40°C 

5x0.8 A + 1A battery charge - refer to chart 1 
5x0.6A + 2A battery charge - refer to chart 1 

Voltage adjustment range 

12÷14VDC 

Ripple 

120mV p-p max. 

Battery charge current 

1A/2A max. @ 17Ah (± 5%) 

Short-circuit protection SCP 

LB5 STRIP 
5x F 1A glass fuse  
 

Summary of Contents for PSDCB05125C

Page 1: ...PSDCB05125C v 1 0 PSDCB 13 8V 5A 5x1A 17Ah Buffer switch mode power supply for CCTV EN Edition 2 from 25 11 2013 Supercedes the edition 1 from 31 01 2013 GREEN POWER CCTV ...

Page 2: ...ts and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices r...

Page 3: ...of the fuse block LB5 Tabela 2 Description of PSU components and connectors fig 3 Element no Fig 3 Description 1 PSU module 2 L N power supply connector 230V AC PE protection connector 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Ibat Sel...

Page 4: ...tage 11V 13 8V DC buffer operation 9 5V 13 8V DC battery assisted operation Output current 5x1A 1A battery charge 5x1A 2A battery charge Output current tAMB 30 C 5x1 A 1A battery charge refer to chart 1 5x1 A 2A battery charge refer to chart 1 Output current tAMB 40 C 5x0 8 A 1A battery charge refer to chart 1 5x0 6A 2A battery charge refer to chart 1 Voltage adjustment range 12 14VDC Ripple 120mV...

Page 5: ...0 7mm colour RAL 9003 Closing Cheese head screw x 2 at the front lock assembly possible Connectors Power supply Φ0 63 2 50 AWG 22 10 OutputsФ0 41 1 63 AWG 26 14 battery output BAT 6 3F 2 5 TAMPER output wires Notes The enclosure does not adjoin the assembly surface so that cables can be led Operation safety tab 5 Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 ...

Page 6: ...circuit Moreover the user shall be informed about the method of unplugging usually through assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230VAC...

Page 7: ...se of fuse damage the replacement of the same parameters is required In case of overload the output voltage is automatically shut off and so is the LED indicator The restoration of the voltage takes place immediately after the failure overload is over 4 2 Battery assisted operation In case of a main power outage the device is immediately switched into a battery assisted operation The PSU is equipp...

Page 8: ...hat within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of th...

Reviews: