background image

www.pulsar.pl                                                       

PSBS1024B                                                                  

BLUE POWER

     

 

1.4 Technical parameters:  

- Electrical parameters (Table 3)  
- Mechanical parameters (Table 4) 
- Safety of use (Table 5) 
- Operation parameters (Table 6) 

Table 3. Electrical parameters

 

PSU type: 

A (EPS - External Power Source) 

Mains supply 

230V AC / 50Hz (-15%/+10%) 

Current consumption 

0,2A @230V AC 

PSU’s power 

28W  

Efficiency 

80% 

Output voltage 

22V÷ 27,6V DC – buffer operation 
20V÷ 27,6V DC – battery operation 

Output current  

1A (without battery) 
0,8A + 0,2A battery charging 
0,5A + 0,5A battery charging 

Output voltage adjustment range 

24÷29V DC 

Ripple voltage 

30mV p-p max. 

PSU current consumption  

20 mA  

Battery charging current 

0,2A or 0,5A

– jumper selectable 

Short-circuit protection SCP 

Electronic - current limitation and/or activation of the F

BAT

 

melting fuse in the battery circuit (failure requires fuse 
replacement) 
Automatic return 

Overload protection OLP 

110-150% of the PSU power, manual restart (failure 
requires the disconnection of the DC output) 

Battery circuit protection SCP and reverse  
polarity connection 

F2A- current limitation, the F

BAT

 melting fuse (failure 

requires fuse replacement) 

Surge protection 

varistors 

Deep discharge battery protection UVP 

U<20V (

± 0,5V) – disconnection of battery terminal 

Tamper protection: 
- TAMPER output indicating enclosure opening or 
detachment from the wall 

 
- micro switch x 2 NC contacts (enclosure closed and 
mounted to the mounting base), 0,5A@50V DC (max.) 

Optical indication: front panel of the PSU 
- AC OK.; LED indicating  the AC power status 
 
- DC OK.; LED indicating  the DC supply at the PSU 
output  
 
- BAT OK.; LED indicating  the battery voltage 

 
- red, normal operation: permanently illuminated, 
failure: off 
- green, permanently illuminated, failure: off 
 
- green, permanently illuminated, 
failure: off 

Technical outputs: 
- EPS; output indicating AC power failure 
 
 
 
 
- PSU; output indicating no DC power/PSU failure  
 
 
 
- LoB output indicating low battery voltage 

 
-  OC type: 50mA max.  
 

Normal operation: L state (0V), 

 

failure: hi-Z state, 

- delay time 10s/60s (+/-20%) 

– jumper selectable 

T

AC

  

 
- OC type: 50mA max.  
 

Normal operation: L state (0V), 

 

failure: hi-Z state,  

 
- OC type, 50mA max.  
 

Normal operation (U

BAT

 >23V): L state (0V), 

 

failure (U

BAT

 <23V):  hi-Z state 

The power supply unit does not feature a battery detection 
function. 

Fuses:  
 

- F

MAINS

  

 

- F

BAT

 

 
T 500mA / 250V  
F 2A / 250V 

       
 
 
 
 
 
 
 

Summary of Contents for PSBS 1024B

Page 1: ...PSBS 1024B v 1 0 PSBS 27 6V 1A 2x7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 3 from 01 06 2016 Supercedes edition 2 from 14 04 2015...

Page 2: ...TS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3...

Page 3: ...RATIONS visualization available at www pulsar pl 1 Buffer power supply PSBS 27 6V relay module MPSBS 2x7Ah PSBS 1024B MPSBS 2x7Ah 2 Buffer power supply PSBS 27 6V 2x0 5A 2x7Ah PSBS 1024B LB2 2x0 5A AW...

Page 4: ...justment FBAT fuse in the battery circuit F2A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical outpu...

Page 5: ...Isolation transformer Printed Circuit Board see Table 1 Fig 2 TAMPER micro switch of tamper protection NC FMAINS fuse in the power supply circuit 230V T500mA 250V L N power supply connector 230V AC PE...

Page 6: ...tion F2A current limitation the FBAT melting fuse failure requires fuse replacement Surge protection varistors Deep discharge battery protection UVP U 20V 0 5V disconnection of battery terminal Tamper...

Page 7: ...operation unacceptable Surges during operation unacceptable Direct insolation unacceptable Vibrations and surges during transport According to the PN 83 T 42106 standard 2 Installation 2 1 Requirement...

Page 8: ...type page 9 section 3 3 6 Use the IBAT jumper to set the maximum battery charging current taking into account the battery parameters 7 Use the PBAT jumper to set to turn on off deep discharge battery...

Page 9: ...Short circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Unde...

Page 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Page 11: ...to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been condit...

Page 12: ...www pulsar pl PSBS1024B BLUE POWER 12 Pulsar Siedlec 150 32 744 apczyca Poland Phone 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl...