Pulsar PSBOC754813 Quick Start Manual Download Page 5

www.pulsar.pl 

 

 

 

 

PSBOC754813 

 

 

 

 

 
 

Mechanical specifications (tab. 3). 

Enclosure dimensions 

159 x 97 x 42 +23 [mm] (LxWxH)  (+/- 2) 

Net/gross weight 

0,59kg / 0,65kg 

Connectors 

power supply, technical outputs

: Φ0,63÷2,5   I/O PCB: Φ0,41÷1,63   

BAT battery outputs: 6,3F-2,5/40cm, 
Led indication output: 3-pin 5 mm connector 

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating specifications (tab.5). 

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

2. Installation. 
 

2.1 Requirements 

The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -

10°C to +40°C. 

 
The  device  shall  be  mounted  in  a  metallic  enclosure  (a  cabinet,  an  intended  case).  In  order  to  fulfil  LVD 

and  EMC  requirements,  the  rules  for:  power-supply,  encasing  and  screening  shall  be  followed,  according  to 
application.  

  
During normal operation, the total current drawn by the equipment may not exceed I=1A

*

.               

Maximum battery charging current: 0,3A

*

. Total device c battery: 1,3A max

 *

 

 
2.2. Installation procedure. 

1. Before installation of the power supply unit, make sure that 230VAC power if cut off.  
2. Mount the unit in the intended location.  
3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU 
terminal (marked with 

 - earth symbol).

 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the ‘PE’ terminal. Using the PSU 
without a properly made and fully operational shock protection circuit is UNACCEPTABLE! 
It can cause a device failure or an electric shock. 
 

 

 

4. Connect load/loads to proper output connectors of the power supply (positive pole is marked as +V, 
negative pole as -V) 
5. Connect the technical outputs to the central or other device. 
6. Connect the battery in accordance with the signs (colours). 
7. Once the tests and operation control have been completed, the enclosure/cabinet can be locked. 

                                                 

*

 

See chart 1

 

Summary of Contents for PSBOC754813

Page 1: ...PSBOC754813 v 1 0 PSBOC 54V 1 3A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 2 from 01 06 2016 Supercedes edition 1 from 13 05 2016 ...

Page 2: ...TS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenanc...

Page 3: ...bsence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB output indicating battery low voltage OC type 10 V V DC supply output 11 L N 230V AC power connector PE protection connector 12 LED indication on the...

Page 4: ...oad protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protection varistors Surge over voltage protection OVP 62V automatic recovery Deep discharge protection UVP U 38V 5 disconnection of the battery terminal Technical outputs EPS output indicating AC power failure PSU output indicating DC absence PSU failure ...

Page 5: ...ounted in confined spaces in accordance with the 2nd environmental class with normal relative humidity RH 90 maximum without condensation and temperature from 10 C to 40 C The device shall be mounted in a metallic enclosure a cabinet an intended case In order to fulfil LVD and EMC requirements the rules for power supply encasing and screening shall be followed according to application During norma...

Page 6: ...ted AC power absence is indicated by the AC diode going out green LED Fig 2 element 2 indicates DC power at the PSU output Under normal status the diode is permanently illuminated In case of a short circuit or an overload the diode is off green LED Fig 2 element 3 indicates battery voltage level Under normal status UBAT 46V the diode is permanently illuminated In case of decrease of battery voltag...

Page 7: ...rease of battery voltage UBAT 46V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 46V the contacts of the relay change over The power supply unit does not feature a battery detection function In the case of no battery or non battery connected the output is in the normal mode CAUTION In the Fig 5 the set of contacts shows a potential free st...

Page 8: ...days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer...

Reviews: