The main panel of the program has been formulated in such a way that it is possible to divide it into smaller 

areas, depending on the number of power supplies.  

The program enables both a visualisation and an analysis of the received data. Exceeding of the acceptable 

parameters  is  indicated  by  highlighting  in  red  the  appropriate  area  or  by  twinkling  of  the  indicator.  Particular  tabs 
contain a chart with an overview of the PSU parameters and failure memo along with the information about status 
and the electrical specifications of the technical outputs. 

 

The ”Power Security” program is available on our website: 

www.pulsar.pl

  

Its detailed description can be found in the manual of the program. 

 

 
 
 

6. Technical specifications.

  

Electrical specifications (tab.6). 
Mechanical specifications (tab.7). 
Operation safety (tab.8). 
Operating specifications (tab.9). 
Factory settings (tab. 10). 

 

Table 6. Electrical specifications. 

PSU type 

A, protection grade 1÷3, II environmental class 

Mains supply 

230V/AC  (-15%/+10%) 

Current consumption 

0,13 A  

Power frequency 

50Hz 

PSU’s power 

17 W 

Efficiency 

72% 

Output voltage 

11,0V÷13,8 V DC – buffer operation 
10,0V÷13,8 V DC – battery-assisted operation 

Output current 

- for grades 1, 2:  

 

 

 

Io = 0,58A + 0,6A battery charge 

- for grade 3: 

 

 

Io = 0,23A + 0,6A battery charge - (connection with 

ARC required, compliant with 9.2 – PN-EN 50131-1) 
 

Io = 0,116A + 0,6A battery charge 

- for general use: 
 

Io = 1,0A + 0,2A battery charge 

 

Io = 0,6A + 0,6A battery charge 

Output voltage setting, escalation and keeping 
time 

10ms / 34ms / 12ms 
 

Output voltage adjustment range 

12,0 V÷ 14,5 V  

Ripple voltage 

30 mV p-p max. 

Current consumption by the PSU systems 
during batter-assisted operation 

I = 22 mA 

Battery charging current 

0,2A / 0,6A –I

BAT 

jumper selectable

 

Low battery voltage indication 

Ubat < 11,5V, during battery-assisted operation 

Over voltage protection OVP 

U>15,5V, disconnection of the output voltage, automatic return 
(AUX+ disconnection)

 

Short circuit protection SCP 

200% ÷ 250% of the PSU power - current limiting and/or fuse 
fault in the battery circuit (fuse-element replacement required)

 

Overload protection OLP 

Program - equipment 

Battery circuit protection SCP and reverse 
polarity connection 

F2,0 A- current limiting, F

BAT

 fuse (failure requires fuse-element 

replacement)

 

Deep discharge battery protection UVP 

U<10,0 V (± 2%) – disconnection (-BAT) of the battery, 
configuration with jumper P

BAT

 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

- time lag, approx. 5s/140s/17m/2h 20m (+/-5%) 
- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

- type – electronic, max 50mA/30V DC, galvanic isolation 
1500V

RMS

 

Technical outputs: 
- EPS FLT; output indicating AC power failure 
 
- APS FLT; output indicating battery failure 
 
- PSU FLT; output indicating PSU failure  
 
- TAMPER output indicating enclosure opening 
and detaching from the mounting surface 

- microswitches x2, NC contacts (enclosure closed ad fixed to 
the mounting surface)

, 0,5A@50V DC (max.) 

Summary of Contents for PSBEN 1012B

Page 1: ...PSBEN 1012B v 1 0 PSBEN 13 8V 1A 7Ah EN Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Page 2: ...4 2 DEEP DISCHARGE BATTERY PROTECTION UVP 12 4 3 DYNAMIC BATTERY TEST 12 4 4 STANDBY TIME 12 4 5 BATTERY CHARGING TIME 12 4 6 OPERATION WITHOUT A BATTERY 12 5 REMOTE MONITORING OPTION WI FI ETHERNET R...

Page 3: ...cation of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs outputs with galvanic isolation collective failure input EXT IN EPS technical ou...

Page 4: ...ime 60h if the faults of the main power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 116A 0 6A battery charge General use if the PSU is n...

Page 5: ...om a battery STOP button disconnection of the PSU during battery assisted operation 5 pin activation of the acoustic indication indication on indication off Caption jumper on jumper off 6 VADJ potenti...

Page 6: ...ption 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector PE connector 6 B...

Page 7: ...proving a certain parameter that is to be displayed Fig 4 Control panel Table 3 A description of the buttons and LEDs of the LED panel parameter selection selection approval red LED indicates presence...

Page 8: ...e codes that can appear during the PSU s operation have been shown Each code is accompanied by an appropriate LED indication on the panel acoustic indication and switching of a dedicated technical out...

Page 9: ...9 6 or 19 2 values informing of the transmission s speed with or set the transmission s speed to 19200 which is displayed as 19 2 approve the setting with the OK button the abbr trS will be displayed...

Page 10: ...time lag T 2h 20m Caption jumper on jumper off APS FLT output indicating battery failure The output indicates a failure in the battery circuit Under normal status during correct operation the output i...

Page 11: ...nal Fig 8 Examples of connections In the option with tamper switches the VEXT jumper must be on It polarises the EXT IN input circuit therefore is required in such configuration The EXT IN input has b...

Page 12: ...y even after unplugging the device from mains The battery failure indication at the APS FLT output is automatically switched off The battery protection system against deep discharged remains on though...

Page 13: ...s In this mode the automation system allows adjustments of PSU s output voltage without indicating a failure connected with working of the battery CAUTION During operation without battery assistance t...

Page 14: ...s 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequenc...

Page 15: ...thernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correctly...

Page 16: ...n with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and memo re...

Page 17: ...0 116A 0 6A battery charge for general use Io 1 0A 0 2A battery charge Io 0 6A 0 6A battery charge Output voltage setting escalation and keeping time 10ms 34ms 12ms Output voltage adjustment range 12...

Page 18: ...Connectors Supply 0 63 2 50 AWG 22 10 Outputs 0 51 2 AWG 24 12 battery outputs BAT 6 3F 2 5 30cm TAMPER output wires 25cm Notes The enclosure does not adjoin the assembly surface so that cables can be...

Page 19: ...s of detaching the device from the mounting surface Proper installation is one of the requirements of the PN EN 50131 6 standard Fig 17 Fixing a tamper grip 2 Connect the power cables 230Vac to L N te...

Page 20: ...ers from damage The outputs will be battery powered The protection system is indicated by illuminating of the OVP red LED on the pcb board PSU FLT output status change into Hi Z high impedance by soun...

Page 21: ...voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of the PSU set 13V Fault in...

Page 22: ...ibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carri...