background image

 

 

 

Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of power-supply (I/P-
O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
 
3000V AC min. 
1500V AC min. 
500V AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100MΩ, 500V DC  

Operation parameters (tab.6). 

Operation temperature 

-10ºC...+40ºC  

Storage temperature 

+25ºC...+60ºC 

Relative humidity 

30%...90%, without condensation 

Vibrations during operation 

Unacceptable 

Impulse waves during operation 

Unacceptable 

Direct isolation 

Unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

2. Installation. 

 

2.1. Requirements. 
 

The  buffer  power-supply  shall  be  mounted  by  the  qualified  installer  having  appropriate  (required  and 

necessary for a given country) permissions and qualifications for connecting (operating) 230V AC installations and 
low-voltage  installations.  The  device  shall  be  mounted  in  closed  rooms,  according  to  the  environment  class  II,  of 
the normal air humidity (RH=90% max. without condensation) and the temperature within the range from -10°C to 
+40°C.  The  power-supply  shall  operate  in  a  vertical  position  so  that  free  and  convectional  air  flow  through 
ventilating holes of the casing is guaranteed. 

  
Before installation, the balance of the power-supply load shall be performed. During the normal operation, 

the sum of currents collected by receivers shall not exceed 

I=10A (P=138W max.)

, including

 

the maximum battery 

charging current 

Ibat. 

 

As  the  power-supply  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  in  the  power  supply  circuit  shall  be  guaranteed.  Moreover,  the  user 
shall  be  informed  about  the  method  of  isolation  of  the  power  supply  from  the  power  voltage  (usually  through 
assignment  and  marking  of  an  appropriate  fuse  in  the  fuse-box).  The  electrical  system  shall  be  made  in 
accordance with valid standards and regulations. 

 

2.2. Installation procedure. 

 

1.  Before installation is started, the voltage in the 230V power-supply circuit shall be isolated. 

2.  The power-supply shall be mounted in a selected location and connection cords shall be lead.  
3.  The  power  cables  (230  VAC)  shall  be  connected  to  L-N  terminals  of  the  power  supply.  The  earth  conductor 

shall be connected to the terminal marked by the earth symbol 

. The connection shall be made by means of 

a three-core cable (with a yellow and green PE protection wire). The power cables shall be lead to appropriate 
terminals of the connection board through bushing.  

 

 

The  circuit  of  the  shock  protection  shall  be  performed  with  a  particular  care,  i.e.  the 
yellow and green protection wire of the power cable shall be connected from one side to 

the terminal marked by the symbol of 

 in the casing of the power-supply. Operation of 

the  power-supply  without  the  properly  made  and  fully  operational  circuit  of  the  shock 
protection is UNACCEPTABLE! It can result in failure of devices and electric shock.

 

 
 

Summary of Contents for PSBC 10A12

Page 1: ...PSU B 13 8V S 10A 1 EL TR 17Ah MC PSBC 10A12 v 1 0 Buffer switch mode power supply unit EN Edition 1 from 14 th December 2010 Supercedes edition...

Page 2: ...rocedure 3 The power supply operation indication 3 1 Optical indication 3 2 Technical output 4 Service and operation 4 1 Overload or short circuit 4 2 Battery operation 4 3 Maintenance 1 Technical des...

Page 3: ...3 1 2 Block diagram fig 1 Fig 1 Block diagram of the power supply unit...

Page 4: ...ply operation 7 AC LED diode that indicates the presence of AC voltage 8 LB LED diode that indicates battery charging 9 OVP LED diode that indicates the activation of the OVP overvoltage protection 10...

Page 5: ...t 1 Separation transformer 2 Power supply unit board tab 1 3 TAMPER micro switch contacts of the anti sabotage protection NC 4 F2 fuse in the power supply circuit 230VAC 5 L N 230VAC power supply conn...

Page 6: ...6 Fig 3 View of the power supply unit...

Page 7: ...protection of the battery circuit and reverse polarity protection 10A current limitation F1 fuse failure requires replace of the fuse element UVP excessive discharge protection U 10 0 V 5 Technical ou...

Page 8: ...shall be performed During the normal operation the sum of currents collected by receivers shall not exceed I 10A P 138W max including the maximum battery charging current Ibat As the power supply is d...

Page 9: ...es not light no 230VAC supply GREEN DIODE lights DC voltage at the AUX output of the power supply unit does not light no DC voltage at the AUX output of the power supply unit Moreover the PSU is equip...

Page 10: ...e case of the short circuit to the AUX BAT output load 200 250 of the PSU power or incorrect connection of the battery the fuse F1 in the battery circuit becomes permanently damaged The restoration of...

Page 11: ...ing of the equipment to the service centre of the manufacturer 7 The repair period mentioned in item 5 may be prolonged if there is no technical capability to carry out the repairs and in the case tha...

Reviews: