background image

 

1.2. Block diagram (fig.1).

 

 

Fig.1. Block diagram of the PSU . 

1.3. Description of elements and connection links of the PSU   (tab.1, tab.2, fig.2). 

Table.1 

No. 

[fig.2] 

Description 

[1] 

A,  jumper 

- configuration of UVP battery protection function 

 

A= 

 protection function (disconnection) of the battery off 

 

A= 

  protection function (disconnection) of the battery on  

(disconnection U<10V) 

B, C jumpers 

- configuration of AC absence indication time lag  

 

B= 

, C= 

  time lag T= 5s 

 

B= 

, C= 

  time lag T= 140s 

 

B= 

, C= 

  time lag T= 1040s (17m 20s) 

 

B= 

, C= 

  time lag T= 2h 20m 30s 

Legend:

 

  

jumper installed  

  jumper removed

 

[2] 

START

 pushbutton (power activation without AC supply)

 

[3] 

P1

 potentiometer, voltage adjustment

 

[4] 

F1 

fuse in the battery circuit

 

[5] 

AC, LB, AUX 

optical indication of the power-supply unit operation

 

[6] 

AC, AUX

 Connection link of the output of the additional optical indication

 

[7] 

OUTPUTS 

connector (Tab.2)

 

[8] 

TAMPER,  

contact of antisabotage protection

 (NC) 

[9] 

F2 

witch in the power supply circuit (230V/AC) 

[10] 

 L-N  

power-supply connector 

230V/AC, 

 

PE protection connector

 

 

[11] 

BAT+/BAT-:  

outputs, battery connBAT=red, - BAT=black

 

[12] 

J,  jumper 

- the limitation of the battery charging current 

 : Ibat=200 mA max. 

 : Ibat=500 mA max. 

Legend:

 

  

jumper installed  

  jumper removed

 

Tab.1. The elements of the power-supply unit.

 

 

Summary of Contents for PSBBH 1012

Page 1: ...PSU B 13 8V S 1 0A 1 EL TR 7Ah HC PSBBH 1012 v 2 0 Buffer switching power supply unit in the ABS IP65 casing EN Edition 3 from the 17 th March 2011 Supercedes edition 2 from the 30 th March 2009...

Page 2: ...pace for 12V 1 2Ah or 7Ah battery horizontal or vertical position depending on configuration The casing features a microswitch indicating door front opening Information about additional equipment for...

Page 3: ...umper installed jumper removed 2 START pushbutton power activation without AC supply 3 P1 potentiometer voltage adjustment 4 F1 fuse in the battery circuit 5 AC LB AUX optical indication of the power...

Page 4: ...tery BAT red BAT black AUX AUX DC supply output AUX U AUX GND COM NC NO Technical output of AC absence relay assisted COM common contact NC normally closed contact without AC supply NO normally opened...

Page 5: ...uires replacement of the fuse element Overvoltage protection OVP U 22V varistor automatically recovered Excessive discharge protection UVP U 10 0 V 5 disconnection of BAT battery Technical outputs COM...

Page 6: ...osition Before installation is started the balance of the power supply load shall be performed During the normal operation the sum of currents collected by receivers shall not exceed I 1 0A P 14W max...

Page 7: ...tion indication 3 1 Optical indication The PSU is equipped with three diodes indicating operation status AC LB AUX placed on the PCB of the power supply unit AC red diode under normal status AC supply...

Page 8: ...U from the power supply network The PSU does not require performing any specific maintenance measures however in the case of significant dust rate its interior is recommended to be cleaned with compre...

Reviews: