Dimensions (LxWxH) 

199 x 97 x 42 [mm] 

Net/gross weight 

0,63kg / 0,68kg 

Protection class PN-EN 60950-1:2007 

I (first) - requires a protective conductor (PE) 

Connectors 

power-supply: 

Φ

0,63÷2,5   I/O PCB : 

Φ

0,41÷1,63   

battery output BAT: 6,3F-2,5/40cm, 
output of optical signalization: plug 3-pin 5 mm 

Electrical strength of insulation: 
-  between  input  (network)  circuit  and  output  circuits 
of power-supply (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-
FG) 
-  between  output  circuit  and  PE  protection  circuit 
(O/P-FG) 

 
 
3000 V/AC min. 
 
1500 V/AC min. 
 
500  V/AC min. 

Insulation resistance: 
-  between  input  circuit  and  output  or  protection 
circuit 

 
100 M

, 500V/DC  

Storage temperature 

-20ºC...+60ºC 

Vibrations and impulse waves during transport 

according to PN-83/T-42106 

 
1.3. Output current vs temperature. 
 

 

 

 
 
 
 
 

Graph 1.  
Allowable output current from the power 
supply depending on ambient temperature.  

2. Installation. 

 
2.1. Requirements. 
 
The  buffer  power  supply  shall  be  mounted  by  the  qualified  installer  having  appropriate  (required  and  necessary 

for  a  given  country)  permissions  and  qualifications  for  connecting  (operating)  230V/AC  installations  and  low  voltage 
installations.  The  device  shall  be  mounted  in  closed  rooms,  according  to  the  environment  class  II,  of  the  normal  air 
humidity (RH=90% max. without condensation) and the temperature within the range from -10°C to +40°C. 

 
The power supply shall be mounted in a close casing (a cubicle, a terminal device) and in order to fulfill LVD and 

EMC requirements the rules for power-supply, encasing and shielding shall be observed according to application. 

Due to the power supply design, the PE wire has to be connected to the corresponding connector of the 

supply unit. Operation without proper grounding of the power supply is not allowed! 

 
Prepare the power supply loading balance before installation:  
 

1.  Output current of 3,0A + 0,5A battery charging. 
2.  Output current of 2,5A + 1,0A battery charging. 

 

Total device c battery:  3,5A. max. 

 
 
2.2. Installation procedure. 

1. Before beginning installation, ensure that the power in the 230V AC power supply circuit is disconnected. 
2. Install the unit in the previously selected place. 
3. Connect the 230VAC power leads. Connect the PE cable (yellow-green) to an appropriate terminal on the 
power supply unit (marked with 

). 

 

The circuit of the shock protection shall be performed with a particular care, i.e. the yellow and green 

protection wire of the power cable shall be connected from one side to the terminal marked by the 

symbol of 

  in the casing of the power-supply. Operation of the power-supply without the properly 

made and fully operational circuit of the shock protection is 

UNACCEPTABLE! 

 It can result in failure of devices and electric shock. 

 

Summary of Contents for PSB1002435

Page 1: ...y supply occurs The power supply has the following protections short circuit SCP overload OLP and overvoltage OVP 1 2 Technical parameters Supply voltage 176 264V AC 50 60Hz Current consumption 0 90A 230VAC max Supply power 100W max Efficiency 83 Output voltage 27 6V DC buffer operation 19V 27 6V DC battery operation Output current 3A 0 5A battery charging 2 5A 1A battery charging Output current t...

Page 2: ...idity RH 90 max without condensation and the temperature within the range from 10 C to 40 C The power supply shall be mounted in a close casing a cubicle a terminal device and in order to fulfill LVD and EMC requirements the rules for power supply encasing and shielding shall be observed according to application Due to the power supply design the PE wire has to be connected to the corresponding co...

Page 3: ... of AC voltage ADJ Potentiometer output voltage adjust I1 I2 Jumper battery charging current configuration Ibat 0 5 A Ibat 1 0 A Legend jumper installed jumper removed B Battery terminal positive Fig 1 Description of terminals B Battery terminal negative Z1 Connector of optical signalization 2 4 Dimensions and fitting of the PSB1002435 power supply Fig 2 Dimensions of power supply 3 Maintenance Al...

Page 4: ...n as possible however not later that within 14 days from the delivering of the equipment to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be prolonged if there is no technical capability to carry out the repairs and in the case that the equipment has been accepted conditionally due to the failing of the warranty terms by the claimant 8 All the services rendered...