Pulsar POE042418B Manual Download Page 7

www.pulsar.pl                                                      POE042418B   

GREEN POWER CCTV PoE

 

 

 

the  connection.  The  power  cables  should  be  connected  to  the  appropriate  terminals  on  the  connection  board 
through the bushing.  

 

The shock protection circuit shall be done with a particular care: the yellow and green wire 

coat of  the  power  cable  should be connected to  the  terminal  marked  with  the  

  symbol  

in  the  PSU enclosure. Operation of the PSU without the properly made and fully operational 
shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  damage  to  the  equipment  or  an 
electric shock

 

 
4.  Connect  the  network  cables  (Ethernet)  to  the  PoE module:  supply voltage  is  present  only  at  the  AUX  sockets 
and the cameras should be connected to them. Pin assignment of the AUX and IN sockets is shown in the Figure 
4: 
 

 

 

Fig. 4. Pin assignment of the AUX and IN connectors. 

 
5. Use the F1/PTC1 ÷ F4/PTC4 jumpers to select the type of short circuit / overload protection of individual circuits. 
Jumper in the Fx position – melting fuse activation, PTCx – PTC fuse activation. 
6. If needed, the following technical connections can be made: 
- FPS technical output of the PSU status – indicates the voltage loss at any of the outputs (AUX1 ÷ AUX4). 
TAMPER indicating enclosure opening. 
7. Check the power supply output voltage: 
- output voltage of the unloaded power supply without a battery should amount to U=27,6V DC. 
8. Connect the batteries in series according to the color markings: 
- battery output (+V): BAT+ cable/ red 
- battery output (0V): BAT- cable / black 
9. Check the optical indication of the PSU status: green LED light on the PoE module. 
10. Close the cover after installing and checking the operation of the power supply. 

 
3.  Power supply operation indication. 

 

3.1. Optical indication. 

The PSU has 7 LED lights at the front panel: 
 

 

 
 

 

 
 

 

 

 

RED LED: 

 

on – The PSU supplied with 230V AC voltage 

 

off – no 230V AC mains supply 

 
RED LED: 

 

on – DC voltage at the output of the switch mode PSU  

 

off – no DC voltage at the output of the switch mode PSU 

 
RED LED: 

 

on – fuse failure at one of the AUX1…AUX4 outputs 

 

off – no failure 

 

 
 
GREEN LED: 

 

on – DC voltage at the AUX1…AUX4 output 

 

off – no DC voltage at the AUX1…AUX4 output 

 

Summary of Contents for POE042418B

Page 1: ...POE042418B v 1 0 PoE 27 6V 4x0 4A 2x7Ah Switch mode buffer power supply unit for CCTV EN Edition 1 from 09 01 2014 Supersedes the edition GREEN POWER CCTV PoE...

Page 2: ...Maintenance 1 Technical description 1 1 General description The PSU is designed for supply of up to 4 webcams requiring stabilized voltage of 24V DC 15 The PSU supplies voltage of 27 6V DC and total c...

Page 3: ...ns supply indication input 3 F1 F4 fuses in the AUX1 AUX4 F500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L4 voltage indication at the AUX outputs during normal oper...

Page 4: ...he module of the switch mode PSU 2 LED light indicating correct operation of the switch mode PSU 3 V1 ADJ potentiometer regulation of the power supply output voltage 4 PoE module 5 Connectors for conn...

Page 5: ...protection 4 x varistor Antisabotage protection TAMPER output indicating enclosure opening microswitch NC contacts enclosure closed 0 5A 50V DC max Optical indication of operation YES LED lights Techn...

Page 6: ...imum battery charging current is 0 2A Total current of the receivers battery is max 1 8A The power supply is designed for a continuous operation and is not equipped with a power switch Therefore an ap...

Page 7: ...position melting fuse activation PTCx PTC fuse activation 6 If needed the following technical connections can be made FPS technical output of the PSU status indicates the voltage loss at any of the ou...

Page 8: ...odule L1 for AUX 1 etc Activation of the short circuit overload protection of a given circuit is indicated by turning off one of the Lx LEDs 3 1 Technical outputs The PSU has the following indication...

Page 9: ...fuse In case of melting fuse activation it should be replaced with a fuse of the same type and of the same rated current 4 2 Battery operation In case of mains power loss the unit will instantly swit...

Page 10: ...service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally...