Pulsar MSRK Series User Manual Download Page 8

www.pulsar.pl 

                  MSRK series                                                  

 

 

 

 

3.3.  Technical outputs 

– relay. 

If the OC type outputs are not sufficient to control the unit, it is possible to use the AWZ639relay module 

changing technical outputs of the OC type to relay type. 

 

 

 

Fig. 5. The diagram of connecting the AWZ639 module.  

 

3.4.  Standby time.  

Battery-assisted operating depends on battery capacity, charging level and load current. To maintain an 

appropriate standby time, current drawn from the PSU in battery mode should be limited: 
       

Total current of the rec battery charging current must

n’t cross maximum current of power supply 

 

3.5.  Battery charging time. 

The  PSU  has  a  battery  circuit  charged  with  direct  current.  The  current  selection  is  done  with  use  of  the  I

BAT

 

jumpers. The table below shows how long does it take to charge a (fully discharged) battery up to min. 80% of its nominal 
capacity. 

 

Table 9. Battery charging time up to the capacity of  0,8. 

Battery 

Charging current 

0,2A 

0,5A 

1A 

7Ah -  9Ah 

32h 

– 36h 

13h - 15h 

17Ah - 20Ah 

28h - 32h  

14h - 16h 

28Ah 

23h 

40Ah 

36h 

 

3.6.  Running PSU on battery backup. 

Power supply allows you to run on battery backup when necessary. To do this, press the START button on PCB. 
 

4.  Operation and use. 

 

4.1.  Overload or short circuit of the PSU output (SCP on). 

The  AUX  output  is  equipped  with  an  electronic  protection.  If  power  supply  is  loaded  with  current  exceeding 

IMAX.  (load  110%  ÷  150%  of  PSU  power),  current  and  voltage  are automatically  limited.  Voltage  at  output  is  restored 
automatically after overload is removed.   

In case of of the short-circuit to the AUX, BAT output, or incorrect connection of the battery, the fuse F

BAT

 in the 

battery  circuit  becomes  permanently  damaged  and  the  restoration  of  the  voltage  at  the  BAT  output  requires  the 
replacement of the fuse. 

 

4.2.  Dynamic battery test. 

 

The  PSU  runs  a  battery  test  every  5  minutes.  It  is  done by  a  momentary  output  voltage  reduction  and  voltage 

measurement at the battery terminals. A failure is indicated when voltage drops below approx.12,2 V 
 

             4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU from the power 

supply  network.  The  PSU      does  not  require  performing  any  specific  maintenance  measures,  however,  in  the  case  of 
significant dust rate, its interior is recommended to be cleaned with  compressed air. In the case of a fuse replacement, 
use a replacement of the same parameters.  

Summary of Contents for MSRK Series

Page 1: ...USER MANUAL EN Edition 1 from 05 01 2021 Supersedes the edition Modules of the series MSRK v 2 0 The module of buffer power supply Grade 2 ...

Page 2: ...ns 2 Installation 2 1 Requirements 2 2 Installation procedure 3 3 Operating status indication 3 1 Optical indication 3 2 Technical outputs 3 3 Technical outputs relay 3 4 Standby time 3 5 Battery charging time 3 6 Running PSU on battery backup 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Dynamic battery test 4 3 Maintenance 1 Technical description 1 1 General desc...

Page 3: ... Block diagram fig 1 Fig 1 Block diagram of PSU 1 3 Description of components and connectors Table 1 Elements of the PSU pcb see tab 2a b c Element no Description START button launching from battery VADJ potentiometer adjustable output voltage FBAT fuse in the battery circuit Terminals AC AC power input EPS technical output of AC power loss indication hi Z state AC power failure 0V state AC power ...

Page 4: ...nfiguration Power supply unit 12V2A see Fig 2a IBAT IBAT 0 2 A IBAT IBAT 0 5 A Power supply unit 12V3A see Fig 2b IBAT IBAT 0 5 A IBAT IBAT 1 0 A Description jumper installed jumper removed Fig 2a View of PCB board of 12V2A model Fig 2b View of PCB board of 12V3A model ...

Page 5: ...ation Charging current jumper selectable 0 2 0 5A 0 5 1A Battery circuit protection SCP and reverse polarity connection FBAT fuse in case of a failure fuse element replacement required Deep discharge battery protection UVP U 10 V 0 5V disconnection of battery terminal Optical indication LEDs on PCB of power supply unit optionally additional LED optical indication see section 3 1 Technical outputs ...

Page 6: ...h the distance between the contacts of all poles in the disconnection state is not less than 3mm It is required to install an installation switch with a nominal current of min 3 A in the power supply circuits outside the power supply unit 1 Install the enclosure or cabinet and lead the cables through the cable ducts 2 Install the PSU module on mounting pins the mounting pins should be installed be...

Page 7: ...ional PKAZ168 module 3 2 Technical outputs The PSU is equipped with indication outputs EPS FLT technical output indicating 230 V power failure The output indicates 230 V power failure Under normal status with the 230 V supply on the output is shorted to ground GND In case of power failure the PSU will switch the output into hi Z high impedance state after a time about 30s APS FLT output indicating...

Page 8: ... battery backup when necessary To do this press the START button on PCB 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on The AUX output is equipped with an electronic protection If power supply is loaded with current exceeding IMAX load 110 150 of PSU power current and voltage are automatically limited Voltage at output is restored automatically after overload is removed ...

Page 9: ...ipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl...

Reviews: