Features: 

 

  built-in power supply module 

  compliance with norm EN50131-6:2017 in  

grade 1, 2 and II enviroment class 

  compliance with norm EN60839-11:2013 in  

grade 1, 2 and II enviroment class 

  DC 13,8 V uninterruptible power supply 

  available versions with current efficiencies: 

o

 

13,8 V: 2 A/3 A

 

  microprocessor-based automation system 

  dynamic battery test 

  battery circuit continuity control 

  battery voltage control 

  battery fuse status control 

  battery charging and maintenance control 

  deep discharge battery protection (UVP) 

 

battery output protection against short circuit and 

reverse connection 

 

battery charging current jumper selectable  

 

START function of manual switch to battery power 

 

LED optical indication 

 

EPS technical output of network loss - OC type 

 

APS technical output indicating battery failure   

– OC type  

 

optional module AWZ639 changing OC outputs into 

relay outputs 

 

additional accessories: set of LED optical indication 

PKAZ168 

 

protections: 

o

  SCP short-circuit protection 

o

  OLP overload protection 

 

warranty 

– 5 years from the production date 

 

Table of contents: 
1. Technical description. 

1.1. General description 
1.2. Block diagram 
1.3. Description of components and connectors 
1.4. Specifications 

2. Installation. 

2.1. Requirements 
2.2. Installation procedure 

3. 3. Operating status indication. 

3.1. Optical indication 
3.2. Technical outputs 
3.3. Technical outputs 

– relay. 

3.4. Standby time 
3.5. Battery charging time 
3.6. Running PSU on battery backup 

4. Operation and use. 
             4.1. Overload or short circuit of the PSU output (SCP on) 
 

4.2. Dynamic battery test 

             4.3. Maintenance.  
 

 

1.  Technical description. 

 

1.1.  General description. 

   Buffer power supply modules  is designed in accordance with the requirements of the (I&HAS) EN50131-6:2017 
and (Access Control) EN60839-

11:2013 standard, grade 1÷2 and II environmental class. The power supplies 

unitsare intended for for an uninterrupted supply of  I&HAS and Access Control devices requiring stabilized voltage 
of 12 V 

DC (±15%). 

Displaying parameters of the modules: 
 

Modules name   

Output voltage 

Output current max. 

MSRK2012 

13,8 V 

2 A 

MSRK3012 

13,8 V 

3 A 

Total current of the rec battery chargi

ng current mustn’t cross maximum current of power supply. 

     
   In case of power failure, a battery back-up is activated immediately 

 

Depending on a required protection level of the alarm system in the installation place, the PSU efficiency and the 

battery charging current should be set as follows: 

 
* Grade 1, 2 - standby time 12h: 
The 12h standby output current can be calculated from the formula: 

I=Q

AKU

/12 - I

Z

 

gdzie:  

Q

AKU

  

– minimum battery capacity [Ah] 

Iz 

– PSU current consumption (including optional modules) [A] (Table 4)

 

 

Summary of Contents for MSRK Series

Page 1: ...USER MANUAL EN Edition 1 from 05 01 2021 Supersedes the edition Modules of the series MSRK v 2 0 The module of buffer power supply Grade 2 ...

Page 2: ...ns 2 Installation 2 1 Requirements 2 2 Installation procedure 3 3 Operating status indication 3 1 Optical indication 3 2 Technical outputs 3 3 Technical outputs relay 3 4 Standby time 3 5 Battery charging time 3 6 Running PSU on battery backup 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Dynamic battery test 4 3 Maintenance 1 Technical description 1 1 General desc...

Page 3: ... Block diagram fig 1 Fig 1 Block diagram of PSU 1 3 Description of components and connectors Table 1 Elements of the PSU pcb see tab 2a b c Element no Description START button launching from battery VADJ potentiometer adjustable output voltage FBAT fuse in the battery circuit Terminals AC AC power input EPS technical output of AC power loss indication hi Z state AC power failure 0V state AC power ...

Page 4: ...nfiguration Power supply unit 12V2A see Fig 2a IBAT IBAT 0 2 A IBAT IBAT 0 5 A Power supply unit 12V3A see Fig 2b IBAT IBAT 0 5 A IBAT IBAT 1 0 A Description jumper installed jumper removed Fig 2a View of PCB board of 12V2A model Fig 2b View of PCB board of 12V3A model ...

Page 5: ...ation Charging current jumper selectable 0 2 0 5A 0 5 1A Battery circuit protection SCP and reverse polarity connection FBAT fuse in case of a failure fuse element replacement required Deep discharge battery protection UVP U 10 V 0 5V disconnection of battery terminal Optical indication LEDs on PCB of power supply unit optionally additional LED optical indication see section 3 1 Technical outputs ...

Page 6: ...h the distance between the contacts of all poles in the disconnection state is not less than 3mm It is required to install an installation switch with a nominal current of min 3 A in the power supply circuits outside the power supply unit 1 Install the enclosure or cabinet and lead the cables through the cable ducts 2 Install the PSU module on mounting pins the mounting pins should be installed be...

Page 7: ...ional PKAZ168 module 3 2 Technical outputs The PSU is equipped with indication outputs EPS FLT technical output indicating 230 V power failure The output indicates 230 V power failure Under normal status with the 230 V supply on the output is shorted to ground GND In case of power failure the PSU will switch the output into hi Z high impedance state after a time about 30s APS FLT output indicating...

Page 8: ... battery backup when necessary To do this press the START button on PCB 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on The AUX output is equipped with an electronic protection If power supply is loaded with current exceeding IMAX load 110 150 of PSU power current and voltage are automatically limited Voltage at output is restored automatically after overload is removed ...

Page 9: ...ipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl...

Reviews: