www.pulsar.pl
MSRK series
2
Features:
built-in power supply module
compliance with norm EN50131-6:2017 in
grade 1, 2 and II enviroment class
compliance with norm EN60839-11:2013 in
grade 1, 2 and II enviroment class
DC 13,8 V uninterruptible power supply
available versions with current efficiencies:
o
13,8 V: 2 A/3 A
microprocessor-based automation system
dynamic battery test
battery circuit continuity control
battery voltage control
battery fuse status control
battery charging and maintenance control
deep discharge battery protection (UVP)
battery output protection against short circuit and
reverse connection
battery charging current jumper selectable
START function of manual switch to battery power
LED optical indication
EPS technical output of network loss - OC type
APS technical output indicating battery failure
– OC type
optional module AWZ639 changing OC outputs into
relay outputs
additional accessories: set of LED optical indication
PKAZ168
protections:
o
SCP short-circuit protection
o
OLP overload protection
warranty
– 5 years from the production date
Table of contents:
1. Technical description.
1.1. General description
1.2. Block diagram
1.3. Description of components and connectors
1.4. Specifications
2. Installation.
2.1. Requirements
2.2. Installation procedure
3. 3. Operating status indication.
3.1. Optical indication
3.2. Technical outputs
3.3. Technical outputs
– relay.
3.4. Standby time
3.5. Battery charging time
3.6. Running PSU on battery backup
4. Operation and use.
4.1. Overload or short circuit of the PSU output (SCP on)
4.2. Dynamic battery test
4.3. Maintenance.
1. Technical description.
1.1. General description.
Buffer power supply modules is designed in accordance with the requirements of the (I&HAS) EN50131-6:2017
and (Access Control) EN60839-
11:2013 standard, grade 1÷2 and II environmental class. The power supplies
unitsare intended for for an uninterrupted supply of I&HAS and Access Control devices requiring stabilized voltage
of 12 V
DC (±15%).
Displaying parameters of the modules:
Modules name
Output voltage
Output current max.
MSRK2012
13,8 V
2 A
MSRK3012
13,8 V
3 A
Total current of the rec battery chargi
ng current mustn’t cross maximum current of power supply.
In case of power failure, a battery back-up is activated immediately
Depending on a required protection level of the alarm system in the installation place, the PSU efficiency and the
battery charging current should be set as follows:
* Grade 1, 2 - standby time 12h:
The 12h standby output current can be calculated from the formula:
I=Q
AKU
/12 - I
Z
gdzie:
Q
AKU
– minimum battery capacity [Ah]
Iz
– PSU current consumption (including optional modules) [A] (Table 4)