4. Operation and use. 

            4.1 Overload or short circuit of the PSU module output. 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module exceeds I

max

 

(load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 

automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load 
for approximately 1 minute. 

In case of of the short-circuit to the AUX, BAT output, or incorrect connection of the battery, the fuse F

BAT

 in 

the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the 
replacement of the fuse. 

 

     4.2 Running the  PSU module from the battery. 

 

The power supply module is equipped with the button on the PCB allowing to run the PSU from the battery, 

when needed. To do that, press and hold the 

START

 button on the unit board for 1 second. 

 

4.3  Deep discharge battery protection UVP. 

  The  power  supply  is  equipped  with  deep  discharge  battery  protection  (UVP).  If  the  voltage  at  the  battery 

terminals drops below 2

0V±0.5V during battery-assisted operation, the batteries will be disconnected. 

The battery 

protection is on when the P

BAT 

jumper is off.

 

 

 

Caution.  

It  is  not  recommended  to  disable  UVP  since  deep  discharge  of  the  batteries  reduces  their  ability  to 
store energy, their capacity and lifetime. 

 
 

 
4.4 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU module  from the 

power supply network. The PSU module  does not require performing any specific maintenance measures, however, in 
the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for MSRK 1024

Page 1: ...MSRK 1024 v 1 0 MSRK 27 6V 1A OC Buffer switch mode power supply module with automatic operation control EN Edition 1 from 11 06 2014 Supersedes the edition ...

Page 2: ...ar from the production date CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Running the PSU module f...

Page 3: ... 24 29V adjustment 4 FBAT fuse in the battery circuit F2A 250V 5 Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure indication hi Z state failure 0V state PSU status O K LoB technical output of low battery voltage indication hi Z state battery voltage UBAT 23V 0V state battery O K BAT...

Page 4: ...atic return Overload protection OLP 110 150 25ºC of power supply manual restart the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections F 2A current limitation FBAT fuse in case of a failure fuse element replacement required Surge protection varistors Excessive discharge protection UVP U 20V 5 disconnect of connection battery configuration by ...

Page 5: ...nsformer isolation 1 Output current 1A without battery 2 Output current 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total device current battery 1A max As the PSU module is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed...

Page 6: ...diode indicates the DC supply status in the output of the PSU module Under normal status the diode is permanently illuminated and in case of a short circuit or overload the diode goes off 3 2 Technical outputs The PSU module is equipped with indication outputs EPS technical output indicating AC power failure The output indicates AC power failure Under normal status with the AC supply on the output...

Page 7: ...n on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge battery protection UVP The power supply is equipped with deep discharge battery protection UVP If the voltage at the battery terminals drops below 20V 0 5V during battery assisted operation the batteries will be disconnected The battery prot...

Page 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper ...

Reviews: