- LoB output indicating battery low voltage 

 
- OC type, 50mA max.  
 

Normal operation (UBAT >23V): L state (0V), 

 

failure (UBAT <23V):  hi-Z state 

F

BAT  

fuse 

F2A / 250V  

 
 
Mechanical parameters (tab. 4). 

Enclosure dimensions 

86 x 63 x 35 (WxLxH) [mm] (+/- 2) 

Fixation 

Dowel pins  x4 (PCB fi=4,2 mm) 

Net/gross weight 

0,07kg/0,15kg 

Connectors 

Outputs: 

Ф0,41÷1,63 (AWG 26-14) 

Battery output BAT: 6,3F-2,5, 30cm 

 
Operating parameters (tab.5). 

Environmental class 

II 

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 
2. Installation. 
 

2.1. Requirements. 

The  buffer  PSU  module  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required for a  given  country)  for  230V/AC  and  low-voltage  installations.  The  unit  should  be  mounted  in 
confined  spaces,  in  accordance  with  the  II-nd  environmental  class,  with  normal  relative  humidity  (RH=90%  maximum, 
without condensing) and temperature from -

10°C to +40°C.  

The unit should be mounted in a metal enclosure (cabinet) in a vertical position so as to ensure free, convection 

air flow through the vents.

  

In order to meet the EU requirements, follow the guidelines on: power supply, enclosures and shielding:  

- according to application. The module requires 30-32V AC power supply with galvanic. (transformer) isolation.

 

 

 

1. Output current 1A (without battery) 
2. Output current 0,8A + 0,2A battery charge 
3. Output current 0,5A + 0,5A battery charge 

                                                        Total device c battery: 1A max. 

 

           As the PSU module is designed for a continuous operation and is not equipped with a power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 
          

 

2.2. Installation procedure. 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Install the enclosure or cabinet and lead the cables through the cable ducts. 
3. Install the PSU module on mounting pins (the mounting pins should be installed before the assembly of the  
    enclosure/cabinet). 
4. Deliver the AC voltage to the ~AC~ terminals. 
5. Connect the 

receivers’ cables to the +AUX, -AUX terminals of the terminal box on the PSU board. 

6. If needed, connect the device cables to the technical outputs: 
    - EPS; technical output indicating AC power failure 
    - PSU; technical output indicating PSU failure. 
    - LoB; technical output indicating low battery voltage 
7. Using the I

BAT 

 pins, determine the maximum battery charging current the should be determine, in accordance  

     with battery parameters. 
8. Using the P

BAT

 pins, determine whether the function of disconnecting the discharged battery U<20V (+/-5%) is to     

be on or off. 

The battery protection is on

 

if the P

BAT

 jumper is removed. 

9.  Make  the  connections  between  the  battery  and  the  power  supply  panel  paying  special  attention  to  the  correct 

polarity. 

Summary of Contents for MSRK 1024

Page 1: ...MSRK 1024 v 1 0 MSRK 27 6V 1A OC Buffer switch mode power supply module with automatic operation control EN Edition 1 from 11 06 2014 Supersedes the edition ...

Page 2: ...ar from the production date CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Running the PSU module f...

Page 3: ... 24 29V adjustment 4 FBAT fuse in the battery circuit F2A 250V 5 Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure indication hi Z state failure 0V state PSU status O K LoB technical output of low battery voltage indication hi Z state battery voltage UBAT 23V 0V state battery O K BAT...

Page 4: ...atic return Overload protection OLP 110 150 25ºC of power supply manual restart the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections F 2A current limitation FBAT fuse in case of a failure fuse element replacement required Surge protection varistors Excessive discharge protection UVP U 20V 5 disconnect of connection battery configuration by ...

Page 5: ...nsformer isolation 1 Output current 1A without battery 2 Output current 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total device current battery 1A max As the PSU module is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed...

Page 6: ...diode indicates the DC supply status in the output of the PSU module Under normal status the diode is permanently illuminated and in case of a short circuit or overload the diode goes off 3 2 Technical outputs The PSU module is equipped with indication outputs EPS technical output indicating AC power failure The output indicates AC power failure Under normal status with the AC supply on the output...

Page 7: ...n on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge battery protection UVP The power supply is equipped with deep discharge battery protection UVP If the voltage at the battery terminals drops below 20V 0 5V during battery assisted operation the batteries will be disconnected The battery prot...

Page 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper ...

Reviews: