1. Technical description. 
 

1.1. General description. 

The buffer power-supply module is used for uninterrupted supply of devices requiring stabilized voltage of 

12V/DC (+/-15%). 

The power-supply module provides voltage within the following range: 

U= 11,0V÷13,8 V 

DC 

of total current efficiency equal to 

Imax=2,5A. 

In case of power voltage decay, prompt switching to battery 

supply  occurs.  The  power-supply  module  has  the  following  protections:  short-circuit  (SCP),  overload  (OLP), 
overheat (OHP). It is adapted for  cooperation with the sealed lead-acid battery  (SLA). The power supply  module 
controls automatically the charging and maintenance process of the battery, what is more it is equipped with the 
BAT  output  protections:  short-circuit  and  reverse  polarity  protection.  The  power-supply  module  is  equipped  with 
excessive  discharge  protection.  In  addition,  the  PSU  module  offers  the  technical  output  (Cx,  NCx,  NOx)  used  for 
controlling the AC supply status.  

 

 

 

 

Information about types: 

Model 

Description 

 
MSRD-13,8V/2,5A 
MSRD 2512 

12V DC buffer (switching) power-supply module, with the total current capacity 
2,5A and output voltage 11,0V-13,8V. Equipped with the AC supply absence 
indication system (battery assisted operation) and battery excessive discharge 
protection. For installation on the DIN rail (TS35 mm).

 

 

 

 

 

 

 

 

 

 

Summary of Contents for MSRD-13,8V/2,5A

Page 1: ...2 0 Buffer switching power supply module with the AC absence indication output UVP battery protection in the casing for the DIN rail EN Edition 2 from the 07th April 2009 Supercedes edition 1 from the 25th September 2008 30092009 ...

Page 2: ...ge decay prompt switching to battery supply occurs The power supply module has the following protections short circuit SCP overload OLP overheat OHP It is adapted for cooperation with the sealed lead acid battery SLA The power supply module controls automatically the charging and maintenance process of the battery what is more it is equipped with the BAT output protections short circuit and revers...

Page 3: ... P potentiometer voltage adjustment 5 INPUTS OUTPUTS connector Tab 2 6 START pushbutton power activation with battery 7 STOP pushbutton power deactivation with battery 8 F switch in the battery circuit Version v 2 0 or higher Table 2 2 5 Description of power supply module outputs AC AC supply input 16V 22V AC BAT BAT DC supply output of the battery BAT red BAT black AUX AUX DC supply output AUX U ...

Page 4: ...ge setting range 11 5 V 14 0 V Voltage adjustment range 1 Ripple voltage 25mV p p max Output current 2 0 A max Current consumption by PSU module systems 25 mA max Battery charging current 500 mA max 7Ah U bat 10 0V or 200 mA max 1 2Ah U bat 10 0V 5 J dip switch function version v 2 0 or higher SCP short circuit protection 200 250 of supply power limitation of current and or fuse failure in the bat...

Page 5: ...plicable and required for the specific country for connecting interference with the 230V AC and low voltage systems The unit should be mounted in the non open premises in accordance with the II nd environmental class with the normal relative humidity RH 90 maximum without condensing and temperature within the range 10 C to 40 C The PSU module should be operated in the position ensuring that the ai...

Page 6: ...otentiometer P monitoring the voltage at the AUX output of the PSU module 8 Connect the battery in accordance with the indications BAT red to plus BAT black to minus the LB diode should go on and the lighting intensity should reduce with the charging time elapsed increasing 9 Once the tests and control operation have been completed lock the enclosure cabinet etc Fig 3 Installation procedure on the...

Page 7: ...f the PSU module power or incorrect connection of the battery the fuse F in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the replacement of the fuse 4 2 Battery assisted operation In the case of power failure in the unit will instantly switch to the battery assisted operation In order to activate the operation of the PSU from the bat...

Page 8: ...le cooperates with the sealed lead acid battery SLA After the operating period ends the power supply shall not be discarded but recycled according to valid regulations WARRANTY 24 months since the sale date 36 months since the production date THE WARRANTY IS VALID ONLY after presenting the invoice of the sale to which the claim refers Pulsar K Bogusz Sp j Siedlec 150 32 744 Łapczyca Poland Tel 48 ...