Pulsar MSR 2012 Manual Download Page 6

www.pulsar.pl                                                                                        MSR2012 

   

 

 

4. Operation and use. 

            4.1 Overload or short circuit of the PSU module output. 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module exceeds Imax 

(load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 

automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load 
for approximately 1 minute. 

In case of of the short-circuit to the AUX, BAT output, or incorrect connection of the battery, the fuse F

BAT

 in 

the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the 
replacement of the fuse. 

 

4.2 Battery-assisted operation. 

              In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

The PSU module is not equipped with a discharged battery disconnection system. 
 

 
4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU module  from the 

power supply network. The PSU module  does not require performing any specific maintenance measures, however, in 
the case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 

 
 

 

WEEE MARK 

 

According to the EU WEE Directive 

– It is required not to dispose of electric or electronic waste as 

unsorted municipal waste and to collect such WEEE separately. 

CAUTION!

 

The power supply  module unit is adapted for a sealed lead-acid battery (SLA). After the operation period it must not be disposed 

of but recycled according to the applicable law. 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Pulsar  

Siedlec 150,  32-744 Łapczyca, Poland 

Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50 

e-mail: 

[email protected]

[email protected]

 

http:// 

www.pulsar.pl

www.zasilacze.pl

 

 

Summary of Contents for MSR 2012

Page 1: ...MSR 2012 v 1 0 MSR 13 8V 2A Buffer switch mode power supply module with technical output FAC EN Edition 3 from 21 11 2016 Supersedes the edition 2 from 11 05 2015 ...

Page 2: ...scription of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU module is intended for an uni...

Page 3: ... AUX DC supply output AUX U AUX GND FAC AC absence technical output relay type CAUTION In Fig 2 the contact set in the potential free status corresponds to a state with no AC power AC power failure 4 LEDs optical indication AC AC voltage LB battery charge AUX output voltage DC 5 Connector to the external LED indicators 6 IBAT jumper battery charging current selection IBAT Ibat 0 2A IBAT Ibat 0 5A ...

Page 4: ...ement Automatic return Overload protection OLP 110 150 25ºC of power supply manual restart the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections 3 15A current limitation FBAT fuse in case of a failure fuse element replacement required Technical outputs FAC output indicating AC power failure relay type R 1A 30VDC 50VAC time lag approx 10s FBA...

Page 5: ...ct the device cables to the technical outputs FAC sygnalizacja stanu AC alarm panel controller indicator LED itp 7 Using the IBAT pins determine the maximum battery charging current the should be determine in accordance with battery parameters 8 Make the connections between the battery and the power supply panel paying special attention to the correct polarity 9 Connect the 230V AC power to the tr...

Page 6: ...assisted operation The PSU module is not equipped with a discharged battery disconnection system 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU module from the power supply network The PSU module does not require performing any specific maintenance measures however in the case of significant dust rate its interior is recommended to be cle...

Reviews: