Pulsar MSR 1512 Quick Start Manual Download Page 5

www.pulsar.pl

                                                     

            MSR1512

                                             

 

 

As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed about the method of unplugging (most frequently through separating and assigning an appropriate fuse in 
the fuse-box). The electrical system shall follow valid standards and regulations. 
            The device should be installed in the metallic enclosure (cabinet). In order to meet the UE requirements, the 
rules concerning: supply, development and shielding ought to be followed- accordingly to the application. The 
module requires 20-22V AC power supply with galvanic separation (transformer insulation). 

2.2 Installation procedure 
 

1. Install the enclosure or cabinet and lead the cables through the cable ducts. 
2. Install the PSU module on mounting pins (the mounting pins should be installed before the assembly of the 
enclosure/cabinet) 
3. Deliver the AC voltage to the ~AC~ terminals. 
4. Connect the receivers’ cables to the +AUX, -AUX terminals of the terminal box on the PSU module. 
5. If necessary, connect the device conductors to the technical outputs:  
 -  FAC; AC status indication (alarm panel, controller, indicator, LED, etc.)

  

6. Using the I

BAT 

 pins, determine the maximum battery charging current the should be determine, in accordance 

with battery parameters. 
7. Activate the ~230V/AC supply (the AC red diode and AUX diode should be permanently illuminated) 
8. Check the output voltage (the PSU voltage without load should amount to 13,6 V÷ 13,9 V, during battery 
charging 11 V÷ 13,8 V). If the value of the voltage requires adjustment, it should be set by the V

ADJ

 potentiometer, 

monitoring the voltage at the AUX output of the PSU module. 
9. Connect the battery in accordance with the signs: +BAT red to ‘plus’, -BAT black to ‘minus’, (the LB diode light 
should fade throughout the time of charging). 
10. Once the tests and control operation have been completed, lock the enclosure/cabinet. 
 
3. Operating status indication. 

 
3.1 LED indication 
The PSU module is equipped with three diodes indicating operating status: AC, LB, AUX.  

 

AC- red diode: under normal status (AC supply) the diode is permanently illuminated. The absence of AC 
supply is indicated by the AC diode going off.    

 

LB- red diode: indicates the battery charging process; the intensity of illumination is dependent on the 
charging current. 

 

AUXgreen diode: indicates the DC supply status in the output of the PSU module. Under normal status, 
the diode is permanently illuminated and in case of a short-circuit or overload, the diode goes off. 

 

3.2 Technical output: 
 

The PSU module is equipped with indication outputs: 

 

FAC - absence of AC supply output: Relay output indicates AC power failure. In case of power failure 
PSU module will switch relay contacts after 10s.  

 
In Figure 2 the configuration of contacts shows relay voltage-free state, which corresponds to the 
no AC network state (AC network failure). 
 
 

4. Operation and use. 

    4.1 Overload or short circuit of the PSU module output 

The AUX output of the PSU module is equipped with the PTC polymer fuse assisted protection. If the load 

of the PSU module exceeds I

max

 (load 110% ÷ 150% @25ºC of the PSU module  power), the output voltage is 

automatically cut off and indicated by the green diode going off. To restore the output power, cut off the output load 
for approximately 1 minute. 

In case of of the short-circuit to the AUX, BAT output, (load 200% ÷ 250% of the PSU module  power) or 

incorrect  connection  of  the  battery,  the  fuse  F

BAT

  in  the  battery  circuit  becomes  permanently  damaged  and  the 

restoration of the voltage at the BAT output requires the replacement of the fuse. 
 
      4.2 Battery-assisted operation 

Immediate battery reverting in case of main power outage. 
In order to run the PSU module from the battery only, connect the BAT connectors in accordance with the 

the signs: +BAT red to ‘plus’ and, -BAT black to 'minus’ of the battery. 

Summary of Contents for MSR 1512

Page 1: ...MSR 1512 v 2 1 MSR 13 8V 1A Buffer switch mode power supply module EN Edition 3 rd 16 Dec 2011 Supersedes 2 nd 12 Feb 2009 edition ...

Page 2: ...ons 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical output 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU module is intended for an uninterrupted supply to devices requiring stabilised volta...

Page 3: ...ly output AUX U AUX GND FAC technical output for no AC network relay type In Figure 2 configuration of contacts shows relay voltage free state which corresponds to the state signalling no AC network AC network failure 4 LED indication AC LED for AC voltage LB LED for battery charge AUX LED for DC voltage 5 Connector to an external LED indicators AC and AUX 6 IBAT pins battery charging current sele...

Page 4: ...the fuse element Technical outputs FAC indicates AC power failure R relay type 1A 30Vdc 50Vac max Time lag about 10s FBAT fuse F2A 250V Mechanical parameters tab 4 Dimensions 85x 58x25 WxLxD 2 Mounting Dowel pins x4 PCB fi 4 2 mm Net Gross weight 0 07kg 0 12kg Connection Otputs Ф0 41 1 63 AWG 26 14 Battery output BAT 6 3F 2 5 30 cm Operating parameters tab 5 Operating temperature 10ºC 40ºC Storage...

Page 5: ... should fade throughout the time of charging 10 Once the tests and control operation have been completed lock the enclosure cabinet 3 Operating status indication 3 1 LED indication The PSU module is equipped with three diodes indicating operating status AC LB AUX AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode go...

Page 6: ...rectly to the main office of the manufacturer 5 The warranty applies to complete equipment accompanied by a properly filled warranty claim with a description of the defect 6 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 7 The repair pe...

Reviews: