2
1.2 Specifications:
- electrical specifications (tab.2)
- mechanical specifications (tab.3)
Table 2.
Supply voltage
13,8V DC
Current consumption
40mA max.
Voltage of low battery indication
U<11,5V +/- 3%
Technical outputs:
- FAC; output indicating AC power
failure
- FPS; output indicating DC
absence/PSU failure
-FLB output indicating low battery
voltage
- relay type: 1A@ 30VDC/50VAC, time lag: approx. 10s.
CAUTION! In Fig.2. the contact set in the potential-free status
corresponds to a state with no AC power (AC power failure).
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z level, time
lag: 10s.
- OC type, 50mA max., normal status: L (0V) level, failure: hi-Z level
- OC type, 50mA max., normal status: (U
BAT
>11,5V): L (0V),
failure: (U
BAT
<11,5V): hi-Z level
LED indication :
- presence of AC power
–
presence of DC voltage at the
PSU output
- battery voltage level
-red LED (fig.1, element 1).
Under normal status (AC supply) the diode
is permanently illuminated. The absence of AC supply is indicated by
the AC diode going out.
Caution: the LED indicates absence of AC power if the loss lasts minimum
10s.
-green LED (fig.1, element 2)
indicates DC power at the PSU output.
Under normal status the diode is permanently illuminated. In case of a
short circuit or an overload, the diode is off.
- green LED (fig.1, element 3)
indicates battery voltage level. Under
normal status (U
BAT
> 11,5V) the diode is permanently illuminated. In
case of decrease of battery voltage (U
BAT
< 11,5V) the diode is off.
Operating conditions
temperature: -10
o
C÷40
o
C, relative humidity : 20%...90%, without
condensation
Storage temperature
-20ºC...+60ºC
Table 3.
D
imensions
110 x 44 x 55 (LxWxH) [mm] (+/-2)
Fixing
M3 screws, mounting plate adjusted for PSB13,8V series power supplies
Connectors
Ф
0,41÷1,63 (AWG 26-14)
Net/gross weight
0,1/0,13 kg
2.1. Requirements.
The module is to be mounted by a qualified installer, holding relevant permits and licenses (applicable and
required for a given country) for 230V/AC interference and low-voltage installations. The unit should be mounted in
confined spaces, in accordance with the 2nd environmental class, with normal relative humidity (RH=90% maximum,
without condensation) and temperature from -10°C to +40°C.
The module shall be mounted with a PSU of PSB 13,8V series in a metal enclosure (cabinet, intended device). In
order to fulfil LVD and EMC requirements, the rules for: power-supply, encasing and screening shall be followed,
according to application.
It is crucial to connect the PE wire to the appropriate PSU terminal.
2.2. Installation procedure.
1. Before installation of the module, make sure that the PSB 13,8V PSU supplying LEDs are disconnected
from the 230V AC mains supply.
2. Mount the module on the PSB 13,8V power supply unit.
3. Cut the BAT+, BAT- leads in the PSB 13,8V PSU, separate and connect to the module, following the
diagram. (fig.2).
4. Cut the leads of the signal connector in the PSB 13,8V power supply unit, separate and connect to the
module, following the diagram. Connect the Lac, Ldc, GND leads of the PSU with appropriate outlets on the
automation module. (see fig. 4).
5. Connect the technical outputs of the other device.
6. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to the appropriate PSU terminal
(marked with
- earth symbol).