![Pulsar Imp 10 Instruction Manual Download Page 27](http://html1.mh-extra.com/html/pulsar/imp-10/imp-10_instruction-manual_1624673027.webp)
Page21
Control Relay Set-up
The control relays are energised to turn the control “ON” (start process
function), and de-energised to turn the control “OFF” (stop process
function). In this way, loss of power will ensure that the pumps are turned
“OFF”.
To set a
control
relay, set the
first parameter
for the relay to equal
2
(for
control).
E.g.
Setting
Relay 1
for control purposes
P210 = 2
Setting
Relay 2
for control purposes
P220 = 2
The
second parameter
for each relay determines the
function
of the control
relay, using the example of
Relay 1
, the
control function
can be selected
from the options available in parameter
P211
.
For full details of all available alarm options please refer to
P211, 221 Relay
Function…
If P210, 220 = 2(control
) tables in Chapter 5.
The
third parameter
and
fourth parameter
are set to determine the switch
points for the
control
relay.
The
control
functions are started and stopped at
the “
ON
” and “
OFF
” setpoints. To
set
a
control down
function (reduce
level) then set “
ON
”
higher than
“
OFF
”. To
set a
control up
function
(increase level) then set “
ON
”
lower than
“
OFF
”.
For example using Relay 1
Control Down Control Up
P213
“ON” Setpoint
P213
“ON” Setpoint
Higher than Lower than
P214
“OFF” Setpoint
P214
“OFF” Setpoint
Loss of Echo Set-up
When a relay is assigned to Loss of Echo (LOE) or fault condition, it will be
set as an alarm relay which will be de-energised to turn the alarm (LOE)
“ON”, and energise to turn the alarm (LOE) “OFF”. In this way, loss of
power will ensure that the alarm is activated.
To set an
alarm
relay, set the
first parameter
for the relay to equal
1
E.g.
Setting
Relay 1
for Alarm purposes
P210 = 4
When a relay is assigned to LOE no further parameters are required.
Summary of Contents for Imp 10
Page 1: ...IMP IMP IMP IMP INSTRUCTION MANUAL...
Page 2: ......
Page 4: ......
Page 16: ...Page 10 3 Wire Source mode the power for the loop is supplied by the IMP IMP IMP IMP...