Pulsar HPSB 5048C Manual Download Page 6

www.pulsar.pl

                                                               

HPSB5048C                                                    

GREEN POWER

 

 

 

6

 

RED LED: 

 

on 

– the PSU is supplied with 230V AC  

 

off 

– no 230V AC supply  

 

GREEN LED: 

 

on 

– DC voltage in the AUX output of the PSU 

 

off 

– no DC voltage in the AUX output of the PSU 

 

2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

                                      Before installation, prepare a PSU load balance: 

 
                                      1. Output current 4,5A + 0,5A battery charge

*

 

                                      2. Output current 4A + 1A battery charge

                                      3. Output current 3A + 2A battery charge

*

 

                                     Total device c battery: 5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
 

2.2 Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE (PSU module connector). Use a three-core cable (with a yellow and green PE protection wire) to 
make the connection. Lead the cables to the appropriate clips through the insulating bushing of the connection 
board. 
 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the 

receivers’ cables to the terminals V+ (+), V-(-) of the PSU module.  

5. Connect the power (~230V) 
6. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=54V DC.   
7. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT 

– cable / GND / black. 

8. Check the PSU operation indicator: green LED on the power supply module. 
9. After installing and checking proper working, the enclosure can be closed. 
 

 
3. Operating status indication. 

The PSU is equipped with two diodes on the front panel:

 

 

 
 

                                                 

*

 

Refer to chart 1

 

Summary of Contents for HPSB 5048C

Page 1: ...HPSB 5048C v 1 0 HPSB 54V 5A 4x17Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 18 03 2016...

Page 2: ...Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical des...

Page 3: ...2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Batter...

Page 4: ...current tAMB 40 C 3A 0 5A battery charge refer to chart 1 2 5A 1A battery charge refer to chart 1 1 5A 2A battery charge refer to chart 1 Voltage adjustment range 48 56VDC Ripple 150mV p p max Curren...

Page 5: ...s can be led Forced cooling built in fan Table 4 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input a...

Page 6: ...The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected...

Page 7: ...ed with the discharged battery disconnection system During the battery assisted operation reducing voltage below 38V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and a...

Page 8: ...equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they...

Reviews: