Pulsar HPSB 5048C Manual Download Page 2

www.pulsar.pl

                                                               

HPSB5048C                                                    

GREEN POWER

 

 

 

2

 

Features: 

 

 

DC 54V/5A uninterruptible power supply*  

 

fitting battery: 4x17Ah/12V  

 

wide range 

of mains supply: 176÷264V  

 

built-in power factor correction system (PFC)   

 

high efficiency 85% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

jumper selectable battery charge current  
0,5A/1A/2A 

 

 

battery output full protection against short-circuit 
and reverse polarity connection  

 

LED indication  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection (AC input)  

 

against sabotage 

 

overload protection (OLP) 

 

overheat protection OHP 

 

 forced cooling - built-in fan 

   warranty 

– 2 year from the production date   

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 
4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Disconnection of discharged battery 
4.3 Maintenance

 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 

48V DC (+/-15%).

 

The PSU provides voltage of 

U=54V DC.

 Current efficiency: 

 

                                     1. Output current 4,5A + 0,5A battery charge

*

 

                                     2. Output current 4A + 1A battery charge

                                     3. Output current 3A + 2A battery charge

*

   

                                                 Total device c battery: 5A max

*

 

In case of power decay 230V, a battery back-up is activated immediately. The PSU is constructed based on the 

switch mode PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can 
accommodate a 4x17Ah/12V battery. A micro switch indicates door opening (front cover). 

 

The power supply housing has space for additional modules (fuse blocks, voltage regulators and DC/DC 
converters). Optional power supply configurations are available at the website

www.pulsar.pl

 

 

 
 
 
 
 
 
 
 
 
 
 

                                                 

*

 

Refer to chart 1

 

Summary of Contents for HPSB 5048C

Page 1: ...HPSB 5048C v 1 0 HPSB 54V 5A 4x17Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 18 03 2016...

Page 2: ...Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical des...

Page 3: ...2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Batter...

Page 4: ...current tAMB 40 C 3A 0 5A battery charge refer to chart 1 2 5A 1A battery charge refer to chart 1 1 5A 2A battery charge refer to chart 1 Voltage adjustment range 48 56VDC Ripple 150mV p p max Curren...

Page 5: ...s can be led Forced cooling built in fan Table 4 Operation safety Protection class PN EN 60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input a...

Page 6: ...The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected...

Page 7: ...ed with the discharged battery disconnection system During the battery assisted operation reducing voltage below 38V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and a...

Page 8: ...equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they...