www.pulsar.pl                                                      HPSBOC3524C                                                              

GREEN POWER plus

 

 

6

 

       

Operation safety (tab.5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

       
      Operating parameters (tab.6)

 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

Before installation, prepare a PSU load balance. 
 

1.  Output current 3A + 0,5A battery charge

*

 

2.  Output current 2,5A + 1A battery charge

*

  

                                         Total device c battery: 3,5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 
 

 
 
 
 
 

                                                 

*

 

See chart 1

 

Summary of Contents for GREEN POWER PLUS HPSBOC 3524C

Page 1: ...HPSBOC 3524C v 1 1 HPSBOC 27 6V 3A 2x17Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 8 from 01 06 2016 Supercedes edition 7 from 01 04 2015 GREEN POWER plus...

Page 2: ...ircuit of the PSU output SCP on 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring...

Page 3: ...e module s see fig 2 Element no Description 1 LED indicating presence of AC power 2 LED indicating presence of DC power 3 LED indicating correct battery voltage 4 EPS AC absence technical output relay...

Page 4: ...lsar pl HPSBOC3524C GREEN POWER plus 4 Fig 2 The view of the PSU Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 Output terminals of the PSU Fig 3 The view of t...

Page 5: ...PSU s enclosure a microswitch NC contacts enclosure closed 0 5A 50V DC max LED indication AC diode indicating AC power status AUX diode indicating DC power status at the PSU output BAT diode indicatin...

Page 6: ...nstallation 2 1 Requirements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required a...

Page 7: ...ck protection circuit is UNACCEPTABLE It can cause a device failure or an electric shock 4 Connect the receivers cables to the terminals V V of the PSU module 5 Connect the power 230V 6 Connect the ba...

Page 8: ...esponds to a state with no DC power PSU failure LoB technical output indicating battery voltage OC type output Under normal status UBAT 23V the output is connected to ground L level 0V In case of decr...

Page 9: ...following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures however in case of significant dust rate its interior is rec...

Page 10: ...ipal waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the a...

Reviews: