Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

 
     Operating parameters (tab.6) 

Operating temperature 

-

10ºC...+40ºC (see: chart 1) 

Storage temperature 

-20

ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insulation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

 

Chart 1. Acceptable output current from the PSU depending on ambient temperature. 

 

 
2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

           Before installation, prepare a PSU load balance. During normal operation, the total current drawn by 
the device  may not exceed I = 3A

*

.  Maximum battery charge current: 0,5A

*

. Total device c battery: 

3,5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
 
 
 

 
 

                                                 

*

 

Refer to chart 1 

 

Summary of Contents for Green Power HPSB 3512C

Page 1: ...HPSB 3512C v 1 0 HPSB 13 8V 3A 17Ah Buffer switch mode power supply unit EN Edition 8 from 24 10 2016 Supersedes edition 7 from 11 08 2014...

Page 2: ...SU intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 3A 0 5A for battery charging In case of pow...

Page 3: ...1 The block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors see tab 2 3 green LED indicates AC power 4 P1 pot...

Page 4: ...www pulsar pl HPSB3512C GREEN POWER 4 Fig 2 The view of the PSU...

Page 5: ...e polarity connection PTC polymer fuse Surge protection varistors Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Sabotag...

Page 6: ...ements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and necessary for a giv...

Page 7: ...the power 230V 6 Connect the battery mind the colours battery output V BAT cable red battery output 0V BAT cable GND black 7 Check the PSU operation indicator green LED 8 Check the PSU output voltage...

Page 8: ...quipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they m...

Reviews: