background image

www.pulsar.pl                                                               HPSB3512C                                               

GREEN POWER

 

 

 

2

 

 

Features: 

 

 

DC 13,8V/3A  uninterruptible power supply

*

  

 

fitting battery: 17Ah/12V 

 

wide range 

of mains supply: 176÷264V  

 

high efficiency 76% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

battery charge current 0,5A 

 

battery output full protection against short-circuit 

and reverse polarity connection 

 

 

LED indication  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection  (input AC) 

 

against sabotage 

 

overload protection (OLP) 

  warranty – 2 year from the production date   

 

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of elements and connectors of the PSU 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Disconnection of discharged battery 
4.3 Maintenance

 

 

 
1. Technical description. 

 
1.1 General description.

 

A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 

12V DC (+/-15%).

 

The PSU provides voltage of 

U=13,8V DC 

with output current of 

I=3A

 

+ 0,5A  for battery charging

*

In case of power 

decay, a battery back-up is activated immediately.  The PSU is constructed based on the switch mode PSU, with high 
energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can accommodate a 17Ah/12V 
battery. A micro switch indicates door opening (front cover). 

 

During normal operation, the total current drawn by the equipment may not exceed I = 3A

*

.  

 Maximum battery charging current: 0,5A

*

.  

Total device c battery: 3,5A max

*

 

OPTIONAL POWER SUPPLY CONFIGURATIONS:  

(visualisation available at: 

www.pulsar.pl) 

 

BATTERY 17Ah: 

1.

 

Buffer power supply unit HPSB 13,8V/3x1A/17Ah. 

- HPS  LB4 3x1,0A (AWZ576 or AWZ575) + 17Ah 

2. Buffer power supply unit HPSB 13,8V/6x0,5A/17Ah.

 

- HPS  LB8 6x0,5A (AWZ580 or AWZ578) + 17Ah 

3. Buffer power supply unit HPSB 13,8V/12V/3A/17Ah.

 

- HPS RN500 (13,8V/12V) + 17Ah 

4. Buffer power supply unit HPSB 13,8V/12V/3x1A/17Ah.

 

- HPS RN500 (13,8V/12V) + LB4 3x1,0A (AWZ576 or AWZ575) + 17Ah 

5.

 

Buffer power supply unit HPSB 

13,8V/5V÷7,4V/2A/17Ah.

 

HPS DCDC20 (5V÷7,4V/2A) + 17Ah 

 
BATTERY 7Ah: 

                                                 

*

 

Refer to chart 1 

 

Summary of Contents for Green Power HPSB 3512C

Page 1: ...HPSB 3512C v 1 0 HPSB 13 8V 3A 17Ah Buffer switch mode power supply unit EN Edition 8 from 24 10 2016 Supersedes edition 7 from 11 08 2014...

Page 2: ...SU intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 3A 0 5A for battery charging In case of pow...

Page 3: ...1 The block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors see tab 2 3 green LED indicates AC power 4 P1 pot...

Page 4: ...www pulsar pl HPSB3512C GREEN POWER 4 Fig 2 The view of the PSU...

Page 5: ...e polarity connection PTC polymer fuse Surge protection varistors Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnect of connection battery Sabotag...

Page 6: ...ements The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 230V AC installations and low voltage installations required and necessary for a giv...

Page 7: ...the power 230V 6 Connect the battery mind the colours battery output V BAT cable red battery output 0V BAT cable GND black 7 Check the PSU operation indicator green LED 8 Check the PSU output voltage...

Page 8: ...quipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they m...