background image

www.pulsar.pl                                                                 HPSB2512B                                              

GREEN POWER

 

 

5

 

W

H

D

 
1.4 Specifications:  
- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operation safety (tab.5) 
- operating parameters (tab.6) 
 

      

Electrical parameters

 (tab. 3) 

PSU type 

A (EPS - External Power Source) 

Mains supply 

 

176÷264V AC 

Current up to 

0,45A@230VAC 

Power frequency 

50÷60Hz  

Supply power 

35W max.  

Efficiency 

74% 

Output voltage 

13,8V DC – buffer operation 
9,5V÷13,8V DC – battery-powered operation 

Output current t

AMB

<30°C 

2A + 0,5A battery charge - refer to chart 1 

Output current t

AMB

=40°C 

1,4A + 0,5A battery charge- refer to chart 1 

Voltage adjustment range 

12÷14VDC 

Ripple 

120mV p-p max. 

Battery charge current 

0,5A max. @ 7Ah (± 5%) 

Short-circuit protection SCP 

electronic 

Overload protection OLP 

PTC polyme fuse 

Overvoltage protection OVP 

U>115% ÷ 150% of the output voltage (set), power cut off, 
automatic return 

Excessive discharge protection UVP 

U<9,5 V (± 5%) – disconnection of battery terminal 

LED indication:  
- AC diode indicating AC power status 
- AUX diode indicating DC power status at 
the PSU output 

 
- red, normal status – on, failure: off 
- green, normal status – on, failure: off  

Sabotage protection: 
- TAMPER indicates enclosure opening 

 
- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

 

 
Mechanical parameters (tab. 4) 

Enclosure dimensions 

250 x 250 x 80+8  [mm] (WxHxD) 

Fixation 

See figure 2 

Fitting battery 

7Ah/12V (SLA) max. 
160x90x75mm (WxHxD) max  

Net/gross weight 

1,7  / 1,9 kg 

Enclosure  

Steel plate DC01, thickness: 0,7mm, colour: RAL 9003 

Closing 

Cheese head screw x 2 (at the front),  (lock assembly possible) 

Connectors 

Power-supply: Φ0,63-2,50 (AWG 22-10) 
Outputs: Φ0,63-2,50 (AWG 22-10) 
Battery output BAT: 6,3F-2,5  
TAMPER output: wires  

Notes 

The enclosure does not touch the assembly surface so that cables can be led. 
Convectional cooling. 

     

Operation safety (tab.5) 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between input and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Summary of Contents for GREEN POWER HPSB 2512B

Page 1: ...HPSB 2512B v 1 0 HPSB 13 8V 2A 7Ah Buffer switch mode power supply unit EN Edition 5 from 05 06 2014 Supercedes the edition 4 from 10 02 2014...

Page 2: ...o devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output current of I 2A 0 5A for battery charging In case of power decay a battery back up is activate...

Page 3: ...ab 2 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 BAT GND battery outputs BAT red GND black 6 TAMPER contact sabotage protection NC 7 Additional connector for LED indi...

Page 4: ...www pulsar pl HPSB2512B GREEN POWER 4 Fig 2 The view of the PSU...

Page 5: ...C power status at the PSU output red normal status on failure off green normal status on failure off Sabotage protection TAMPER indicates enclosure opening microswitch NC contacts enclosure closed 0 5...

Page 6: ...convectional air flow through ventilating holes of the enclosure Before installation prepare a PSU load balance During normal operation the total current drawn by the device may not exceed I 2A Maxim...

Page 7: ...amount to U 13 8V DC 9 After installing and checking proper working the enclosure can be closed 3 Operating status indication 3 1 LED indication of operating status The is equipped with two diodes on...

Page 8: ...ater that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the r...