OPERATION
Receptacles and Extension Cords
Only use high quality, well-insulated, grounded extension cords in good condition with generator receptacles. Extension
cords should have a minimum rating of 125 Volts AC, 20 Amps and should be kept as short as possible to minimize voltage
drop. Follow each load manufacturer’s power rating recommendation when selecting receptacle and extension cord.
Do not connect 3-phase loads to generator.
CAUTION!
12 Volt 8.3 Amp Output is for charging batteries only!
WARNING!
1
2
Extension Cord Selection
Refer to the below table to ensure the extension cord used has the capacity to carry the required load. If the size of the
cable is inadequate it can cause a voltage drop, which can damage the electrical device and cord.
Current
(Amps)
Load (Watts)
Maximum Cord Length
120V
240V
#8 Wire
#10 Wire
#12 Wire
#14 Wire
#16 Wire
2.5
300
600
X
1000 ft.
600 ft.
375 ft.
250 ft.
5
600
1200
X
500 ft.
300 ft.
200 ft.
125 ft.
7.5
900
1800
X
350 ft.
200 ft.
125 ft.
100 ft.
10
1200
2400
X
250 ft.
150 ft.
100 ft.
50 ft.
15
1800
3800
X
150 ft.
100 ft.
65 ft.
X
20
2400
4800
175 ft.
125 ft.
75 ft.
X
X
25
3000
6000
150 ft.
100 ft.
X
X
X
30
3600
7200
125 ft.
65 ft.
X
X
X
120 Volt AC, 20 Amp receptacle
• Two 120 Volt AC, 20 Amp receptacles.
• One 120 Volt AC,30Amp RV receptacle
• 120 / 240 Volt AC, 30 Amp twist lock receptacle (NEMA L14-30).
• This receptacle has a 20 Amp push-to reset circuit breaker to protect against overload.
• Each socket is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 2400 watts (2.4 kW) at 20 Amps.
• Use extension cords having a minimum rating of 125 Volts AC, 20 Amps.
• This receptacle has a 30 Amp push-to reset circuit breaker to protect against overload.
• This receptacle is rated to operate 120 Volt, AC, single phase, 60Hz loads requiring up to 3600 watts (3.6 kW) at 30
Amps. It is also rated to operate 240 Volt AC, single phase, 60Hz loads requiring up to 7,200 watts (7.2 kW).
• Use a NEMA L14-30 plug with this receptacle.
• Use a 4-wire cord rated for 240 Volts AC, 30 Amps to the plug. You can use the same 4-wire cord to operate a 120 Volt
load.
120 / 240 Volt AC, 30 Amp locking receptacle