6.4. Technical outputs. 

The PSU is equipped with galvanically isolated indication outputs changing status after a specified event: 
 

 

EPS FLT 

– output indicating 230 V power loss

The output indicates 230 V power loss. Under normal status 

– with the 230 V supply on, the output is closed. In 

case of power failure, the PSU will switch the output into the open position after a time lag determined in the „EPS” 
configuration menu (see section 6.3.3, Table 10). 

 

 

APS FLT 

– output indicating battery failure.

  

The output indicates a failure in the battery circuit. Under normal status (during correct operation) the  

output is closed. In case of failure, the PSU will switch the output into the open position. Failure can be triggered by 
the following events: 
 

 

- faulty batteries 

 

 

- undercharged batteries 

 

 

- disconnected batteries 

 

 

- high resistance of the battery circuit 

 

 

- battery voltage below  23 V during battery-assisted operation 
- battery fuse failure 
- no continuity in the battery circuit 

 

 

PSU FLT 

– output indicating PSU failure

.  

The  output  indicates  the  PSU  failure.  Under  normal  status  (during  correct  operation)  the  output  is  closed.  In 

case of PSU failure, it will switch into the open position. Failure can be triggered by the following events: 
 

 

- U

AUX1, AUX2

 output voltage below 26 V 

 

 

- U

AUX1, AUX2

 output voltage over 29,2 V 

 

 

- battery charging circuit failure 

 

 

- blown F

AUX1

 or F

AUX2 

fuse - exceeding the rated current of the PSU 

- activation of overvoltage protection OVP 
- mains supply voltage over 254 V AC 
- mains supply voltage below 195 V AC 
- to high battery temperature (>65 

°C) 

- temperature sensor failure, t < -20 

°C or t > 80 °C 

- enclosure opening - TAMPER 
- internal damage of the PSU 

 

 

The technical outputs have been made with galvanic isolation between the PSU’s systems and the  

attached devices. 
 

 

Fig. 10. Electrical diagram of technical outputs.  

 

 

 

 

ALARM - technical output of collective failure indication.

 

Output indicating collective failure. In the case of failure at any EPS, APS, or PSU output or at the EXTi 

input, the collective failure signal ALARM will be generated. 

 
 

CAUTION! 

In  Fig.2  the  set  of  contacts  shows  a  potential-free  status  of  the  relay,  which 

corresponds to power supply collective failure of the PSU. 

 

 
 
 
 

 
 
 
 
 
 

Summary of Contents for EN54-5A28

Page 1: ...EN54 5A28 v 1 1 EN54 27 6V 5A 2x28Ah power supply unit for fire alarm systems EN Edition 5 from 31 01 2019 Supersedes the edition 4 from 12 01 2016 LED Version ...

Page 2: ...failure codes and information messages 17 6 3 PSU CONFIGURATION 19 6 3 1 Performing battery test tSt 20 6 3 2 EXTo output ON OFF Eto 21 6 3 3 Setting the delay time for EPS output EPS 21 6 3 4 Acoustic indication ON OFF bUZ 22 6 3 5 LED Display Dimmer dIS 23 6 3 6 Setting the communication address Adr applies to cooperation with PowerSecurity 24 6 3 7 Setting the transmission speed trS applies to ...

Page 3: ...30 7 7 BATTERY TEMPERATURE MEASUREMENT 31 7 8 STANDBY TIME 31 8 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 32 8 1 COMMUNICATION VIA THE USB TTL INTERFACE 32 8 2 ETHERNET NETWORK COMMUNICATION 32 8 3 THE WI FI WIRELESS COMMUNICATION 33 8 4 RS485 NETWORK COMMUNICATION 34 8 5 POWERSECURITY PROGRAM 35 9 TECHNICAL PARAMETERS 37 Table 12 Electrical parameters 37 Table 13 Mechanical parameters 38...

Page 4: ...ation port with implemented MODBUS RTU protocol Power Security is a free application for remote monitoring of power supplies for PC and Android Phones remote monitoring options WiFi Ethernet RS485 USB remote battery test additional modules required cooperation with optional EN54 LB4 or EN54 LB8 fuse modules optical indication of PSU overload OVL acoustic indication of failure adjustable delay for ...

Page 5: ...ual Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial connection cable Keys to lock the power supply 2 pieces Cable tie 190x4 8 12 pieces ...

Page 6: ...t YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Battery fuse failure indication YES YES Charging circuit failure indication YES YES Low output voltage indication YES YES High output voltage indication YES YES Indication of power supply failure YES YES Overvoltage protection YES YES Short circuit pr...

Page 7: ... Output current Imax b 5 A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing RAL 3001 red with battery housing for two 28 Ah 12V batteries The PSU works with maintenance free lead acid batteries made with AGM technology or gel technology 4 2 Block diagram The PSU has been manufactured based on a high efficiency syst...

Page 8: ... battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC AC power input EPS FLT technical output of AC power failure indication open AC power failure closed AC power O K PSU FLT technical output of PSU failure indication open failure closed PSU operation O K APS FLT technical output of battery failure open ba...

Page 9: ...mponents of the PCB of the EMC filter Fig 3 Component No Description FMAINS fuse in the power supply circuit 230 V T6 3 A 250 V L N power supply connector 230 V protective connector Connector for connecting the PSU Fig 3 The view of the EMC filter ...

Page 10: ... module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x28 Ah batteries 9 Embossing for cable gland 10 Embossing for cable gland WiFi antenna or cable communication interface 11 Embossings for concealed wires 12 Lock 13 Battery connectors positive BAT red negative BAT black ...

Page 11: ...he casing As the PSU performs a periodic battery test measuring the resistance of connections special attention should be paid to the proper connection of the cables to the batteries Installation cables should be firmly connected to the battery side terminals and to the power supply connector If necessary it is possible to permanently disconnect the battery from the power supply systems by removin...

Page 12: ...lective failure of the PSU EPS FLT technical output of AC power loss indication PSU FLT technical output of PSU failure APS FLT technical output of the battery failure EXTi input of collective failure 5 Install the batteries in a designated area of the enclosure see Fig 4 Connect the batteries with the PSU paying special attention to the correct polarity Batteries must be connected in series using...

Page 13: ... Description Additional information moves the pointer on the screen next screen selection selection approval green LED indicating 230 V voltage yellow LED indicating exceeding the Imax a current or power supply overload section 6 9 6 10 yellow LED indicating PSU failure section 6 2 3 yellow LED indicating battery failure yellow LED ALARM indicating collective failure green LED AUX1 indicating powe...

Page 14: ...7 The description of display symbols Symbol Description Additional information AUX1 output voltage V Factory setting 27 6 V 20 C AUX2 output voltage V Factory setting 27 6 V 20 C Total current of the receivers A Io I AUX1 IAUX2 Resistance of the battery circuit Ω Section 7 6 Battery temperature C Section 7 7 Mains supply voltage V 230 V mains supply voltage indication Failure history Section 6 2 6...

Page 15: ... mΩ the power supply unit will indicate a failure The measurement result is displayed with a resolution of 0 01 ohm 6 2 4 Battery temperature indicator t C Battery voltage indicator displays the measured temperature of the batteries The temperature is used by the automatic control system for compensation of the battery charging voltage The measurement result is displayed with a resolution of 1 C 6...

Page 16: ...taneously indicate several failures Thanks to this solution codes of all failures and their priority can be previewed in the FLc menu In the FLc menu each press of the OK button on the panel displays the next error code that caused the failure If there are multiple failures at the same time pressing the OK button will display the next code The display order of failures is arranged by priority of i...

Page 17: ... FLT ALARM No AC mains supply FMAIN fuse failure F02 AUX1 fuse fail PSU FLT ALARM Blown FAUX1 fuse AUX2 fuse fail Blown FAUX2 fuse F03 BAT fuse fail APS FLT ALARM Blown FBAT fuse Short circuit in the battery circuit Short circuit in the AUX output circuit F04 Output overload PSU FLT ALARM PSU overload Section 6 9 F05 Battery undercharged APS FLT ALARM Spent batteries Undercharged batteries Section...

Page 18: ...C voltage PSU FLT ALARM Mains supply below 195 V AC Section 6 2 5 F21 PSU cover opened PSU FLT ALARM Section 6 6 F50 F54 Internal supply fail PSU FLT ALARM service codes F60 No communication PSU FLT ALARM no communication with LCD panel F61 F64 Control panel fail PSU FLT ALARM service codes F65 Access unlocked passwords unlocked Table 9 List of PSU message codes Message code Description I00 Power ...

Page 19: ...uration The PSU is equipped with a configuration menu that allows to configure the settings by changing or the activation of some of its parameters The figure illustrating the configuration menu structure is shown below Fig 9 The PSU configuration menu ...

Page 20: ...mission trS Determines the speed of communication 9 6k 115 2k factory setting Section 6 3 7 Parity of the transmission trP Determines the method of communication 8N2 8E1 factory setting 8O1 Section 6 3 8 6 3 1 Performing battery test tSt The tSt menu activates the test of the batteries see section 7 5 connected to the power supply If the test is negative it is indicated by the appropriate message ...

Page 21: ...ftmost buttons on the LED panel the tst parameter will be displayed use the or buttons to display the Eto parameter press OK The current status of the relay will be displayed use the or buttons to in order to set the status On relay on OFF relay off press OK relay output status is changed in order to return to the main menu simultaneously press the rightmost and leftmost buttons on the LED panel 6...

Page 22: ...ndicated acoustically The frequency and number of signals depend on the type of event Table 11 Acoustic indication No Description Event 1 1 signal every 10s battery mode 230 V power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals battery mode The PSU will be disconnected because of the battery d...

Page 23: ...ay if no buttons are pressed within 5 minutes If the display is in the blackout mode pressing any button will reactivate the display simultaneously press the rightmost and leftmost buttons on the LED panel the tSt parameter will be displayed use the or buttons to display the dIS parameter press OK The current status will be displayed use the or buttons in order to set the status On dimmer on OFF d...

Page 24: ...ter press OK The current address of the PSU will be displayed use the or buttons in order to set the address 1 247 address of the PSU during the communication with the computer confirm by pressing OK in order to return to the main menu simultaneously press the rightmost and leftmost buttons 6 3 7 Setting the transmission speed trS applies to cooperation with PowerSecurity All the parameters respon...

Page 25: ...the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settings simultaneously press the rightmost and leftmost buttons The tSt parameter will be displayed use the or buttons to display the ...

Page 26: ...U FLT output indicating PSU failure The output indicates the PSU failure Under normal status during correct operation the output is closed In case of PSU failure it will switch into the open position Failure can be triggered by the following events UAUX1 AUX2 output voltage below 26 V UAUX1 AUX2 output voltage over 29 2 V battery charging circuit failure blown FAUX1 or FAUX2 fuse exceeding the rat...

Page 27: ...f the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC outputs open collector or relay outputs can be used as the source of the signal Fig 12 Examples of connections In the option with external switch the V EXT jumper which polarises the EXT IN input circuit and is required in such configuration must be on The EXTi input has been adjus...

Page 28: ...ircuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting location is provided within the housing see Fig 4 The figure below shows the connection between the power supply fuse module and receivers Fig 14 The connection of fuse module When installing the fuse ...

Page 29: ... time and overload level microprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT and ALARM technical outputs 6 10 Indication of exceeding Imax a current Exceeding the Imax a output current during the power supply operation is indicated by the microprocessor using the LED OVL li...

Page 30: ... Deep discharge battery protection UVP The PSU is fitted with the disconnection system and the battery discharge indication If the voltage at the battery terminals drops below 20 V 0 2 V during battery assisted operation acoustic indication will be activated and the batteries will be disconnected within 15s The batteries are reconnected to the power supply unit automatically once the 230 V mains s...

Page 31: ...in battery mode should be limited Required minimum battery capacity to work with the PSU can be calculated with the following formula QAKU 1 25 Id Iz Td Ia Iz Ta 0 05 Ic where QAKU The minimum battery capacity Ah 1 25 the factor related to the decrease in battery capacity due to aging Id the current drawn by the load during inspection A Iz PSU current consumption A Td required inspection time h Ia...

Page 32: ...ower supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 7 8 8 1 Communication via the USB TTL interface The easiest way of communication between the PSU and the computer is provided by the USB TTL INTU interface This interface allows direct connection between the computer and the PSU and is recognizable by the operating sy...

Page 33: ... against adverse environmental conditions Fig 17 Ethernet network communication using the RS485 INTRE interface 8 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequency band according to the IEEE 802 11 bgn standard The WiFi INTW interface shall be mounted in a selected...

Page 34: ...st adverse environmental conditions Fig 19 The Wi Fi communication using the RS485 WIFI INTRW interface 8 4 RS485 network communication Another type of network communication is the RS485 communication using two wire transmission path To achieve this kind of data exchange the PSU should be equipped with the additional RS485 TTL INTR interface converting data from the PSU into the RS485 standard and...

Page 35: ...er supplies in case of failures the backlight changes accordingly in both the manager window and the Windows taskbar In addition the program allows you to download the operation history of the power supply the history of events and visualization in the form of charts and tables The downloaded data can be saved The program also provides functionality in the form of a remote battery test The result ...

Page 36: ...ynoptic board or the list mode This is especially useful when the PowerSecurity program works with a large number of power supplies The application enables both visualization and analysis of read data Exceeding the permissible parameters is signaled by a change in color of the relevant field to yellow and a flashing indicator light It is possible to view the current power supply parameters histori...

Page 37: ... 3 A current limit FAUX melting fuse failure requires fuse replacement Overload protection OLP Hardware Software Battery circuit protection SCP and reverse polarity connection F10 A current limit FBAT melting fuse failure requires fuse replacement Deep discharge battery protection UVP U 20 V 2 disconnection BAT of the batteries TAMPER output indicating enclosure opening Microswitch TAMPER Technica...

Page 38: ...ls Mains supply Ф0 51 2 AWG 24 12 Outputs Ф0 51 2 AWG 24 12 Battery outputs BAT Ф6 M6 0 2 5 Cable glands PG9 cable diameter Ф4 8mm PG11 cable diameter Ф5 10mm Notes The enclosure does not adjoin the mounting surface so that cables can be led Convection cooling Table 14 Safety of use Protection class EN 60950 1 2007 I first Protection grade EN 60529 2003 IP42 Insulation electrical strength between ...

Page 39: ...ir if it is used in dusty conditions In case of fuse replacement use only compatible replacement parts Technical inspections should be carried out not less frequently than once per year During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 CAUTION According to the recommendations of the CNBOP and V...

Page 40: ...llect such WEEE separately CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar sp j Siedlec 150 32 744 Łapczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl ...

Reviews: