5.7. Technical outputs - connection with DSO controller.
The technical outputs are connected with wires to the Alarm System controller. The wires can be used to
connect the controller to the appropriate connector in order to monitor technical signals.
Fig. 23. The scheme of connecting the technical outputs to the DSO controller.
The configuration of A1, A2, and A3 outputs, depending on the functions performed, shall be made in the
controller itself and using a dedicated software.
5.8. Overload/short circuit of the power supply output.
In the event of short-circuit in any of the OUT1 ... OUT9 amplifier outputs, the controller output, or router
outputs, the corresponding fuse in the circuit is permanently blown. Restoration of the voltage at the output requires
fuse replacement (use a replacement of the same parameters).
The PSU has output overload detection function. In exceptional circumstances, if the power supply is
overloaded and the output voltage of the power supply drops below 20V, the power supply will disconnect all power
outputs. The „OFF” parameter will be displayed Then, make sure that any of the amplifiers is not supplied from the
PSU during normal operation (at 230V mains voltage) and RESET the power supply (turn the power off and on).