Pulsar Blue Power PSBS 5012E Manual Download Page 4

www.pulsar.pl                                                       

PSBS5012E                                                                

BLUE POWER

     

 

1.3 Description of components and power supply terminals (Table 1, Fig.2). 
 

Table 1. Components of the Power supply PCB (Printed Circuit Board) (see Fig. 2). 

Component 

no. 

Description 

 

P

BAT 

Jumper 

– configuration of discharged battery disconnection system (UVP)  

 

P

BAT

 = 

 discharged battery disconnection system OFF 

 

P

BAT

 = 

  discharged battery disconnection system ON 

 

T

AC

 Jumper

- setting the delay time for AC power failure indication 

 

T

AC

 = 

 delay time T= 60s 

 

T

AC

 = 

 delay time T= 10s 

Description: 

 jumper on, 

  jumper off

 

 

START

 button (running the PSU from the battery) 

 

V

ADJ

 potentiometer,

 

DC 12 

÷ 14,5V voltage adjustment 

 

F

BAT

 

fuse in the battery circuit, F6,3A / 250V 

 

Terminals: 
~AC~    

– AC power input 

EPS 

– technical output of AC power failure indication 

 

 

hi-Z state 

= AC power failure 

 

 

 

0V state  

= AC power - O.K. 

PSU

  

– technical output of PSU failure indication 

 

 

hi-Z state 

= failure 

 

 

0V state  

= PSU status O.K.

  

LoB

 

– technical output of low battery voltage indication 

 

 

hi-Z state 

= battery voltage U

BAT

 <11,5V 

 

 

0V state 

= battery O.K.  

+BAT-   

 

terminals for battery connection 

+AUX-  

–DC power output, (+AUX= +U, -AUX=GND) 

Description: hi-Z 

– high impedance, 0V – connection to the ground GND 

 

LEDs  

– optical indication:

 

AC  

– AC power

  

LB  

– battery charging 

AUX  

– output voltage DC 

 

Optional, external optical indication output terminal

 

 

I

BAT 

Jumper; 

- battery charging current configuration 

 

J1= 

  J2= 

  J3= 

   Ibat =0,5A 

 

J1= 

  J2= 

  J3= 

   Ibat =1A 

 

J1= 

  J2= 

  J3= 

   Ibat =2A 

 

J1= 

  J2= 

  J3= 

   Ibat =3A   

Description: 

 jumper on, 

  jumper off 

 

 

Fig. 2. The view of the Power supply PCB. 

Summary of Contents for Blue Power PSBS 5012E

Page 1: ...PSBS 5012E v 1 1 PSBS 13 8V 5A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 7 from 03 11 2016 Supercedes edition 6 from 01 06 2016...

Page 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Page 3: ...BS 13 8V 4x1A 40Ah PSBS 5012E LB4 4x1A AWZ575 or AWZ576 40Ah 3 Buffer power supply PSBS 13 8V 8x0 5A 40Ah PSBS 5012E LB8 8x0 5A AWZ578 or AWZ580 40Ah 4 Buffer power supply PSBS 13 8V 16x0 3A 40Ah PSBS...

Page 4: ...n the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure i...

Page 5: ...use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 0 57A 230V AC PSU s power 76W Efficiency...

Page 6: ...L state 0V failure hi Z state delay time 10s 60s 20 jumper selectable TAC OC type 50mA max Normal operation L state 0V failure hi Z state OC type 50mA max Normal operation UBAT 11 5V L state 0V failur...

Page 7: ...Output current 3 5A 2A battery charging 4 Output current 2 5A 3A battery charging Total current battery is max 5 5A The power supply is designed for a continuous operation and is not equipped with a p...

Page 8: ...BAT jumper is OFF 8 Mount the battery in the battery compartment of the enclosure Fig 3 Connect the batteries with the PSU paying special attention to the correct polarity 9 Switch on the 230V AC supp...

Page 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Page 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Page 11: ...equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they...

Reviews: