Pulsar Blue Power PSBS 5012E Manual Download Page 10

www.pulsar.pl                                                       

PSBS5012E                                                                

BLUE POWER

     

 

10 

4. Service and operation. 

 
4.1  Overload or short-circuit of the power supply output (SCP activation). 

            The AUX output of the PSU is protected against short-circuit by

 

PTC polymer fuse. If the power supply load 

current exceeds Imax. (110% ÷ 150% @ 25°C of the PSU power), automatic disconnection of the output voltage, 
indicated  by  switching  off  the  green  LED,  takes  place.  To  restore  the  voltage  at  the  output,  disconnect  the  load 
from the power supply output for approximately 1 minute. 
 

In case of a short-circuit at the AUX, BAT output or reverse battery connection, the F

BAT

 fuse in the battery 

circuit becomes permanently damaged. The voltage restoration at the BAT output requires fuse replacement. 

 

4.2  Running the PSU from the battery. 

 

The power supply is equipped with the button on the PCB allowing to run the PSU from the battery, when 

needed. To do that, press and hold the 

START

 button on the unit board for 1 second. 

 

4.3  Deep discharge battery protection UVP. 

The  power  supply  is  equipped  with  deep  discharge  battery  protection  (UVP).  If  the  voltage  at  the  battery 

terminals drops below 1

0V±0.5V during battery-assisted operation, the batteries will be disconnected. 

The battery 

protection is on when the P

BAT 

jumper is off.

 

 

Caution.  

It is not recommended to disable  UVP since deep  discharge of the batteries reduces their ability to 
store energy, their capacity and lifetime. 

 
 

4.4  Maintenance. 

All  maintenance  procedures  can  be  performed  after  disconnecting  the  power  supply  from  the  power 

network.  The  PSU  does  not  require  any  specific  maintenance;  however,  its  interior  should  be  cleaned  with 
compressed air if used in dusty conditions. In case of fuse replacement, use only compatible replacement parts. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Blue Power PSBS 5012E

Page 1: ...PSBS 5012E v 1 1 PSBS 13 8V 5A 65Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 7 from 03 11 2016 Supercedes edition 6 from 01 06 2016...

Page 2: ...iption 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Power supply operati...

Page 3: ...BS 13 8V 4x1A 40Ah PSBS 5012E LB4 4x1A AWZ575 or AWZ576 40Ah 3 Buffer power supply PSBS 13 8V 8x0 5A 40Ah PSBS 5012E LB8 8x0 5A AWZ578 or AWZ580 40Ah 4 Buffer power supply PSBS 13 8V 16x0 3A 40Ah PSBS...

Page 4: ...n the battery circuit F6 3A 250V Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure i...

Page 5: ...use Table 5 Operation parameters Table 6 Table 3 Electrical parameters PSU type A EPS External Power Source Mains supply 230V AC 50Hz 15 10 Current consumption 0 57A 230V AC PSU s power 76W Efficiency...

Page 6: ...L state 0V failure hi Z state delay time 10s 60s 20 jumper selectable TAC OC type 50mA max Normal operation L state 0V failure hi Z state OC type 50mA max Normal operation UBAT 11 5V L state 0V failur...

Page 7: ...Output current 3 5A 2A battery charging 4 Output current 2 5A 3A battery charging Total current battery is max 5 5A The power supply is designed for a continuous operation and is not equipped with a p...

Page 8: ...BAT jumper is OFF 8 Mount the battery in the battery compartment of the enclosure Fig 3 Connect the batteries with the PSU paying special attention to the correct polarity 9 Switch on the 230V AC supp...

Page 9: ...hort circuit at the output Output overload DC DC voltage converter failure Under voltage protection activation LoB output indicating low battery voltage The output indicates low battery voltage Under...

Page 10: ...e power supply is equipped with the button on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge...

Page 11: ...equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they...

Reviews: