background image

www.pulsar.pl 

 

 

 

 

PSBS10A12D 

 

 

 

 

 
 

 

Fig. 4. Electrical diagram of the OC outputs. 

 

4. Operation and use. 
 

4.1 Overload or short circuit of the PSU output  
The output circuit of the PSU is equipped with the electronic current protection. If the output voltage value 

exceeds the acceptable threshold – Imax, the PSU output will be disconnected. The disconnection will be indicated 
by the  O1, O2, O3 and AUX  diodes going out. Reactivation of the voltage will be automatic after disconnecting the 
receivers from the output. 

Additionally, the AUX1, AUX2, AUX3 outputs are protected separately, with the use of PTC polyswitches. If 

the load exceeds 2,5A, there will  be an automatic disconnection of the output voltage indicated by the O1,  O2 or 
O3 green diode going out. Restoring of the output voltage requires cutting off the output load for at least 1 minute. 

In case of a short circuit at the AUX, BAT output (load: 200% ÷ 250% of the PSU power) or reverse battery 

connection, the F

BAT

 fuse in the battery circuit becomes permanently damaged and the restoration of the voltage at 

the BAT output requires the replacement of the fuse. 

 

 

4.2 Battery-assisted operation. 

 

In case of the main power outage, the device is immediately switched into a battery-assisted operation. 
In order to run the PSU from the battery only, connect the BAT connectors in accordance with the signs:  

+ BAT red to ‘plus’ and, - BAT black to 'minus’ then press the START button on the main board and hold it for 5 
seconds. 

 

 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system  (UVP),  configured  by 
the P

BAT 

jumper. The protection mode is off when the P

BAT

 jumper is removed. 

 

4.3 Maintenance  
 
Any and all maintenance operations may be performed following the disconnection of the PSU from the 

power supply network. The PSU does not require performing any specific maintenance measures. However, in 
case of dust, clean the interior with compressed air. In case of fuse replacement, use a replacement of the same 
parameters. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for BLUE POWER PSBS 10A12D

Page 1: ...PSBS 10A12D v 1 0 PSBS 13 8V 10A 40Ah Buffer switched mode power supply unit EN Edition 2 from 18 09 2012 Supersedes edition 1 from 02 03 2012...

Page 2: ...use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply...

Page 3: ...power supply unit PSBS 13 8V 3x5V 7 4V 12x0 5A 40Ah PSBS 10A12D 3xDCDC20 5V 7 4V 2A 3xLB4 12x0 5A AWZ574 or AWZ576 40Ah 1 2 Block diagram fig 1 Fig 1 Block diagram of the PSU 1 3 Description of PSU c...

Page 4: ...ck 12 FAC AC absence technical output OC type open collector hi Z level status AC power failure L level status AC supply 13 FPS technical output of the PSU operation status OC type open collector hi Z...

Page 5: ...on transformer 2 PSU board tab 1 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230 V AC power connector PE PE connector 6 Battery connectors...

Page 6: ...s automatic return after DC output circuit disconnection Over voltage protection OVP U 16 5V disconnection of the output voltage automatic return AUX disconnection Battery circuit protection SCP and r...

Page 7: ...holes of the enclosure The PSU supplies voltage of 13 8 V DC with current efficiency of 1 Output current 10A without a battery 2 Output current 9 3A 0 7A battery charge 3 Output current 7 9A 2 1A batt...

Page 8: ...the PCB of the module and indicate the PSU operation status AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode going...

Page 9: ...tput load 200 250 of the PSU power or reverse battery connection the FBAT fuse in the battery circuit becomes permanently damaged and the restoration of the voltage at the BAT output requires the repl...

Page 10: ...provide warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of the manufacturer 7 The repair period mentioned in item 6 may be p...

Reviews: