Pulsar AWZ 09123 Manual Download Page 6

 

2. 

Installation

 

2.1 Requirements. 

 

The buffer power-supply shall be mounted by the qualified installer having appropriate (required and necessary 

for  a  given  country)  permissions  and  qualifications  for  connecting  (operating)  230V  AC  installations  and  low-voltage 
installations.  The  device  shall  be  mounted  in  closed  rooms,  according  to  the  environment  class  II,  of  the  normal  air 
humidity (RH=90% max. without condensation) and the temperature within the range from -10°C to +40°C. The power-
supply shall operate in a vertical position so that free and convectional air flow through ventilating holes of the casing is 
guaranteed.  

Before  installation  is  started,  the  balance  of  the  power-supply  load  shall  be  performed.  During  the  normal 

operation,  the  sum  of  currents  collected  by  receivers  shall  not  exceed

  I=3A  (P=36W  max.).  It  is  acceptable  to 

change values of fuses to other than original, if not all outputs of power supply are used and Pmax is not 
exceeded. 

 
As the power-supply is designed for a continuous operation and is not equipped with a power-switch, therefore 

an appropriate overload protection in the power supply circuit shall be guaranteed. Moreover, the user shall be informed 
about the method of isolation of the power supply from the power voltage (usually through assignment and marking of 
an  appropriate  fuse  in  the  fuse-box).  The  electrical  system  shall  be  made  in  accordance  with  valid  standards  and 
regulations. 
 

2.2 Installation procedure. 

 

1. Before installation is started, the voltage in the 230V power-supply circuit shall be isolated. 

2. The power-supply shall be mounted in a selected location and connection cords shall be lead.  
3. Remove the power fuse protecting the power supply circuit.  
4. The power cables (~230V AC) shall be connected to L-N terminals of the power supply.  The earth conductor shall be 

connected to the terminal marked by the earth symbol 

. The connection shall be made by means of a three-core cable 

(with a yellow and green PE protection wire). The power cables shall be lead to appropriate terminals of the connection 
board through bushing.

 

The  circuit  of  the  shock  protection  shall  be  performed  with  a  particular  care,  i.e.  the  yellow  and  green 
protection wire of the power cable shall be connected from one side to the terminal marked by the symbol of 

    in  the  casing  of  the  power-supply.  Operation  of  the  power-supply  without  the  properly  made  and  fully 

operational  circuit  of  the  shock  protection  is  UNACCEPTABLE!.  It  can  result  in  failure  of  devices  and  electric 
shock.  

 

 
5.  Connect  the  conductors  of  consumers  to: 

A1,  A2,    A3,    B1,  B2,  B3,  C1,  C2,  C3

    and 

GND 

x3  (maintaining 

polarization).

 

6. As there are significant voltage drops at the resistance of power cables of receivers during installation, it is possible to 
adjust a voltage value by potentiometer 

— 

A - outputs A1, A2, A3 

— 

B - outputs B1, B2, B3 

— 

C - outputs C1, C2, C3

 

7. Insert the fuse into the power supply circuit and switch on power. 
8. Check the optical signaling of the power supply. 
9. After installation is completed and operation of the power-supply is checked, the casing can be closed.  

 

3. The power supply unit operation indication.

 

The power-supply is equipped with the optical signaling of operation modes. Voltage at the outputs of the power 

supply is indicated by lighting of green LEDs at the front panel of the device. 

 
3.1 Optical signaling (fig.3.). 

 

 

Green 

LEDs A1….C3

 indicate the power-supply mode at outputs: A1…..C3 

If power supply is lost at the output (fuse blow), a correspondent LED stops lighting 
(A1 for A1 output, etc.) 

 

The red 

LED AC

 indicates supply status at power supply unit input. In case of supply loss at input (lack of 

230V AC, F failure) the diode stops lighting. 
 

Summary of Contents for AWZ 09123

Page 1: ...PSU S 12V L 3A 9 FTA PTC TR MC AWZ 09123 v 1 0 Linear stabilized power supply unit EN Edition 1 from the 30th January 2011 Supercedes edition _____________...

Page 2: ...and operation 4 1 Short circuit protection 4 2 Overload protection 4 3 Maintenance 1 Technical description 1 1 General description Buffer power supply unit is designed for the supply of equipment req...

Page 3: ...circuit DC 3 P A B C voltage adjustments output voltage regulation for a particular group 4 OUTPUTS of power supply unit connector Tab 2 5 F fuse in the power supply circuit 230V AC 6 L N power suppl...

Page 4: ...4 Fig 2 The view of the power supply unit...

Page 5: ...status AC normal status lights failure status does not light OVP overvoltage protection status normal status lights failure status does not light Fuse F Bezpiecznik FA1 FC3 T 1A 250V F 500mA 250V Mech...

Page 6: ...230V AC shall be connected to L N terminals of the power supply The earth conductor shall be connected to the terminal marked by the earth symbol The connection shall be made by means of a three core...

Page 7: ...of about 1 min It is acceptable to change values of fuses to other than original if not all outputs of power supply are used and Pmax is not exceeded 4 2 Procedure in case of overload activation of OL...

Page 8: ...n item 5 may be prolonged if there is no technical capability to carry out the repairs and in the case that the equipment has been accepted conditionally due to the failing of the warranty terms by th...

Reviews: